{"id":4244,"date":"2026-09-25T00:00:00","date_gmt":"2026-09-25T00:00:00","guid":{"rendered":"https:\/\/chac-electric.com\/?p=4244"},"modified":"2026-10-19T03:37:15","modified_gmt":"2026-10-19T03:37:15","slug":"%d9%85%d8%a7-%d9%87%d9%8a-%d8%aa%d8%b7%d8%a8%d9%8a%d9%82%d8%a7%d8%aa-%d9%85%d9%86%d8%ad%d9%86%d9%8a%d8%a7%d8%aa-%d8%a7%d9%86%d9%82%d8%b7%d8%a7%d8%b9-%d8%a7%d9%84%d9%85%d9%83%d9%88%d9%86%d8%a7%d8%aa","status":"publish","type":"post","link":"https:\/\/chac-electric.com\/ar\/blog\/what-is-type-b-mcb-tripping-curve-applications-and-selection\/","title":{"rendered":"\u0645\u0627 \u0647\u0648 \u0646\u0648\u0639 \u0627\u0644\u0645\u0643\u0648\u0646\u0627\u062a \u0627\u0644\u0645\u064a\u0643\u0627\u0646\u064a\u0643\u064a\u0629 \u0627\u0644\u0645\u062a\u0639\u062f\u062f\u0629 (MCB) \u0645\u0646 \u0627\u0644\u0646\u0648\u0639 B\u061f \u0645\u0646\u062d\u0646\u0649 \u0627\u0644\u0627\u0646\u0642\u0637\u0627\u0639 \u0648\u0627\u0644\u062a\u0637\u0628\u064a\u0642\u0627\u062a \u0648\u0627\u062e\u062a\u064a\u0627\u0631\u0647\u0627"},"content":{"rendered":"<p>A <strong>\u0642\u0641\u0644 \u0627\u0644\u062a\u064a\u0627\u0631 \u0627\u0644\u0645\u062a\u0631\u062f\u062f \u0645\u0646 \u0627\u0644\u0646\u0648\u0639 B<\/strong> is a miniature circuit breaker with a B time-current characteristic. Its instantaneous magnetic operating band is commonly 3\u20135 times rated current in the IEC-based product families covered by the manufacturer\u2019s curve. That band is not the normal load allowance, and \u201cType B\u201d here does not mean a Type B residual-current device. Select the breaker from the load\u2019s starting behavior and the circuit\u2019s fault-clearing requirements together.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/09\/what-is-type-b-mcb-tripping-curve-applications-and-selection-featured-v2-200k.webp\" alt=\"\u0645\u0627 \u0647\u064a \u062a\u0637\u0628\u064a\u0642\u0627\u062a \u0645\u0646\u062d\u0646\u0649 \u0627\u0646\u0642\u0637\u0627\u0639 \u0627\u0644\u062a\u064a\u0627\u0631 \u0627\u0644\u0643\u0647\u0631\u0628\u0627\u0626\u064a \u0645\u0646 \u0627\u0644\u0646\u0648\u0639 B \u0648\u0627\u062e\u062a\u064a\u0627\u0631\u0647\u061f\" loading=\"eager\"\/><\/p>\n<h2 id=\"understand-the-magnetic-band-and-the-thermal-curve\">Understand the magnetic band and the thermal curve<\/h2>\n<p>A thermal-magnetic MCB responds to sustained overload through its thermal mechanism and to sufficiently high current through its magnetic mechanism. Schneider Electric\u2019s Acti9 FAQ gives a B-curve band of 3\u20135 times rated current. For a hypothetical B20 device using that characteristic, the band corresponds to 60\u2013100 A. This is an illustration of the multiplier, not a guaranteed trip point at every temperature or duration.<\/p>\n<p>Below the magnetic region, the thermal curve still matters. A breaker carrying somewhat more than its rating does not necessarily open instantly. Read the complete manufacturer time-current curve, including tolerances and test conditions, when checking overloads and disconnection time.<\/p>\n<h2 id=\"check-the-actual-inrush-before-calling-a-load-low-inrush\">Check the actual inrush before calling a load low-inrush<\/h2>\n<p>B-curve devices are often considered for resistive loads and circuits with modest starting currents. \u201cLighting,\u201d however, is not a complete electrical description: a bank of LED drivers can draw a short charging pulse at switch-on. Obtain the driver\u2019s inrush information and any manufacturer limit on the number of drivers per protective device.<\/p>\n<p>The useful design question is whether the combined startup stays within the breaker\u2019s acceptable operating envelope. A low running wattage does not prove low inrush. Group switching, simultaneous restart after a power failure and replacement driver types can all change that envelope without changing the circuit\u2019s everyday current.<\/p>\n<h2 id=\"compare-b-and-c-curves-against-the-fault-conditions\">Compare B and C curves against the fault conditions<\/h2>\n<p>\u0627\u0644 <strong>B-curve tripping characteristic<\/strong> has a lower magnetic threshold than the C characteristic in the cited Acti9 guidance, which gives C as 5\u201310 times rated current. Moving to C can tolerate a larger startup pulse, but it also changes the current needed for rapid magnetic operation. Check the fault path and required disconnection time before accepting that change.<\/p>\n<p>For a long cable run, inspect the minimum fault-current condition as well as the maximum fault level at the board. A device must interrupt the largest credible fault within its rating and operate quickly enough at the fault conditions relevant to the installation. Raising the threshold solely to stop a nuisance trip can leave that second check unresolved.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/09\/what-is-type-b-mcb-tripping-curve-applications-and-selection-product-200k.webp\" alt=\"CHAC \u0645\u0627 \u0647\u064a \u0645\u0646\u062d\u0646\u0649 \u062a\u0633\u0627\u0631\u0639 \u0627\u0644\u0645\u0643\u0648\u0646\u0627\u062a \u0627\u0644\u0645\u064a\u0643\u0627\u0646\u064a\u0643\u064a\u0629 \u0645\u0646 \u0627\u0644\u0646\u0648\u0639 B \u0648\u062a\u0637\u0628\u064a\u0642\u0627\u062a\u0647\u0627 \u0648\u0627\u062e\u062a\u064a\u0627\u0631\u0647\u0627\" loading=\"lazy\"\/><\/p>\n<h2 id=\"keep-the-curve-letter-separate-from-other-ratings\">Keep the curve letter separate from other ratings<\/h2>\n<p>A B marking does not establish breaking capacity, AC\/DC suitability, residual-current sensitivity or arc-fault detection. Those are separate characteristics. In particular, a Type B RCD classification concerns residual-current waveforms, whereas a B-curve MCB characteristic concerns overcurrent operation. Similar wording is not evidence of equivalent protection.<\/p>\n<p>Review the available curves in CHAC\u2019s <a href=\"https:\/\/chac-electric.com\/ar\/%d9%82%d8%a7%d8%b7%d8%b9-%d8%a7%d9%84%d8%af%d8%a7%d8%a6%d8%b1%d8%a9-%d8%a7%d9%84%d9%85%d8%b5%d8%ba%d8%b1\/\">miniature circuit breaker range<\/a> and the exact variant on the <a href=\"https:\/\/chac-electric.com\/ar\/product\/cqb2-63-miniature-circuit-breaker\/\">\u0635\u0641\u062d\u0629 CQB2-63 MCB<\/a>. Confirm the model curve and rating instead of transferring a competitor\u2019s threshold or application approval to a CHAC catalogue number.<\/p>\n<h2 id=\"diagnose-unwanted-trips-before-changing-the-breaker\">Diagnose unwanted trips before changing the breaker<\/h2>\n<p>Record when the trip occurs, which loads switch together and whether the event follows maintenance or a change of equipment. Immediate startup trips and delayed overload trips call for different investigations. Check the circuit and connections before assuming the selected curve is the only problem.<\/p>\n<p>A replacement <strong>MCB curve selection<\/strong> should document the load inrush, cable protection and disconnection-time review. The <a href=\"https:\/\/chac-electric.com\/ar\/blog\/%d9%81%d9%84%d8%a7%d8%b4-%d9%83%d9%87%d8%b1%d8%a8%d8%a7%d8%a6%d9%8a-%d9%85%d8%b5%d8%ba%d8%b1-20-%d8%a3%d9%85%d8%a8%d9%8a%d8%b1\/\">20 A MCB selection guide<\/a> shows how the current rating and curve remain separate decisions. Keep that record so a later technician understands why the replacement was chosen.<\/p>\n<h2>Which part of the specification answers each question?<\/h2>\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Question<\/th>\n<th scope=\"col\">Relevant characteristic<\/th>\n<th scope=\"col\">Do not confuse it with<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Will it tolerate startup?<\/td>\n<td>Full time-current curve and load inrush<\/td>\n<td>Running current alone<\/td>\n<\/tr>\n<tr>\n<td>Can it clear the fault?<\/td>\n<td>Breaking capacity at the declared voltage<\/td>\n<td>The B curve letter<\/td>\n<\/tr>\n<tr>\n<td>Does it detect leakage?<\/td>\n<td>A separate residual-current function<\/td>\n<td>A Type B MCB marking<\/td>\n<\/tr>\n<tr>\n<td>Can it operate on DC?<\/td>\n<td>Explicit DC rating and wiring instructions<\/td>\n<td>Its AC trip curve<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<section id=\"faq\">\n<h2>\u0627\u0644\u0623\u0633\u0626\u0644\u0629 \u0627\u0644\u0634\u0627\u0626\u0639\u0629<\/h2>\n<h3>\u0645\u0627 \u0647\u0648 \u0646\u0637\u0627\u0642 \u0627\u0644\u0633\u0641\u0631 \u0644\u0628\u0637\u0627\u0642\u0629 MCB \u0645\u0646 \u0627\u0644\u0646\u0648\u0639 B\u061f<\/h3>\n<p>\u0648\u0641\u0642\u064b\u0627 \u0644\u0644\u0645\u0648\u0627\u0635\u0641\u0629 IEC 60898-1\u060c \u064a\u062a\u0645 \u062a\u062d\u062f\u064a\u062f \u0645\u0646\u0637\u0642\u0629 \u0627\u0644\u062a\u0634\u063a\u064a\u0644 \u0627\u0644\u0641\u0648\u0631\u064a\u0629 \u0639\u0627\u062f\u0629\u064b \u062d\u0648\u0644 3-5 \u0623\u0636\u0639\u0627\u0641 \u0627\u0644\u062a\u064a\u0627\u0631 \u0627\u0644\u0645\u0642\u062f\u0631\u060c \u0648\u0644\u0643\u0646 \u0627\u0644\u062d\u062f \u0627\u0644\u0623\u0642\u0635\u0649 \u0627\u0644\u0645\u062d\u062f\u062f \u0644\u0627\u062e\u062a\u0628\u0627\u0631\u0627\u062a \u0647\u0630\u0647 \u0627\u0644\u0645\u0646\u0637\u0642\u0629 \u0648\u0627\u0644\u0628\u064a\u0627\u0646\u0627\u062a \u0627\u0644\u062e\u0627\u0635\u0629 \u0628\u0627\u0644\u0645\u0646\u062a\u062c \u064a\u062a\u0645 \u062a\u062d\u062f\u064a\u062f\u0647\u0645\u0627 \u0648\u0641\u0642\u064b\u0627 \u0644\u0644\u0646\u0645\u0648\u0630\u062c \u0627\u0644\u0645\u0642\u062f\u0645.<\/p>\n<h3>When should I use a B-curve MCB?<\/h3>\n<p>Consider it where the load\u2019s inrush is compatible with the B characteristic and the circuit meets the required disconnection conditions. Resistive and some lighting circuits may fit, but LED drivers, transformers and other electronic loads need an actual inrush check.<\/p>\n<h3>\u0647\u0644 \u064a\u0645\u0643\u0646\u0646\u064a \u0627\u0633\u062a\u0628\u062f\u0627\u0644 \u0645\u0646\u062d\u0646\u0649 C \u0628\u0646\u0645\u0648\u0630\u062c B\u061f<\/h3>\n<p>\u0648\u0644\u0627 \u064a\u064f\u0633\u062a\u062e\u062f\u064e\u0645 \u0625\u0644\u0627 \u0628\u0639\u062f \u0627\u0644\u062a\u062d\u0642\u0642 \u0645\u0646 \u062a\u0627\u0631\u064a\u062e \u0627\u0644\u062d\u0648\u0627\u062f\u062b\u060c \u0648\u0638\u0631\u0648\u0641 \u0627\u0644\u0625\u0631\u0633\u0627\u0644 \u0627\u0644\u0639\u0631\u0636\u064a \u0648\u062a\u064a\u0627\u0631 \u0627\u0644\u062e\u0637\u0623. \u0642\u062f \u064a\u062d\u0633\u0646 \u0639\u062a\u0628\u0629 \u0645\u063a\u0646\u0627\u0637\u064a\u0633\u064a\u0629 \u0623\u062f\u0646\u0649 \u0645\u0646 \u0639\u0645\u0644\u064a\u0629 \u0625\u0632\u0627\u0644\u0629 \u0627\u0644\u062e\u0637\u0623\u060c \u0644\u0643\u0646\u0647\u0627 \u0642\u062f \u062a\u0633\u0628\u0628 \u0627\u0646\u0642\u0637\u0627\u0639 \u0627\u0644\u062a\u064a\u0627\u0631 \u0623\u062b\u0646\u0627\u0621 \u0628\u062f\u0621 \u0627\u0644\u062a\u0634\u063a\u064a\u0644.<\/p>\n<h3>\u0647\u0644 \u064a\u0639\u0646\u064a \u0627\u0644\u0646\u0648\u0639 B \u0623\u0646\u0651\u0647 \u0645\u062a\u0648\u0627\u0641\u0642 \u0645\u0639 DC\u061f<\/h3>\n<p>\u0644\u0627. \u201cB\u201d \u0647\u0648 \u062a\u0635\u0646\u064a\u0641 \u062f\u0627\u0626\u0645\u064a \u0627\u0644\u062a\u064a\u0627\u0631 \u0644\u0623\u0633\u0631\u0629 \u0645\u0642\u0627\u0648\u0645\u0627\u062a \u0627\u0644\u062a\u0628\u0627\u0637\u0624\u060c \u0648\u0644\u064a\u0633 \u062a\u0635\u0646\u064a\u0641\u064b\u0627 \u0644\u0644\u062c\u0647\u062f \u0627\u0644\u062f\u0627\u0626\u0631\u064a. \u064a\u064f\u0631\u062c\u0649 \u0627\u0644\u062a\u062d\u0642\u0642 \u0645\u0646 \u0627\u0644\u062c\u0647\u062f \u0648\u0627\u0644\u0642\u0637\u0628\u064a\u0629 \u0648\u0628\u064a\u0627\u0646\u0627\u062a \u0627\u0644\u0627\u062e\u062a\u0628\u0627\u0631 \u0627\u0644\u062f\u0627\u0626\u0631\u064a \u0628\u0634\u0643\u0644 \u0645\u0646\u0641\u0635\u0644.<\/p>\n<h3>What is the difference between B and C curve circuit breakers?<\/h3>\n<p>In the cited Acti9 guidance, B has a 3\u20135 times rated-current magnetic band and C has a 5\u201310 times band. Both also have thermal overload behavior. Choose using the exact model curve, load inrush and fault-clearing requirements rather than an application label alone.<\/p>\n<\/section>\n<h2>\u0627\u0644\u0645\u0631\u0627\u062c\u0639<\/h2>\n<ul>\n<li><a href=\"https:\/\/www.se.com\/au\/en\/faqs\/FA290880\/\" target=\"_blank\" rel=\"noopener noreferrer nofollow\">Schneider Electric: B, C and D characteristics for Acti9 MCBs<\/a><\/li>\n<li><a href=\"https:\/\/www.electrical-installation.org\/enwiki\/Practical_values_for_a_protective_scheme\" target=\"_blank\" rel=\"noopener noreferrer nofollow\">Schneider Electric Electrical Installation Guide: conductor protection<\/a><\/li>\n<\/ul>\n<p>For a model-specific review, <a href=\"https:\/\/chac-electric.com\/ar\/%d8%a7%d8%aa%d8%b5%d9%84-%d8%a8%d9%86%d8%a7\/\">\u0627\u062a\u0635\u0644 \u0628\u0640 CHAC Electric<\/a> with the circuit diagram, supply voltage, load details and destination-market requirements.<\/p>","protected":false},"excerpt":{"rendered":"<p>\u064a\u062a\u0636\u0645\u0646 \u0647\u0630\u0627 \u0627\u0644\u062f\u0644\u064a\u0644 \u0634\u0631\u062d\u064b\u0627 \u0645\u0641\u0635\u0644\u0627\u064b \u0644\u062a\u0642\u0646\u064a\u0627\u062a \u0642\u0641\u0644 \u0627\u0644\u062f\u0627\u0626\u0631\u0629 \u0627\u0644\u0635\u063a\u064a\u0631\u0629 \u0645\u0646 \u0646\u0648\u0639 DC\u060c \u0628\u0627\u0644\u0625\u0636\u0627\u0641\u0629 \u0625\u0644\u0649 \u0639\u0645\u0644\u064a\u0629 \u0627\u0644\u0627\u062e\u062a\u064a\u0627\u0631 \u0648\u0627\u0644\u0631\u0628\u0637 \u0648\u0627\u0644\u062a\u0646\u0633\u064a\u0642 \u0648\u0627\u0644\u062a\u062d\u0642\u0642 \u0645\u0646 \u0627\u0644\u0627\u0645\u062a\u062b\u0627\u0644 \u0627\u0644\u0644\u0627\u0632\u0645\u0629 \u0644\u0644\u0645\u0634\u062a\u0631\u064a\u0646 \u0627\u0644\u0643\u0647\u0631\u0628\u0627\u0626\u064a\u064a\u0646 \u062d\u0648\u0644 \u0627\u0644\u0639\u0627\u0644\u0645.<\/p>","protected":false},"author":1,"featured_media":4242,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[],"class_list":["post-4244","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":8}},"acf":[],"_links":{"self":[{"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/posts\/4244","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/comments?post=4244"}],"version-history":[{"count":4,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/posts\/4244\/revisions"}],"predecessor-version":[{"id":5174,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/posts\/4244\/revisions\/5174"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/media\/4242"}],"wp:attachment":[{"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/media?parent=4244"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/categories?post=4244"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/chac-electric.com\/ar\/wp-json\/wp\/v2\/tags?post=4244"}],"curies":[{"name":"\u0644\u0639\u0628 \u062c\u064a\u062f\u0629","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}