{"id":3915,"date":"2026-09-02T16:00:00","date_gmt":"2026-09-02T16:00:00","guid":{"rendered":"https:\/\/chac-electric.com\/?p=3915"},"modified":"2026-10-14T06:45:36","modified_gmt":"2026-10-14T06:45:36","slug":"what-is-a-contactor-in-hvac","status":"publish","type":"post","link":"https:\/\/chac-electric.com\/de\/blog\/what-is-a-contactor-in-hvac\/","title":{"rendered":"Was ist ein Kontaktor in der HVAC-Branche?"},"content":{"rendered":"<p>A burned contactor can seem to explain an HVAC shutdown, but replacing it does not establish why it failed. An unstable control supply, damaged termination, unsuitable switching duty, or a compressor fault may stress the replacement in the same way. The useful question is whether the device receives a valid command, closes correctly, and delivers power to a serviceable load. Those are separate checks, and confusing them can produce repeated parts costs and downtime. This guide explains what the contactor does, how qualified technicians distinguish control faults from contact and load faults, and what documentation supports a replacement decision.<\/p>\n<p>The short answer is that an HVAC contactor lets a low-power control circuit switch a compressor, condenser fan, heater, or pump circuit. Reliable diagnosis separates the coil command from the contact and load response. A replacement should match the verified coil voltage and frequency, pole arrangement, load-duty rating, switching rate, terminals, and environment. IEC 60947-4-1 provides a product-standard framework for contactors and motor-starters, not proof that any particular replacement suits the equipment. Have a qualified technician record the installed circuit requirements before selecting a part; a matching ampere number alone is not enough.<\/p>\n<figure class=\"article-hero\"><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/what-is-a-contactor-in-hvac-scene.webp\" alt=\"Qualifizierter Techniker inspiziert einen HVAC-Schalter in einem kommerziellen Schalttafelgeh\u00e4use.\"\/><figcaption>Application scene for documented electrical selection and verification.<\/figcaption><\/figure>\n<p>A contactor is an electrically operated switch designed for remote control. A thermostat, building-management controller, or safety chain commands its coil. In a conventional electromagnetic design, the mechanism then closes the main contacts that carry the higher current required by the load. This separation keeps compressor current out of delicate control devices and makes sequencing and interlocking practical.<\/p>\n<p>The basic idea is simple, but replacement errors occur because the power circuit and control circuit have different requirements. The voltage supplying the compressor need not be the voltage supplying its <a href=\"https:\/\/chac-electric.com\/de\/blog\/ac-contactor-coil-voltage-selection-oem-panels\/\">contactor coil<\/a>. Similar frames can also have different coil frequencies, motor ratings, auxiliary contacts, or environmental limits.<\/p>\n<h2>What Does an HVAC Contactor Do Inside the System?<\/h2>\n<h3>How does the coil turn a control signal into mechanical movement?<\/h3>\n<p>In a conventional <a href=\"https:\/\/chac-electric.com\/de\/blog\/schlieser-im-vergleich-zu-offner-schutz\/\">normally open<\/a> contactor, a spring holds the movable armature away from the magnetic core at rest. When the control circuit applies the specified voltage, the coil produces magnetic flux. The armature moves, contact pressure rises, and the main poles close. For many conventional AC coils, the apparent power required during pull-in differs from that required after the magnetic circuit is sealed; electronic coil designs may behave differently.<\/p>\n<p>That distinction explains why a coil data sheet may list both inrush VA and sealed VA. A control transformer selected only from steady-state consumption may not support simultaneous pull-in of several devices. Electronic control outputs can also have momentary-current limits. Check the exact coil data and the control-source capability rather than assuming all coils of the same voltage impose the same burden.<\/p>\n<h3>Why are main and auxiliary contacts not interchangeable?<\/h3>\n<p>Main contacts switch the compressor, fan, pump, or electric-heating circuit. Auxiliary contacts carry control signals for status feedback, electrical interlocking, or sequencing. Their normal state and ratings must match the original logic; an unused-looking auxiliary can be essential to a safety or staging sequence. An auxiliary-contact current rating is not authorization to use it in place of a main load pole.<\/p>\n<p>A contactor is not a complete protective device. Overload protection responds to sustained overcurrent, while a fuse or circuit breaker interrupts fault current. Those functions may be separate or integrated elsewhere in the equipment. The guide to <a href=\"https:\/\/chac-electric.com\/de\/blog\/overload-contactor-and-how-it-works\/\">overload contactors and motor protection<\/a> explains why switching and protection must be coordinated rather than treated as interchangeable.<\/p>\n<h2>How Should Technicians Diagnose an HVAC Contactor?<\/h2>\n<p>Safe <strong>contactor troubleshooting<\/strong> follows the signal through the circuit instead of jumping from a symptom to a part. A qualified technician first confirms the call for operation and the status of safeties. The next checks establish whether the correct voltage reaches the coil under the actual pull-in condition, whether the armature seats cleanly, and whether the closed contacts deliver the expected voltage to the load.<\/p>\n<p>Electrical compartments can contain hazardous voltage, stored charge, and automatic moving equipment. In covered US workplaces, <a href=\"https:\/\/www.osha.gov\/laws-regs\/regulations\/standardnumber\/1910\/1910.333\" rel=\"nofollow noopener\" target=\"_blank\">1910.333 Selection and use of work practices<\/a> requires exposed live parts to be deenergized unless the specified exceptions apply. Qualified-person restrictions and suitable protective measures govern work on energized parts. The observations below are diagnostic logic for trained personnel, not a live-work procedure.<\/p>\n<table>\n<thead>\n<tr>\n<th>Observed symptom<\/th>\n<th>Evidence to collect<\/th>\n<th>Possible fault families<\/th>\n<th>Why replacement alone may fail<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>No pull-in when cooling is requested<\/td>\n<td>Control command, safety-chain state, coil marking, and voltage at the coil<\/td>\n<td>Open safety, wiring fault, failed controller, open coil, or wrong coil<\/td>\n<td>The contactor may never receive a valid command<\/td>\n<\/tr>\n<tr>\n<td>Buzzing or rapid chatter<\/td>\n<td>Voltage before and during pull-in, transformer output, connections, and armature seating<\/td>\n<td>Undervoltage, excessive circuit drop, contamination, mechanical obstruction, or frequency mismatch<\/td>\n<td>A new coil can chatter under the same unstable supply<\/td>\n<\/tr>\n<tr>\n<td>Coil pulls in but the load does not start<\/td>\n<td>Line voltage, voltage delivered through each closed pole, protection state, and load condition<\/td>\n<td>Open or high-resistance contact, lost phase, protection operation, wiring fault, or failed load<\/td>\n<td>The compressor or upstream circuit may be the root cause<\/td>\n<\/tr>\n<tr>\n<td>Localized heating or discoloration<\/td>\n<td>Terminal condition, conductor suitability, torque history, current balance, and contact voltage drop<\/td>\n<td>Loose termination, overload, eroded contact, corrosion, or repeated chatter<\/td>\n<td>Heat damage can extend into conductors and the enclosure<\/td>\n<\/tr>\n<tr>\n<td>Load continues after the command ends<\/td>\n<td>Coil command after shutdown, mechanical release, and isolated contact condition<\/td>\n<td>Welded contacts, binding mechanism, back-fed control voltage, or logic fault<\/td>\n<td>The control circuit must be ruled out before condemning the device<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Why can a normal coil-voltage reading miss a pull-in problem?<\/h3>\n<p>A plausible unloaded reading does not establish that the control supply can deliver the coil&#8217;s pull-in burden. A reading taken only after the armature has seated can also miss a brief voltage dip. For an authorized diagnostic test, the qualified technician records the voltage at the coil during the command, pull-in, and holding state, then compares those distinct conditions with the exact manufacturer&#8217;s operating limits. There is no universal voltage tolerance that can replace the model&#8217;s documentation.<\/p>\n<p>If the voltage falls only during pull-in, the investigation shifts to the control transformer, simultaneous secondary loads, and the series devices or connections in the control path. Long conductors, poor connections, or a marginal controller output may contribute. If voltage remains within the specified limits but the armature fails to seat, mechanical condition and coil identity become more important. Neither result alone proves that the compressor is healthy.<\/p>\n<h3>What can contact voltage drop show that continuity cannot?<\/h3>\n<p>A deenergized continuity check can show that a contact closes, but it does not prove that it carries load without excessive resistance. During an authorized loaded test, the technician evaluates the voltage across each closed pole and any imbalance, using the manufacturer&#8217;s criteria where available. An abnormal result can involve contact erosion, contamination, insufficient pressure, or a damaged termination; it should be interpreted alongside load current rather than against an invented universal millivolt threshold.<\/p>\n<p>The timing matters too. Coil behavior during armature movement and load-side behavior after seating are different observations. Combining them into a single statement such as &#8220;voltage is normal&#8221; can conceal a control-supply dip or a contact fault.<\/p>\n<h3>Can noise come from something other than damaged contacts?<\/h3>\n<p>Dust, insects, corrosion, or debris on magnetic faces can obstruct closure. Loose mounting and equipment vibration may amplify hum. An AC coil intended for a different frequency may not operate as specified. Inspection should therefore cover the enclosure, mechanism, mounting, coil marking, ambient conditions, and moisture evidence, not just the visible contact faces. Noise alone is not a conclusive failure test.<\/p>\n<h2>What Determines Contactor Life in HVAC Service?<\/h2>\n<p>Manufacturers distinguish mechanical life from electrical life. Mechanical-life figures describe operation without the electrical wear caused by switching the rated load. Electrical life depends on the current and voltage being switched, load type, switching duty, and operating frequency. A catalog&#8217;s largest life figure may therefore describe conditions unlike the installed HVAC duty.<\/p>\n<h3>Why does switching duty matter more than frame amperes?<\/h3>\n<p>The utilization-category framework in <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/74487\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60947-4-1<\/a> distinguishes switching duties. AC-1 generally covers non-inductive or slightly inductive loads; AC-3 covers starting a squirrel-cage motor and switching it off while running; AC-4 covers more severe duties such as inching or plugging. A device&#8217;s AC-1 current cannot be assumed to equal its AC-3 motor rating.<\/p>\n<p>For a compressor, identify the rating the equipment manufacturer actually requires. North American definite-purpose contactor documentation may specify full-load amperes, locked-rotor amperes, horsepower, or resistive-load ratings. An IEC motor rating at another voltage, or a higher resistive-current label, does not by itself establish compressor-duty suitability. Compare the exact product&#8217;s declared duty, voltage, phases, starting demands, and conditions of use with the equipment instructions.<\/p>\n<h3>What should be recorded when a replacement fails again?<\/h3>\n<p>Repeated starts, abnormal starting duration, voltage problems, and motor overload are separate stresses. Schneider Electric&#8217;s <a href=\"https:\/\/www.electrical-installation.org\/enwiki\/Motor_protection_functions\" rel=\"nofollow noopener\" target=\"_blank\">Motor protection functions<\/a>, last edited August 5, 2026, identifies rapid-cycle lockout, long-start protection, overload protection, and voltage-related protection as distinct functions. This general guidance does not prove that a particular HVAC unit includes them; its diagram and controller documentation must show what is actually implemented.<\/p>\n<p>For repeat failures, retain the equipment and contactor identities, coil marking, failure time, command state, pull-in and holding observations, load-current findings, terminal condition, and relevant controller or protection events. Record whether the event follows a restart, a long idle period, simultaneous staging, or a protection operation. Comparing the failed and replacement devices with that event record is more useful than repeatedly increasing the contactor&#8217;s frame size. Compressor restart limits must come from its manufacturer, not a universal starts-per-hour rule.<\/p>\n<p>Contact welding and severe pitting are outcomes, not complete diagnoses. Supply disturbances, load faults, poor terminations, chatter, and an incorrect duty rating can leave similar evidence. Correcting the original stress is part of the repair. Where the design requires separate overload protection, a <a href=\"https:\/\/chac-electric.com\/de\/product\/thermostatische-uberlastschaltung-der-serie-cqr2\/\">thermal overload relay<\/a> must be selected and coordinated for the actual motor and starter; adding one is not a substitute for diagnosing a compressor fault.<\/p>\n<h3>When is a contact kit an acceptable repair?<\/h3>\n<p>Some industrial contactors have manufacturer-approved replacement coils or contact kits. Renewal can be reasonable when the exact design supports field service, the frame and arc-control parts remain undamaged, trained personnel follow the instructions, and post-service checks verify operation. The parts and device identity must remain traceable.<\/p>\n<p>Complete replacement may be necessary when the housing, mechanism, coil, terminals, or arc-control parts are compromised, or when authorized renewal parts are unavailable. Filing or sanding contact faces should not be treated as an approved repair unless the manufacturer explicitly permits that procedure. A visually cleaner surface does not establish restored contact geometry or rated performance.<\/p>\n<h2>How Do You Specify a Compatible Replacement?<\/h2>\n<p>A reliable replacement starts with the equipment wiring diagram and full markings on the installed device. A photo helps identify layout but cannot verify coil burden, motor duty, or conditions of use. If markings are damaged or conflict with the diagram, consult current equipment documentation rather than guessing from appearance.<\/p>\n<table>\n<thead>\n<tr>\n<th>Specification item<\/th>\n<th>What to record<\/th>\n<th>Risk if omitted<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Lastdienst<\/td>\n<td>Compressor, fan, heater or pump; motor data; starting method; applicable compressor, utilization or horsepower rating<\/td>\n<td>A resistive-load ampere value may be misapplied to a motor<\/td>\n<\/tr>\n<tr>\n<td>Main circuit<\/td>\n<td>Voltage, phase, frequency, poles, operational current, and protection arrangement<\/td>\n<td>Contacts may be underrated or the switching arrangement may differ from the equipment design<\/td>\n<\/tr>\n<tr>\n<td>Control circuit<\/td>\n<td>Coil voltage and frequency, inrush and holding characteristics, source capacity, suppression, and terminal layout<\/td>\n<td>The device may fail to pull in or exceed the controller&#8217;s output capability<\/td>\n<\/tr>\n<tr>\n<td>Switching pattern<\/td>\n<td>Starting frequency, operating sequence, interlocks, and auxiliary-contact states<\/td>\n<td>The selected duty may not cover the installed operation<\/td>\n<\/tr>\n<tr>\n<td>Installation environment<\/td>\n<td>Ambient limits, enclosure, moisture, contamination, vibration, altitude, conductors, and terminals<\/td>\n<td>Electrical or mechanical conditions may exceed the published limits<\/td>\n<\/tr>\n<tr>\n<td>Market documentation<\/td>\n<td>Destination, product standard, listing or certification scope, drawings, labels, and permitted replacement arrangements<\/td>\n<td>A physically compatible part may still be unacceptable for the equipment<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>The contactor must also fit the protection and isolation strategy. A disconnect may provide the designated isolation function, while a contactor provides commanded switching; neither role should be inferred solely from appearance. Review the load requirements using the same discipline described in <a href=\"https:\/\/chac-electric.com\/de\/blog\/choose-right-motor-contactor-industrial-needs\/\">choosing the right motor contactor<\/a>. The fuse or breaker, available fault current, and equipment short-circuit rating also need their own documented review.<\/p>\n<p>For an OEM or replacement program, approve a complete record rather than a shorthand cross-reference. A buyer evaluating an <a href=\"https:\/\/chac-electric.com\/de\/product\/hochleistungskontaktor-der-cqc1-serie-und-zubehorteile\/\"><strong>AC contactor replacement<\/strong><\/a> should confirm ratings for the intended voltage and duty, coil characteristics, accessories, mounting, terminal capacity, ambient limits, and required documentation. Track revisions across repeat orders so a coil or auxiliary-contact change is reviewed before it reaches the assembly line. A CHAC product-family page is a starting point for documentation, not evidence of interchangeability with an installed HVAC part.<\/p>\n<figure class=\"article-figure\"><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/what-is-a-contactor-in-hvac-product.webp\" alt=\"CHAC AC contactor product reference for a documented HVAC control application\"\/><figcaption>Product reference for project-specific low-voltage electrical selection.<\/figcaption><\/figure>\n<h2>Which Standards and Safety Rules Shape the Selection?<\/h2>\n<p>IEC 60947-4-1 covers electromechanical contactors and motor-starters within low-voltage switchgear and controlgear. It provides performance and verification requirements. A utilization-category designation does not itself prove third-party certification or compliance of the complete HVAC assembly.<\/p>\n<p><a href=\"https:\/\/www.shopulstandards.com\/ProductDetail.aspx?productId=UL60947-4-1_3_S_20220126\" rel=\"nofollow noopener\" target=\"_blank\">UL 60947-4-1<\/a> addresses contactors and motor-starters with North American requirements. US installation requirements must be checked against the locally adopted electrical code, equipment instructions, and any authority having jurisdiction. An IEC rating should not be presented as an automatic substitute for the documentation required for a North American assembly.<\/p>\n<p>Workplace safety is a separate obligation. Under OSHA 1910.333(b)(2), control devices and interlocks cannot be the sole means of deenergizing equipment. A thermostat set to OFF or an open contactor does not establish isolation. The qualified person must address all electrical energy sources, stored energy, lockout\/tagging requirements, and verification of the deenergized condition, including possible backfeed. These are US occupational requirements; other jurisdictions have their own applicable rules.<\/p>\n<h2>What Are the Most Common HVAC Contactor FAQs?<\/h2>\n<h3>What does an HVAC contactor do?<\/h3>\n<p>It lets a low-power control signal switch a higher-power compressor, fan, pump, or heater circuit. In a conventional electromagnetic design, the coil moves the mechanism while the main contacts carry the load current. Switching does not replace overload or short-circuit protection.<\/p>\n<h3>How can a technician tell whether the contactor is bad?<\/h3>\n<p>The qualified technician confirms the control command and coil behavior during pull-in and holding, evaluates closure and release, and checks the power delivered through the contacts. An open coil, welded contacts, or abnormal contact performance may support replacement, but control-supply, termination, protection, and load faults must also be evaluated.<\/p>\n<h3>Why does an HVAC contactor chatter?<\/h3>\n<p>Possible causes include coil undervoltage, excessive control-circuit drop, poor connections, obstructed magnetic faces, vibration, or an incorrect coil frequency. Noise alone does not identify the cause. The exact coil&#8217;s operating limits and the conditions during the event matter more than a normal reading taken at another time.<\/p>\n<h3>Can only the contacts be replaced?<\/h3>\n<p>Only when the manufacturer authorizes renewal for that design and provides the correct parts and procedure. Damage to the frame, coil, terminals, arc-control parts, or mechanism may require complete replacement. The circuit condition that caused the wear still needs investigation.<\/p>\n<h3>Does a replacement contactor only need the same amp rating?<\/h3>\n<p>No. The required coil voltage and frequency, poles, compressor or motor duty, operating frequency, auxiliary contacts, terminals, mounting, environment, and market documentation all matter. A higher resistive-current rating or similar physical size does not establish replacement suitability.<\/p>\n<h3>Can a contactor read the correct voltage but still fail to pull in?<\/h3>\n<p>Yes. An unloaded or holding-state reading may miss a brief control-voltage dip during pull-in, and a mechanical obstruction can prevent closure even with an adequate supply. Distinguishing those conditions requires model-specific data and qualified diagnosis, not homeowner testing inside an energized compartment.<\/p>\n<h3>Is it safe to push the contactor in manually to test the compressor?<\/h3>\n<p>No. Manual forcing can bypass the normal control and safety sequence and expose someone to energized parts or unexpected equipment operation. Leave internal testing to a qualified technician using the equipment instructions and applicable safe-work requirements; thermostat OFF is not verified electrical isolation.<\/p>\n<h2>Which Sources Support These Selection and Safety Principles?<\/h2>\n<ol>\n<li>International Electrotechnical Commission, <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/74487\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60947-4-1<\/a>, product-standard scope and utilization categories.<\/li>\n<li>UL Standards &amp; Engagement, <a href=\"https:\/\/www.shopulstandards.com\/ProductDetail.aspx?productId=UL60947-4-1_3_S_20220126\" rel=\"nofollow noopener\" target=\"_blank\">UL 60947-4-1<\/a>, North American contactor and motor-starter requirements.<\/li>\n<li>Schneider Electric, <a href=\"https:\/\/www.electrical-installation.org\/enwiki\/Motor_protection_functions\" rel=\"nofollow noopener\" target=\"_blank\">Motor protection functions<\/a>, updated August 5, 2026; general motor-protection guidance, not an HVAC model specification.<\/li>\n<li>Occupational Safety and Health Administration, <a href=\"https:\/\/www.osha.gov\/laws-regs\/regulations\/standardnumber\/1910\/1910.333\" rel=\"nofollow noopener\" target=\"_blank\">1910.333 Selection and use of work practices<\/a>, US occupational electrical work requirements.<\/li>\n<\/ol>\n<p>The replacement decision should start with the event and circuit requirements, not the appearance of the old part. First establish whether the command and control supply remain valid during pull-in; then evaluate the contact path, terminations, protection, and load. Select the replacement against the equipment&#8217;s required duty and exact coil data, and confirm the installation and documentation requirements before returning it to service. Repeated failure calls for finding the repeated stress, not simply increasing the ampere label. For a commercial HVAC or OEM application, the CHAC CQC6 <a href=\"https:\/\/chac-electric.com\/de\/product\/cqc6-series-industrial-ac-contactor-oem-manufacturer\/\"><strong>HVAC contactor<\/strong><\/a> product page provides a route to request model documentation and discuss the load, control, switching, and environmental requirements; it does not establish compatibility by itself.<\/p>","protected":false},"excerpt":{"rendered":"<p>Erfahren Sie, wie ein HVAC-Techniker Kompressoren und Ventilatoren steuert, wie Techniker Fehler diagnostizieren und was Sie \u00fcberpr\u00fcfen m\u00fcssen, bevor Sie ein Ersatzteil ausw\u00e4hlen.<\/p>","protected":false},"author":1,"featured_media":3913,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[91,113,114,115,116],"class_list":["post-3915","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog","tag-electrical-procurement","tag-hvac-contactor","tag-ac-contactor","tag-compressor-control","tag-hvac-maintenance"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":8}},"acf":[],"_links":{"self":[{"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/posts\/3915","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/comments?post=3915"}],"version-history":[{"count":8,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/posts\/3915\/revisions"}],"predecessor-version":[{"id":4792,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/posts\/3915\/revisions\/4792"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/media\/3913"}],"wp:attachment":[{"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/media?parent=3915"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/categories?post=3915"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/chac-electric.com\/de\/wp-json\/wp\/v2\/tags?post=3915"}],"curies":[{"name":"GUT GESPIELT","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}