CQM6E Electronic Adjustable MCCB OEM Manufacturer
The CQM6E Electronic Adjustable Molded Case Circuit Breaker provides advanced, tunable protection against overloads, short-circuits, and ground faults for currents from 10A to 1250A. The electronic trip unit allows precise adjustment of parameters like long-time delay, short-time delay, instantaneous, and ground fault settings. With 3 or 4 poles and breaking capacities up to 75kA, it complies with IEC/EN 60947 and GB/T 14048 standards. Accessory options include digital displays and communication modules for smart monitoring. Motorized or manual operations, 800V insulation, and tested life make it suitable for dynamic industrial and automation systems requiring flexibility and high selectivity.
IEC/EN 60947-2 (Interruptores automáticos)
IEC/EN 60947-3 (Aparamenta)
IEC/EN 60947-4 (Contactores y arrancadores de motores)
Características del producto
■ Precise Electronic Trip: Features an adjustable electronic release for highly accurate Long-Time, Short-Time, and Instaneous (L-S-I) protection.
■ Advanced Ground Fault Protection: Includes a dedicated ground fault (G) protection setting for enhanced system safety.
■ Visual Status Indication: Equipped with an intuitive control panel featuring a current light bar and clear indicators for overload and pre-alarm status.
■ Communication Ready: Provides the foundation for smart functionality, supporting integration with motorized operators for remote control.
Cumplimiento
Meets international and regional standards including
IEC/EN 60947-1(General Rules) GB/T 14048.1
IEC/EN 60947-2(Circuit-Breakers) GB/T 14048.2
IEC/EN 60947-3(Switchgear) GB/T 14048.3
IEC/EN 60947-4( Contactors & Motor-Starters) GB/T 14048.4
Lista de accesorios


Characteristic curve

Guía de selección

| Product code① | Shell frame grade② | Shell frame rating current optional designator③ | Breaking capacity④ | |||
| CQM6 | E | 160 | S | M | H | |
| Molded case circuit breaker | E Electronically Adjustable |
160 | 160 | / | 50/35 | 50/50 |
| 250 | 250 | / | 50/35 | 50/50 | ||
| 630 | 630 | 35/25 | 50/35 | 75/75 | ||
| 800 | 800 | 35/25 | 50/35 | 75/75 | ||
| 1250 | 1250 | 35/25 | 50/35 | 75/75 | ||
| Operating method ⑤ | Number of poles ⑤ | Método de desacoplador y accesorios internos ⑥ | Corriente nominal A ⑦ |
| P | 4 | 300 | 160A |
| P: Motorized operation Z: Turn the handle W: Direct operation |
tripolar tetrapolar |
2: Intelligent disconnectors Note: The last two digits are the accessory code (see attachment) |
160, 250, 630, 800, 1250 |
| Función ⑧ | Four-pole products can be selected code ⑨ | Código especial ⑩ |
| 2 | A | I |
| 1: For power distribution 2: For motor protection |
A: N-pole without protection, can not be combined B: N-pole with protection, can be combined C: N-pole with protection, can be combined D: N-pole with protection, can not be combined Note: If the customer does not have a clear request, four-pole products will be defaulted to the B category |
I: Overload alarm non-trip function |
Main Technical Parameters
| Número de modelo | CQM6E-160 | CQM6E-250 | ||||
| Rated current of frame level Inm(A) | 160 | 250 | ||||
| Número de polos | 3, 4 | 3, 4 | ||||
| Rated current In(A),at 40℃,50℃,55℃ | 32, 63, 125, 160 | 160, 250 | ||||
| Rated operating voltage Ue(V),AC 50/60Hz | 400/415 | 400/415 | ||||
| Rated insulation voltage Ui (V) | 800 | 800 | ||||
| Rated impulse withstand voltage Uimp(KV) | 8 | 8 | ||||
| Breaking capacity designation | M | H | M | H | ||
| Short-circuit breaking capacity Icu/Ics(kA) | AC400/415V | 50/35 | 50/50 | 50/35 | 50/50 | |
| Rated short-time withstand current Icw(kA),1s | AC400/415V | 2 | 2 | 5 | 5 | |
| Selectivity category | B | B | B | B | ||
| Number of operating cycles (cycle) | ON | 6000 | 6000 | |||
| OFF | 10000 | 10000 | ||||
| Electronic decouping (adjustable) | Power distribution protection | ● | ● | ● | ● | |
| Motor protection | ● | ● | ● | ● | ||
| Accessory | Auxiliary contacts | ● | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ● | ||
| Shunt disconnect | ● | ● | ● | ● | ||
| Undervoltage detent | ● | ● | ● | ● | ||
| Manual operating mechanism | ● | ● | ● | ● | ||
| Motorized operating mechanism | ● | ● | ● | ● | ||
| Backplane wiring | ● | ● | ● | ● | ||
| Inserted | ● | ● | ● | ● | ||
| Coupling plate | ● | ● | ● | ● | ||
| Partition between phases | ● | ● | ● | ● | ||
| Overall dimensions (mm) (a-b-c-ca) | ![]() |
3P | 90-155-84-109 | 105-165-93-120 | ||
| 4P | 120-155-84-109 | 140-165-93-120 | ||||
Note:● for optional accessories;”-” for no optional accessories.
| Número de modelo | CQM6E-630 | CQM6E-800 | CQM6E-1250 | ||||||||
| Rated current of frame level Inm(A) | 630 | 800 | 1250 | ||||||||
| Número de polos | 3, 4 | 3, 4 | 3, 4 | ||||||||
| Rated current In(A), at 40℃, 50℃, 55℃ | 400, 630 | 630, 800 | 1000, 1250 | ||||||||
| Rated operating voltage Ue(V), AC 50/60Hz | 400/415 | 400/415 | 400/415 | ||||||||
| Rated insulation voltage Ui (V) | 800 | 800 | 800 | ||||||||
| Rated impulse withstand voltage Uimp(KV) | 8 | 8 | 8 | ||||||||
| Breaking capacity designation | S | M | H | S | M | H | S | M | H | ||
| Short-circuit breaking capacity Icu/Ics(kA) | AC400/415V | 35/25 | 50/35 | 75/75 | 35/25 | 50/35 | 75/75 | 35/25 | 50/35 | 75/75 | |
| Rated short-time withstand current Icw(kA), 1s | AC400/415V | 8 | 8 | 8 | 10 | 10 | 10 | 19.2 | 19.2 | 19.2 | |
| Selectivity category | B | B | B | B | B | B | B | B | B | ||
| Number of operating cycles(cycle) | ON | 3000 | 3000 | 1000 | |||||||
| OFF | 8000 | 8000 | 3000 | ||||||||
| Electronic decouping (adjustable) |
Power distribution protection | ● | ● | ● | ● | ● | ● | ● | ● | ● | |
| Motor protection | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Accessory | Auxiliary contacts | ● | ● | ● | ● | ● | ● | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Shunt disconnect | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Undervoltage detent | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Manual operating mechanism | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Motorized operating mechanism | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Backplane wiring | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Inserted | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Coupling plate | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Partition between phases | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
| Overall dimensions | ![]() |
3 P | 140-257-105-155 | 210-275-105-155 | 210-275-105-155 | ||||||
| (mm) (a-b-c-ca) | 4 P | 185-257-105-155 | 280-275-105-155 | 280-275-105-155 | |||||||
Note:● for optional accessories;”-” for no optional accessories.
Intlligent Release Adjustment Panel

1.Ir: Rated Current (Ir) Setting Dial
The setting dial for the rated current, applicable to 160-1250 frame sizes. The selectable settings on the front panel are:0.4, 0.45, 0.5, 0.55,0.6, 0.7,0.8,0.9,1.0, OFF.
2.Tr. Long-Time Delay (Tr) Setting Dial
The setting dial for the overload long-time delay. When the current passing through the circuit breaker reaches 1.5 times lr (×in), the breaker trips within the set time.
The selectable settings are: 8s, 12s, 16s, 24s, 32s, 48s, 64s, 96s, 128s,256s.
3.Isd: Short-Time Delay Current (Isd) Setting Dial
The setting dial for the short-time delay current multiplier. Selectable setting are: 2,3, 4, 5, 6,7,8, 9, 10, OFF. When a short-circuit current equal to the set value(×Ir, ×In) passes through the breaker, it will trip after a time delay.
4.Tsd: Short-Time Delay Operating Time (Tsd) Setting Dial
The setting dial for the short-time delay operating time. It is divided into inverse-time protection (2t ON) and definite-time protection (2t OFF). Selectable settings are: 0.05s, 0.1s, 0.15s, 0.2s, 0.3s. When a short-circuit current equal tosses through the breaker, it will trip within the set time.
5.li: Instantaneous Current (Ii)Setting Dial
The setting dial for the instantaneous current multiplier. Selectable settare:2,3,4,5,6,8,9,10,12. When a short-circuit current equal to the set value (×in) passes through the breaker, it will trip instantaneously.
6.Ip: Pre-alarm Current(Ip) Setting Dial
The setting dial for the pre-alarm current multiplier. Selectable settings are:60%,65%,70%, 75%, 80%, 85%, 90%, 95%, 100%, OFF. When the current passing through the breaker reaches the set value (×ir, ×in), the pre-alarm indicator light will illuminate.
7.Ig: Ground Fault Current (Ig) Setting Dial
The setting dial for the ground fault current multiplier. Selectable setting are:0.2,0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0,OFF. When the ground fault current passing through the breaker reaches the set value (×In),the breaker will trip due to the ground fault.
Characteristics of Intelligent Release: It has protection functions such as overload long-delay inverse time, short-circuit short-delay inverse time,short-circuit short-delay fixed time,and short-circuit instantaneous action. These functions can be set by the user to form the required protection characteristics. The inverse time action characteristics of long-delay overcurrent protection are shown in the table:
| Current | time of action | ||
| power distribution |
1.05lr | >2h inoperative(In>63A),1h inoperative (In≤63A) | |
| 1.3r | <1h action | ||
| 1.5lr | Settling time tr(s) | Inm-125A、250A、400A、630A、800A、1250A | |
| 8、12、16、24、32、48、64、96、128、256 | |||
Remarks:Tolerance of operation value is ±10%,tolerance of operation time is ±15%.
Short delay overcurrent protection action characteristics
When Tsd is within the 12tON stall range,it is a fixed time limit:
| Current | time of action | |||||
| I≤Isd≤6Ir counter-time limit | I²T2=(6Xlr)² Tsd | |||||
| I>Isd and I>6Ir Inverse time limit to fixed time limit |
Consolidation time | 0.05 | 0.1 | 0.15 | 0.2 | 0.3 |
| Inaccuracies | ±0.02 | ±0.03 | ±0.04 | ±0.06 | ±0.08 | |
| Returnable time | – | – | 0.14 | 0.21 | 0.3 | |
Remarks :1 is the actual passing current, T2 is the actual action time,lsd is the set short delay curent, Tsd is the set short delay action time
When Tsd is in the range of I2tOFF gear,it is fixed time limit:
| Current | time of action | |||||
| l≥lsd Current Error±10% | Consolidation time | 0.05 | 0.1 | 0.15 | 0.2 | 0.3 |
| Inaccuracies | ±0.02 | ±0.03 | ±0.04 | ±0.06 | ±0.08 | |
| Returnable time | – | – | 0.14 | 0.21 | 0.3 | |
Remarks:lis the actual passing current,T2 is the actual action time;lsdis the short delay curent, Tsd is the short delay actiontime.
Short-circuit transient protection action characteristics
| Current | li=(2,3,4,5,6,8,9,10,12)×ln | |
| Motion Characteristics | Operating current | Minimum operating current 0.9li Maximum inoperative current 1.1li |
| time of action | <0.1s | |
Grounding protection operating characteristics
| Current | Ig=(0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1.0)×ln | |
| Motion Characteristics | Ig≤0.9lg Circuit breaker inoperative | Ig>1.1lg |
| time of action | Tg=0.4(fixed time limit) | |
The electronic striker panel indicators are set as follows

Overload pre-warning characteritics:
| Load Current | I<1lp | I > 1lp |
| Indicator status | Indicator ligh is not flashing,does not light up | Indicator light constant |
| Load Current | I<1.15lp | I ≥ 1.15lp |
| Indicator status | Indicator light is not on | Indicator ligh is on |
| Load Current | ≥0.4In(Single phase) | l≥0.2ln(Tri-phase) |
| Indicator status | Indicator light is on | Indicator light is on |
Nota:
1.The above current error±10%.
2.The pre-alarm current needs to satisfy the startup current constraint,i.e.,the current cannot be lower than the operating condition.
Outline and Installation Dimensions(mm)


| Molded case circuit breaker | Overall dimension | Installation dimensions | Bolt | |||||||||||||||||||||
| A | A1 | A2 | A3 | B | B1 | B2 | B3 | B5 | B6 | H | H1 | H2 | H3 | H4 | H5 | H6 | A4 | B4 | ||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |||||||||||||||||
| CQM6E-160 | 90 | 120 | 60 | 90 | – | – | – | – | 155 | 134 | 102 | 50 | 50 | – | 109 | 83 | 4 | 83 | 76 | 24.5 | 24.5 | 30 | 132 | M8 |
| CQM6E-250 | 105 | 140 | 70 | 105 | – | – | – | – | 165 | 144 | 102 | 50 | 110 | – | 120 | 95 | 4 | 91 | 84 | 22.5 | 24 | 35 | 126 | M8 |
| CQM6E-630 | 140 | 185 | 88 | 132 | 140 | 196 | 112 | 196 | 257 | 230 | 179 | 90 | 110 | 42 | 155 | 107 | 5 | 105 | 97 | 30 | 32 | 44 | 194 | M10 |
| CQM6E-800 | 210 | 280 | 140 | 210 | 180 | 250 | 140 | 250 | 275 | 243 | 192 | 90 | 110 | 87 | 155 | 107 | 5 | 104 | 97 | 25 | 25 | 70 | 242.5 | M12 |
| CQM6E-1250 | 210 | 280 | 140 | 210 | 180 | 250 | 140 | 250 | 275 | 243 | 192 | 90 | 110 | 87 | 155 | 107 | 5 | 104 | 97 | 25 | 25 | 70 | 242.5 | M10*2 |
Appearance and instllation dimensions at the rear of the panel

Appearance and installation dimensions of the rear part for the plug-in type(on the panel)

| Molded case circuit breaker | B-board rear wiring dimensions | C Front-of-Board Wiring Dimensions | C Plug-in wiring size | ||||||||||||||||||||||||
| A1 | B | B1 | H | H1 | φd | φd1 | φd2 | φd3 | A4 | B4 | A | A1 | A2 | A3 | A4 | A5 | A6 | A7 | H | B | B1 | B2 | B3 | φd | H2 | H3 | |
| 125 | 25 | 114 | 111 | 62 | 87 | 6 | 14 | 5 | 5 | 25 | 111 | 130 | 58 | 115 | 132 | 17.5 | 20 | 58 | 97 | 28 | 75 | 50 | 50 | 77 | 5.5 | 15 | 10.5 |
| 160 | 30 | 134 | 132 | 72 | 112 | 8 | 18 | 5 | 5 | 30 | 132 | 155 | 60 | 134 | 173 | 38 | 40 | 60 | 98 | 50 | 92 | 60 | 60 | 94 | 6.5 | 31 | 19.5 |
| 250 | 35 | 144 | 126 | 87 | 126 | 12 | 24 | 5 | 5 | 35 | 126 | 165 | 54 | 144 | 184 | 45 | 47 | 54 | 95 | 50 | 107 | 70 | 70 | 109 | 6.5 | 35 | 21.5 |
| 630 | 44 | 230 | 194 | 83 | 136 | 18 | 35 | 7 | 7 | 44 | 194 | 257 | 125 | 225 | 280 | 55 | 57 | 125 | 169 | 60 | 140 | 87 | 60 | 142 | 9 | 32 | φ23 |
| 800 | 70 | 243 | 243 | 174 | 243 | 26 | 48 | 7 | 7 | 70 | 243 | 275 | 147 | 242 | 42 | 55 | 58 | 147 | 190 | 91 | 218 | 140 | 107 | 222 | 10.5 | 31 | φ27 |
Appearance and installation dimensions of the rear part for the plug-in type(on the panel)

| Model Number | A | E | L2 | L3 | D | E | H | H1 | L | A1 | B1 | D1 | A2 | B2 | D2 |
| 160 | 112 | 30 | 200 | 216 | 4.5 | 6.5 | 56 | 28 | 182 | 172 | 30 | 5.5 | 67 | 60 | 6.5 |
| 250 | 150 | 35 | 233 | 245 | 4.5 | 8.5 | 74 | 33 | 202 | 191 | 35 | 5.5 | 74 | 70 | 6.5 |
| 630 | 283 | 70 | 363 | 405 | 6.5 | 12.5 | 125 | 67 | 341 | 327 | 70 | 6.5 | 143 | 140 | 7 |
| 800 | 283 | 70 | 363 | 405 | 6.5 | 12.5 | 125 | 67 | 341 | 327 | 70 | 6.5 | 143 | 140 | 7 |
The internal accessories of CQM6E series include under-voltage detent,shunt detent, auxiliary alarm detent,its main technical paraameters and wiring diagrams are as follows.
Under-voltage release device

| Internal accessories | |
| Rated voltage of the power supply | Main Performance |
| AC220,AC240 AC380,AC415 |
A. When the supply voltage drops to 70%and 35%of the rated voltage, the undervoltage detector shall operate. B. When the electro-hydraulic voltage is lower than 35%of the rated voltage,the undervoltage detractor should not be able to absorb,in order to prevent the circuit breaker from closing. C.When the power supply voltage is equal to or greater than 85% of the rated voltage,the undervoltage detractor will ensure the absorption, and ensure the reliable closing of the circuit breaker. |

| Shunt release device | |
| Rated supply voltage | Main Performance |
| DC24,DC110 AC220,AC3B0 |
The shunt release can operate reliably between 70%and 110%of the rated voltage value. |

| Auxiliary alarm contact | |
| Rated voltage of power supply | Main performance |
| Auxiliary switch AC 125V 5A,AC 250V 3A DC 125V 0.4A,DC 125V 0.2A |
Provides differentiated signals for circuit breakers in the”closed” and “open”positions. |
| Alarm switch AC 125V 5A,AC 250V 3A DC 125V0.4A,DC 125V 0.2A |
Provides signals to distinguish between “normal operation and “fault free release” positions of circuit breakers. |
| Auxiliary alarm switch AC 125V 5A.AC 250V 3A DC 125V 0.4A,DC125V 0.2A |
Provides signals to distinguish between “closed”, “open” and “fault free release” positions of the circuit breaker. |
Internal accessory
DC3 Electric Operation Mechanism
DC3 series electric operation mechanism is adopted advanced switching power supply technology,utilizing smallpermanent contact motordrive,small working current,suitable for 63-800A plastic case circuit breakers.
| Model Number | DC3-125 | DC3-160 | DC3-250 | DC3-630 | DC3-800 | |
| Compatible Model |
CQM6-125 | CQM6-160 CQM6RT-160 CQM6RE-160 |
CQM6RE-250 CQM6-250 CQM6L-250 CQM6RT-250 CQM6Z-250 |
CQM6-630 CQM6L-630 CQM6RT-630 CQM6RE-630 CQM6Z-630 |
CQM6-800 CQM6L-800 CQM6RT-800 CQM6RE-800 CQM6L-1250 CQM6RE-1250 |
|
| Overall Dimensions |
A | 25 | 30 | 35 | 44 | 70 |
| B | 117 | 132 | 126 | 194 | 243 | |
| C | 73 | 90 | 90 | 130 | 130 | |
| H | 98 | 98(89.5) | 102(92) | 152 | 153 | |
| Rated voltated V |
AC-110-240, DC100-220,DC24 |
AC 230,DC 220 AC 100,DC 110 |
||||
| Starting current A | ≤0.5 | ≤2 | ||||
| Mechanical life(times) | 14000 | 10000 | 5000 | |||
| Power(W) | 14 | 35 | ||||

1.Manual operation:Counterclockwse operationis prohibited.
2.When operating manually,insert the handle at the starting point and turn it 180° in a clockwise direction.

Manual operating mechanism
Shape of the circular handle and the door panel opening size (the distance from the center of the opening to the hinge should not be less than 200mm)

Outline and Installation Schematic Diagram of the Central Series Manual Opion Mechanism

| Hand-operated mechanism model | A | B | C | D | H |
| 160 | 30 | 132 | 66 | 66 | 46 |
| 250 | 35 | 126 | 63 | 63 | 51 |
| 630 | 128 | 194 | 97 | 97 | 76 |
| 800 | 198 | 243 | 121.5 | 121.5 | 76 |
| 1250 | 198 | 243 | 121.5 | 121.5 | 76 |
¿Por qué elegir CHAC?
Con más de 30 años de experiencia en fabricación, más de 1100 empleados, más de 100 millones de postes
Con una capacidad anual y un proceso de producción automatizado 90%, CHAC ofrece una capacidad de producción estable y un estricto
control de calidad para clientes OEM/ODM globales. Nuestro sistema de fabricación interno respalda a largo plazo
Cooperación para marcas eléctricas, importadores y distribuidores.
30+
AÑOS DE EXPERIENCIA
Especializado en fabricación eléctrica de bajo voltaje
1100+
EMPLEADOS
Equipo profesional garantiza calidad y entrega estables
100M+
CAPACIDAD ANUAL DE LOS POLOS
Capacidad de producción a gran escala para satisfacer la demanda mundial
90%
PRODUCCIÓN AUTOMATIZADA
Automatización avanzada para alta eficiencia y consistencia

Línea de ensamblaje automatizada

Laboratorio de pruebas

Inyección y Estampado

Inspección de calidad





Un estricto sistema de control de calidad garantiza que cada producto cumpla con los estándares mundiales.
¿Qué podemos personalizar?
Flexible customization services are available for enclosure dimensions, component configuration,
branding and project requirements.
Recinto
Diseño
Tamaños, estructuras y detalles de instalación de recintos personalizados.
Interno
Configuración
Opciones flexibles de diseño interno y disposición de componentes.
Marca e
Logo
Logotipos de marca propia, placas de identificación e identificación de marca.
Empaquetado
Diseño
Soluciones de embalaje, cajas personalizadas, etiquetas y manuales.
Eléctrico
Configuración
Instalación eléctrica adaptada a los requisitos de la aplicación.
Certificación
Apoyo
Soporte para estándares del mercado objetivo y requisitos de cumplimiento.
Descargar
Interruptor automático de caja moldeada serie CQM6
Descripción general completa de componentes eléctricos de bajo voltaje y referencia para la selección de productos.
¿Necesita documentos técnicos?
Contáctenos para obtener hojas de datos, certificados, planos, orientación de selección o soporte para proyectos OEM/ODM.
Preguntas frecuentes
¿Admite la personalización de productos según nuestros requisitos de diseño?
Absolutamente. Nos especializamos en cooperación OEM y ODM en el campo de la electricidad de bajo voltaje y hemos brindado servicios personalizados a muchas empresas de renombre internacional. Ofrecemos soporte de proceso completo, que incluye diseño de I+D, ajustes de parámetros y selección de materiales especiales, asegurando que el producto cumpla completamente con sus requisitos.
P2: ¿Cuál es tu capacidad de producción y Cantidad Mínima de Pedido (MOQ)?
A2: Operamos una base de producción altamente automatizada con una producción anual de más de 100 millones de polos para interruptores automáticos en miniatura. Nuestra política de MOQ es flexible. Podemos ofrecer pedidos de prueba competitivos para lotes pequeños y planes de garantía de capacidad de producción dedicada.
P3: ¿Qué garantías hay sobre la calidad del producto y las certificaciones?
Nuestros productos principales cuentan con las certificaciones CCC, CE, CB y más, y se venden en más de 30 países y regiones en todo el mundo. La empresa ha establecido un Centro de Operaciones de Calidad dedicado que trabaja con los departamentos de negocios y producción para implementar un control de calidad de proceso completo, garantizando que los productos cumplan con los estándares internacionales.
P4: ¿Tiene la capacidad para la I+D de productos y para convertir conceptos en realidad?
A4: Contamos con un equipo completo de I+D y talleres digitales, respaldados por una amplia experiencia en personalización al servicio de numerosos clientes internacionales. Desde la propuesta conceptual y el desarrollo de muestras hasta la producción en masa, ofrecemos soporte técnico integral para ayudar a dar vida a tus ideas.