Fabricante OEM de interruptores automáticos en caja moldeada (MCCB) electrónicos ajustables CQM6E

El CQM6E MCCB provides adjustable overload, short circuit and ground-fault protection within its published 32–1250A range. Specification should follow the system voltage, load, conductor coordination, prospective fault current and applicable rules—not the ampere value alone.

Polacos
3P / 4P
Corriente nominal:
32–1250A
Voltaje nominal
CA 400/415V
Viaje / Protección:
adjustable overload, short circuit and ground-fault protection
Datos de última hora:
S/M/H classes up to 75kA, according to frame and ordered configuration
Estándar
Referencias de la IEC/EN 60947 y GB/T 14048 que se enumeran en la página

Descripción del producto

CQM6E is a mccb circuit breaker for AC 400/415V distribution and protection applications. Its published range covers 32–1250A with 3P / 4P options. Selection depends on the complete power-system design, including fault level, coordination, conductor ampacity, enclosure conditions and local rules.

The supplied product specification references IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-3 and IEC/EN 60947-4, together with GB/T 14048.1, .2, .3 and .4. These standard references do not, by themselves, establish certification for a particular order.

Características clave

  • Precise Electronic Trip: Features an adjustable electronic release for highly accurate Long-Time, Short-Time, and Instantaneous (L-S-I) protection.
  • Advanced Ground Fault Protection: Includes a dedicated ground fault (G) protection setting for enhanced system safety.
  • Visual Status Indication: Equipped with an intuitive control panel featuring a current light bar and clear indicators for overload and pre-alarm status.
  • Remote operation: Supports integration with a compatible motorised operator. Confirm the required control arrangement for the ordered configuration.
  • Published current range: 32–1250A.

Aplicaciones típicas

Typical applications include industrial automation, critical feeders and systems that require adjustable selectivity or monitoring. These are evaluation contexts rather than universal approvals. Confirm the exact frame, voltage, breaking duty, trip unit, accessories and installation method before specification.

Guía de Solicitudes y Selección

Use the verified CQM6E values below to create a shortlist, then validate the complete circuit. An MCCB rating does not replace conductor calculations, fault-current analysis, coordination review or local installation requirements.

Punto de selección CQM6E reference Lo que el proyecto debe confirmar
Corriente nominal 32–1250A Design current, conductor ampacity, installation method, temperature and grouping
Voltaje CA 400/415V Sistema de suministro y capacidad nominal de los equipos
Polacos 3P / 4P Live conductors and neutral treatment
Trip / protection adjustable electronic L-S-I-G protection Load profile, fault response and coordination
Capacidad de corte S/M/H classes up to 75kA, according to frame and ordered configuration Prospective short-circuit current at the installation point

Electronic vs Thermal-Magnetic Trip

Electronic trip units can provide adjustable thresholds and additional monitoring functions. Confirm the actual setting range, auxiliary supply and coordination study for the ordered model.

Protection Settings
Review Electronic MCCBs →

MCCB vs MCB

An MCCB is normally evaluated for higher current, fault duty or accessory flexibility; an MCB may be more suitable for compact final circuits.

Current & Fault Duty
Compare MCCB and MCB →

Icu vs Ics

The saved data for CQM6E lists S/M/H classes up to 75kA, according to frame and ordered configuration. Match the declared duty to the prospective short-circuit current and continuity objective.

Short-Circuit Study
Review Technical Support →

Pole and Neutral Arrangement

Published pole options are 3P / 4P. Confirm which conductors must be switched, protected and isolated together.

System Arrangement
View MCCB Range →

Guía de pedidos

  1. State the exact model: CQM6E.
  2. Provide frame and rated current within the published range: 32–1250A.
  3. Confirm poles: 3P / 4P.
  4. Specify the trip unit or protection function: adjustable electronic L-S-I-G protection.
  5. Provide system voltage, frequency, application, expected fault level, destination market and quantity.
  6. List required accessories, terminals, documents and any approved OEM/ODM marking or packaging requirements.

Comprobaciones de Instalación y Coordinación

  • Use the exact model drawing and instructions; do not infer terminal positions, supply direction or accessory compatibility from another MCCB.
  • Verify conductor material and cross-section against the circuit calculation, terminal data, temperature and grouping.
  • Confirm Icu/Ics or DC fault duty, upstream/downstream coordination, enclosure conditions, altitude and clearances.
  • Installation, isolation, testing and maintenance must be performed by qualified personnel under applicable rules.

Guía de selección

CHAC CQM6E MCCB - Selection Guide

Código de producto ① Grado de marco de carcasa ② Shell frame grade ③ Breaking capacity ④
CQM6 E 160 S M H
Disjuntor de carcasa moldeada E
Electronically Adjustable
160 160 / 50/35 50/50
250 250 / 50/35 50/50
400 400 35/25 50/35 70/50
630 630 35/25 50/35 70/50
800 800 35/25 50/35 70/50
1250 1250 / 50/35 70/55
Operating method ⑤ Number of poles ⑤ Trip Unit &Accessories ⑥ Corriente nominal A ⑦
P 3 400 160A
Funcionamiento motorizado
Z:Turn the handle
W: Operación directa
160A:3P,4P
250A:3P,4P
400A:3P,4P
630A:3P,4P
800A:3P,4P
1250A:3P,4P
1600A:3P,4P
2:Intelligent disconnectors
Note:The last two digits are the accessory code (see attachment)
160,250,400,630,800,1000,1250
Función ⑧ 4P Option Code ⑨ Código especial ⑩
2 A I
1: Para la distribución de energía
Para la protección del motor
A:N-pole without protection,can not be combined
B:N-pole without protection,can be combined
C:N-pole with protection,can be combined
D:N-pole with protection,can not be combined
Note:If the customer does not have a clear request,four-pole products will be defaulted to the B category
I:Overload alarm non trip function

Lista de accesorios

CHAC CQM6E MCCB - Accessory List
CHAC CQM6E MCCB - Accessory List

Parámetros técnicos principales

Número de modelo CQM6E-160 CQM6E-250
Corriente nominal en el nivel de la trama Inm(A) 160 250
Número de polos 3,4 3,4
Rated current In(A),at 40°C,50°C,55°C 32,63,125,160 160,250
Tensión de funcionamiento nominal Ue(V), CA 50/60Hz 400/415 400/415
Tensión de aislamiento nominal Ui (V) 800 800
Tensión de resistencia a la impulsión nominal Uimp(KV) 8 8
Designación de la capacidad de ruptura M H M H
Capacidad de desconexión por cortocircuito Icu/Ics (kA) AC400/415V 50/35 50/50 50/35 50/50
Rated short-time withstand current Icw(kA),1s AC400/415V 2 2 5 5
Categoría de selectividad B B B B
Number of operating cycles ENCENDIDO 6000 6000
DESACTIVADO 10000 10000
Electronic decouping
(adjustable)
Protección de la distribución de energía ● ● ● ●
Protección del motor ● ● ● ●
Accesorios Controles auxiliares ● ● ● ●
Controles de alarma ● ● ● ●
Desconexión del derivado ● ● ● ●
Dispositivo de protección contra subvoltaje ● ● ● ●
Mecanismo de operación manual ● ● ● ●
Mecanismo de operación motorizado ● ● ● ●
Conexión de la placa trasera ● ● ● ●
Insertado ● ● ● ●
Placa de acoplamiento ● ● ● ●
División entre fases ● ● ● ●
Dimensiones totales
(mm) (a-b-c-ca)
CHAC CQM6E MCCB outline dimension reference a b c and ca 3 P 90×155×85×109 105×165×93×119
4 P 120×155×85×10 140×165×93×119

Note: ● indicates an available optional accessory; – indicates that the accessory is not available.

Número de modelo CQM6E-400 CQM6E-630
Corriente nominal en el nivel de la trama Inm(A) 630 630
Número de polos 3,4 3,4
Rated current In(A),at 40°C,50°C,55°C 400 400,630
Tensión de funcionamiento nominal Ue(V), CA 50/60Hz 400/415 400/415
Tensión de aislamiento nominal Ui (V) 800 800
Tensión de resistencia a la impulsión nominal Uimp(KV) 8 8
Designación de la capacidad de ruptura S M H S M H
Capacidad de desconexión por cortocircuito Icu/Ics (kA) AC400/415V 35/25 50/35 70/50 35/25 50/35 70/50
Rated short-time withstand current Icw(kA),1s AC400/415V 8 8 8 8 8 8
Categoría de selectividad B B B B B B
Number of operating cycles(circle) ENCENDIDO 3000 3000
DESACTIVADO 8000 8000
Electronic decouping
(adjustable)
Protección de la distribución de energía ● ● ● ● ● ●
Protección del motor ● ● ● ● ● ●
Accesorios Controles auxiliares ● ● ● ● ● ●
Controles de alarma ● ● ● ● ● ●
Desconexión del derivado ● ● ● ● ● ●
Dispositivo de protección contra subvoltaje ● ● ● ● ● ●
Mecanismo de operación manual ● ● ● ● ● ●
Mecanismo de operación motorizado ● ● ● ● ● ●
Conexión de la placa trasera ● ● ● ● ● ●
Insertado ● ● ● ● ● ●
Placa de acoplamiento ● ● ● ● ● ●
División entre fases ● ● ● ● ● ●
Dimensiones totales
(mm) (a-b-c-ca)
CHAC CQM6E MCCB outline dimension reference a b c and ca 3 P 140×257×108×156 140×257×108×156
4 P 185×257×108×156 185×257×108×156

Note: ● indicates an available optional accessory; – indicates that the accessory is not available.

Número de modelo CQM6E-800 CQM6E-1250
Corriente nominal en el nivel de la trama Inm(A) 800 1250
Número de polos 3,4 3,4
Rated current In(A),at 40°C,50°C,55°C 630,800 800,1000,1250
Tensión de funcionamiento nominal Ue(V), CA 50/60Hz 400/415 400/415
Tensión de aislamiento nominal Ui (V) 800 1000
Tensión de resistencia a la impulsión nominal Uimp(KV) 8 12
Designación de la capacidad de ruptura S M H M H
Capacidad de desconexión por cortocircuito Icu/Ics (kA) AC400/415V 35/25 50/35 70/50 50/35 75/55
Rated short-time withstand current Icw(kA),1s AC400/415V 10 10 10 12.5 12.5
Categoría de selectividad B B B B B
Número de ciclos de funcionamiento (ciclo) ENCENDIDO 1000 1000
DESACTIVADO 3000 3000
Electronic decouping (adjustable) Protección de la distribución de energía ● ● ● ● ●
Protección del motor ● ● ● ● ●
Accesorios Controles auxiliares ● ● ● ● ●
Controles de alarma ● ● ● ● ●
Desconexión del derivado ● ● ● ● ●
Dispositivo de protección contra subvoltaje ● ● ● ● ●
Mecanismo de operación manual ● ● ● ● ●
Mecanismo de operación motorizado ● ● ● ● ●
Conexión de la placa trasera ● ● ● ● ●
Insertado ● ● ● ● ●
Placa de acoplamiento ● ● ● ● ●
División entre fases ● ● ● ● ●
Dimensiones totales
(mm) (a-b-c-ca)
CHAC CQM6E MCCB outline dimension reference a b c and ca 3 P 210×275×114×163 210×275×114×163
4 P 280×275×114×163 280×275×114×163

Note: ● indicates an available optional accessory; – indicates that the accessory is not available.

Characteristic curve

CHAC CQM6E MCCB - Characteristic curve

Intelligent Release Adjustment Panel

CHAC CQM6E MCCB - Intlligent Release Adjustment Panel

1.Ir: Rated Current (Ir) Setting Dial

The setting dial for the rated current, applicable to 160-1250 frame sizes. The selectable settings on the front panel are: 0.4, 0.45, 0.5, 0.55, 0.6, 0.7, 0.8, 0.9, 1.0, OFF.

2.Tr: Long-Time Delay (Tr) Setting Dial

The setting dial for the overload long-time delay. When the current passing through the circuit breaker reaches 1.5 times Ir (×In), the breaker trips within the set time. The selectable settings are: 8s, 12s, 16s, 24s, 32s, 48s, 64s, 96s, 128s, 256s.

3.Isd: Short-Time Delay Current (Isd) Setting Dial

The setting dial for the short-time delay current multiplier. Selectable settings are: 2, 3, 4, 5, 6, 7, 8, 9, 10, OFF. When a short-circuit current equal to the set value (×Ir, ×In) passes through the breaker, it will trip after a time delay.

4.Tsd: Short-Time Delay Operating Time (Tsd) Setting Dial

The setting dial for the short-time delay operating time. It is divided into inverse-time protection (I²t ON) and definite-time protection (I²t OFF). Selectable settings are: 0.05s, 0.1s, 0.15s, 0.2s, 0.3s. When a short-circuit current equal to Isd passes through the breaker, it will trip within the set time.

5.Ii: Instantaneous Current (Ii) Setting Dial

The setting dial for the instantaneous current multiplier. Selectable settings are: 2, 3, 4, 5, 6, 8, 9, 10, 12. When a short-circuit current equal to the set value (×In) passes through the breaker, it will trip instantaneously.

6.Ip: Pre-alarm Current (Ip) Setting Dial

The setting dial for the pre-alarm current multiplier. Selectable settings are: 60%, 65%, 70%, 75%, 80%, 85%, 90%, 95%, 100%, OFF. When the current passing through the breaker reaches the set value (×Ir, ×In), the pre-alarm indicator light will illuminate.

7.Ig: Ground Fault Current (Ig) Setting Dial

The setting dial for the ground fault current multiplier. Selectable settings are: 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0, OFF. When the ground fault current passing through the breaker reaches the set value (×In), the breaker will trip due to the ground fault.

The intelligent release provides adjustable overload long-time inverse-time protection, short-circuit short-time inverse-time or definite-time protection, and instantaneous protection. The following table gives the long-time overcurrent characteristics.

Actualidad time of action
power
distribution
1.05Ir >2h inoperative(In>63A),1h inoperative (In≤63A)
1.3r <1h action
1.5Ir Settling time tr(s) Inm-125A、250A、400A、630A、800A、1250A
8、12、16、24、32、48、64、96、128、256

Remarks: Operating-current tolerance is ±10%; operating-time tolerance is ±15%.

Short-Time Overcurrent Protection Characteristics

With I²t ON, short-time protection uses an inverse-time characteristic.

Actualidad time of action
I≤Isd≤6Ir counter-time limit I²T2=(6XIr)² Tsd
I>Isd and I>6Ir
Inverse time limit to fixed time limit
Consolidation time 0.05 0.1 0.15 0.2 0.3
Inaccuracies ±0.02 ±0.03 ±0.04 ±0.06 ±0.08
Returnable time – – 0.14 0.21 0.3

I is the actual current, T2 is the actual operating time, Isd is the short-time current setting and Tsd is the short-time delay setting.

With I²t OFF, short-time protection uses a definite-time characteristic.

Actualidad time of action
l≥Isd Current Error±10% Consolidation time 0.05 0.1 0.15 0.2 0.3
Inaccuracies ±0.02 ±0.03 ±0.04 ±0.06 ±0.08
Returnable time – – 0.14 0.21 0.3

I is the actual current, T2 is the actual operating time, Isd is the short-time current setting and Tsd is the short-time delay setting.

Instantaneous Short-Circuit Protection Characteristics

Actualidad li=(2,3,4,5,6,8,9,10,12)×ln
Motion Characteristics Operating current Minimum operating current 0.9li
Maximum inoperative current 1.1li
time of action <0,1 s

Ground-Fault Protection Characteristics

Actualidad Ig=(0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1.0)×ln
Motion Characteristics Ig≤0.9lg Circuit breaker inoperative Ig>1.1lg
time of action Tg=0.4(fixed time limit)

Electronic Release Panel Indicators

CHAC CQM6E MCCB - The electronic striker panel indicators are set as follows

Overload Pre-Alarm Characteristics

Load Current I<1lp I ≥ 1lp
Indicator status Indicator ligh is not flashing,does not light up Indicator light constant
Load Current I<1.15lp I ≥ 1.15lp
Indicator status Indicator light is not on Indicator ligh is on
Load Current ≥0.4In(Single phase) l≥0.2ln(Tri-phase)
Indicator status Indicator light is on Indicator light is on

Nota:

Note: The stated current tolerance is ±10%.

Select the pre-alarm threshold with the starting current and operating conditions in mind.

Outline and Installation Dimensions(mm)

CHAC CQM6E MCCB - Outline and Installation Dimensions(m)Outline and Installation Dimensions(mm)
CHAC CQM6E MCCB - Outline and Installation Dimensions(m)Outline and Installation Dimensions(mm)

Disjuntor de carcasa moldeada Dimensiones totales Installation dimensions Boit
A A1 A2 A3 B B1 B2 B3 B5 B6 H H1 H2 H3 H4 H5 H6 A4 B4
3P 4P 3P 4P 3P 4P 3P 4P
CQM6E-160M 90 120 60 90 – – – – 155 134 103 50 48 – 109.2 90 2.2 84.9 23.6 23.6 24.9 30 132 M8
CQM6E-250M 105 140 70 105 – – – – 165 144 102 50 95 – 118.6 97.6 2.8 93.4 23.1 23.1 23.2 35 126 M8
CQM6E-400/630 SMH 400A 140 185 88 132 140 196 112 168 257 230 179 90 103 42 156 112.1 3.5 107.5 30.9 30.9 32 44 194 M10
CQM6E-630SMH 630A 140 185 88 132 140 196 112 168 257 230 179 90 103 42 156 112.1 3.5 107.5 33.4 33.4 34 44 194 M10
CQM6E-800SMH 630A 210 280 140 210 180 250 140 210 275 243 192 90 103 87 162.5 118.4 2.7 114.3 28.5 28.5 30.7 70 242.5 M12
CQM6E-800SMH 800A 210 280 140 210 180 250 140 210 275 243 192 90 103 87 162.5 118.4 2.7 114.3 29.5 29.5 32.7 70 242.5 M12
CQM6E-1250SMH 210 280 140 210 180 250 140 210 275 243 192 90 103 87 162.5 118.4 2.7 114.3 31.50 31.5 34.7 70 242.5 M10

Rear-Connected Installation Dimensions

CHAC CQM6E MCCB - Appearance and instllation dimensions at the rear of the panel

Plug-In Installation Dimensions

CHAC CQM6E MCCB - Appearance and installation dimensions of the rear part for the plug-in type(on the panel)

Disjuntor de carcasa moldeada B-board rear wiring dimensions C Front-of-Board Wiring Dimensions C Plug-in wiring size
A1 B B1 H H1 φd φd1 φd2 φd3 A4 B4 A A1 A2 A3 A4 A5 A6 A7 H B B1 B2 B3 φd H2 H3
125 25 114 111 62 87 6 14 5 5 25 111 130 58 115 132 17.5 20 58 97 28 75 50 50 77 5.5 15 10.5
160 30 134 132 72 112 8 18 5 5 30 132 155 60 134 173 38 40 60 98 50 92 60 60 94 6.5 31 19.5
250 35 144 126 87 126 12 24 5 5 35 126 165 54 144 184 45 47 54 95 50 107 70 70 109 6.5 35 21.5
400 44 230 194 83 136 18 35 7 7 44 194 257 125 225 280 55 57 125 169 60 140 87 60 142 9 32 φ23
630 44 230 194 83 136 18 35 7 7 44 194 257 125 225 280 55 57 125 169 60 140 87 60 142 9 32 φ23
800 70 243 243 174 243 26 48 7 7 70 243 275 147 242 42 55 58 147 190 91 218 140 107 222 10.5 31 φ27

Plug-In Installation Dimensions

CHAC CQM6E MCCB - Appearance and installation dimensions of the rear part for the plug-in type(on the panel)

Model Number A E L2 L3 D E H H1 L A1 B1 D1 A2 B2 D2
160 112 30 200 216 4.5 6.5 56 28 182 172 30 5.5 67 60 6.5
250 150 35 233 245 4.5 8.5 74 33 202 191 35 5.5 74 70 6.5
400 283 70 363 405 6.5 12.5 125 67 341 327 70 6.5 143 140 7
630 283 70 363 405 6.5 12.5 125 67 341 327 70 6.5 143 140 7
800 283 70 363 405 6.5 12.5 125 67 341 327 70 6.5 143 140 7

CQM6E internal accessories include undervoltage releases, shunt releases, auxiliary contacts and alarm contacts. Their technical parameters and wiring diagrams are shown below.

Undervoltage Release

CHAC CQM6E MCCB - Under-voltage release device

Internal accessories
Rated voltage of the power supply Main Performance
AC220,AC240
AC380,AC415
A. When the supply voltage drops to 70%and 35%of the rated voltage, the undervoltage detector shall operate.
B. When the electro-hydraulic voltage is lower than 35%of the rated voltage,the undervoltage detractar should not be able to absorb,in order to prevent the circuit breaker from closing.
C.When the power supply voltage is equal to or greater than 85% of the rated voltage,the undervoltage detractar will ensure the absorption, and ensure the reliable closing of the circuit breaker.

CHAC CQM6E MCCB - Under-voltage release device

Shunt release device
Rated supply voltage Main Performance
DC24,DC110
AC220,AC3B0
The shunt release can operate reliably between 70%and 110%of the rated voltage value.

CHAC CQM6E MCCB - Under-voltage release device
CHAC CQM6E MCCB - Under-voltage release device
CHAC CQM6E MCCB - Under-voltage release device

Auxiliary alarm contact
Rated voltage of power supply Main performance
Auxiliary switch
AC 125V 5A,AC 250V 3A DC
125V 0.4A,DC 125V 0.2A
Provides differentiated signals for circuit breakers in the"closed" and "open"positions.
Alarm switch
AC 125V 5A,AC 250V 3A DC
125V0.4A,DC 125V 0.2A
Provides signals to distinguish between "normal operation and "fault free release" positions of circuit breakers.
Auxiliary alarm switch
AC 125V 5A.AC 250V 3A DC
125V 0.4A,DC125V 0.2A
Provides signals to distinguish between "closed",
"open" and "fault free release" positions of the circuit
breaker.

External Accessories

CD3 Motorised Operating Mechanism

The CD3 operating mechanism uses switching power-supply technology and a small permanent-magnet motor. The supplied accessory specification covers 63–800A moulded-case circuit breakers; confirm compatibility with the ordered frame.

Model Number CD3-125 CD3-160 CD3-250 CD3-400/630 DC3-800
Compatible
Modelo
CQM6-125 CQM6-160
CQM6RT-160
CQM6R-160
CQM6E-250
CQM6-250
CQM6L-250
CQM6RT-250
CQM6-630
CQM6L-630
CQM6RT-630
CQM6E-630
CQM6-800
CQM6L-800
CQM6RT-800
CQM6E-800
CQM6L-1250
CQM6E-1250
Overall
Dimensions
A 25 30 35 44 70
B 117 132 126 194 243
C 73 90 90 130 130
H 98 98(89.5) 102(92) 152 153
Rated
voltated V
AC-110-240,
DC100-220,DC24
AC 230,DC 220
AC 100,DC 110
Starting current A ≤0.5 ≤2
Mechanical life(times) 14000 10000 5000
Power(W) 14 35

CHAC CQM6E MCCB - technical diagram 20

Do not turn the manual operating mechanism anticlockwise.

For manual operation, insert the handle at the starting position and turn it 180° clockwise.

CHAC CQM6E MCCB - technical diagram 21

Manual Operating Mechanism

The following drawing shows the rotary handle and door-panel cut-out. The distance from the centre of the opening to the hinge must be at least 200mm.

CHAC CQM6E MCCB - technical diagram 22

Central Manual Operating Mechanism Dimensions

CHAC CQM6E MCCB - technical diagram 23

Hand-operated mechanism model A B C D H
160 30 132 66 66 46
250 35 126 63 63 51
400 128 194 97 97 76
630 128 194 97 97 76
800 198 243 121.5 121.5 76
1250 198 243 121.5 121.5 76

¿Por qué elegir CHAC?

Con más de 30 años de experiencia en fabricación, más de 1100 empleados, más de 100 millones de postes
Con una capacidad anual y un proceso de producción automatizado 90%, CHAC ofrece una capacidad de producción estable y un estricto
control de calidad para clientes OEM/ODM globales. Nuestro sistema de fabricación interno respalda a largo plazo
Cooperación para marcas eléctricas, importadores y distribuidores.

Imágenes del producto del disyuntor de circuito de aire Cqw2 Series
30+

AÑOS DE EXPERIENCIA

Especializado en fabricación eléctrica de bajo voltaje

Imágenes del producto del disyuntor de circuito de aire Cqw2 Series
1100+

EMPLEADOS

Equipo profesional garantiza calidad y entrega estables

Imágenes del producto del disyuntor de circuito de aire Cqw2 Series
100M+

CAPACIDAD ANUAL DE LOS POLOS

Capacidad de producción a gran escala para satisfacer la demanda mundial

Imágenes del producto del disyuntor de circuito de aire Cqw2 Series
90%

PRODUCCIÓN AUTOMATIZADA

Automatización avanzada para alta eficiencia y consistencia

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Línea de ensamblaje automatizada

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Laboratorio de pruebas

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Inyección y Estampado

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Inspección de calidad

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM
Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM
Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM
Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM
Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Un estricto sistema de control de calidad garantiza que cada producto cumpla con los estándares mundiales.

¿Qué podemos personalizar?

For CQM6E projects, CHAC can review private-label marking, packaging, approved appearance options, published 32–1250A electrical configurations and technical-document requirements. Requests outside the published range are subject to engineering evaluation, testing, minimum order quantity and project feasibility.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Recinto
Diseño

Tamaños, estructuras y detalles de instalación de recintos personalizados.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Interno
Configuración

Opciones flexibles de diseño interno y disposición de componentes.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Marca e
Logo

Logotipos de marca propia, placas de identificación e identificación de marca.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Empaquetado
Diseño

Soluciones de embalaje, cajas personalizadas, etiquetas y manuales.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Eléctrico
Configuración

Instalación eléctrica adaptada a los requisitos de la aplicación.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Certificación
Apoyo

Soporte para estándares del mercado objetivo y requisitos de cumplimiento.

Imágenes del producto de CQM6E, un regulador de CA electrónico ajustable de la marca OEM

Descargar

PDF

Interruptor automático de caja moldeada serie CQM6

Descripción general completa de componentes eléctricos de bajo voltaje y referencia para la selección de productos.

Descargar PDF

Arriba

¿Necesita documentos técnicos?

Contáctenos para obtener hojas de datos, certificados, planos, orientación de selección o soporte para proyectos OEM/ODM.

Contáctanos

CQM6E Product FAQ

What is the CQM6E MCCB used for?

The CQM6E is specified for adjustable overload, short circuit and ground-fault protection in AC 400/415V systems within the published 32–1250A range. Suitability depends on the fault study, conductor coordination, enclosure and local rules.

What does the electronic trip unit do in the CQM6E?

The electronic trip unit processes current signals and provides the adjustable protection functions stated for the model. Confirm the available long-time, short-time, instantaneous, ground-fault, auxiliary-power and communication options for the ordered configuration.

How do I choose the CQM6E rated current and poles?

Start with the design current and conductor calculation, then choose a published current within 32–1250A and poles from 3P / 4P. Neutral treatment, fault level, ambient conditions and coordination also need review.

What breaking capacity should I check on the CQM6E?

Use the declared S/M/H classes up to 75kA, according to frame and ordered configuration for the exact frame, voltage and configuration. The prospective short-circuit current at the installation point must be within the applicable duty; a larger ampere value alone is not a selection rule.

Can the CQM6E replace an MCB or an earth-leakage device?

An MCCB is not automatically a like-for-like replacement. The CQM6E provides adjustable overload, short circuit and ground-fault protection; residual-current protection, DC interruption, adjustable settings and other functions must be confirmed separately from the project requirement.

How should the CQM6E be installed and tested?

Use only the exact model drawing, terminal identification and accessory instructions. A qualified person should verify isolation, conductor size, torque, clearances, settings, fault duty and functional tests before energising the circuit.

Confirm the Right CQM6E Configuration

Send the frame, rated current, poles, protection function, system voltage, expected fault level, destination market and quantity. CHAC will review the request against the published model range.

Solicitar un presupuesto