{"id":4517,"date":"2026-10-09T00:00:00","date_gmt":"2026-10-09T00:00:00","guid":{"rendered":"https:\/\/chac-electric.com\/?p=4517"},"modified":"2026-10-20T05:19:09","modified_gmt":"2026-10-20T05:19:09","slug":"les-causes-de-protection-contre-les-defauts-de-connexion-au-sol-et-les-courts-circuits","status":"publish","type":"post","link":"https:\/\/chac-electric.com\/fr\/blog\/ground-fault-vs-short-circuit-causes-protection-examples\/","title":{"rendered":"D\u00e9faillance du circuit de la terre vs court-circuit : causes, protection et exemples"},"content":{"rendered":"<p>Lorsqu\u2019un \u00e9lectricien de maintenance \u00e0 Chicago a constat\u00e9 qu\u2019un disjoncteur se d\u00e9clenchait \u00e0 chaque mise en marche d\u2019une pompe, il a isol\u00e9 la charge et test\u00e9 le circuit d\u00e9riv\u00e9 plut\u00f4t que de le r\u00e9armer \u00e0 plusieurs reprises. L\u2019humidit\u00e9 avait cr\u00e9\u00e9 un chemin de courant vers le conducteur de terre de l\u2019\u00e9quipement, tandis qu\u2019un c\u00e2ble endommag\u00e9 distinct pr\u00e9sentait un court-circuit entre la phase et le neutre. Les sympt\u00f4mes \u00e9taient similaires, mais les m\u00e9canismes de protection et les proc\u00e9dures de d\u00e9pannage diff\u00e9raient.<\/p>\n<p>R\u00e9sum\u00e9 : Un d\u00e9faut \u00e0 la terre est un courant ind\u00e9sirable qui s\u2019\u00e9coule d\u2019un conducteur sous tension vers la terre ou vers une partie m\u00e9tallique expos\u00e9e ; un court-circuit est une connexion ind\u00e9sirable de faible imp\u00e9dance entre des conducteurs situ\u00e9s \u00e0 des potentiels diff\u00e9rents. Tous deux peuvent d\u00e9clencher les dispositifs de protection contre les surintensit\u00e9s, mais les dispositifs de protection contre les d\u00e9fauts \u00e0 la terre mesurent le d\u00e9s\u00e9quilibre et le court-<a href=\"https:\/\/chac-electric.com\/fr\/blog\/rcbo-pour-les-electriciens-une-solution-fiable-de-protection-des-circuits\/\">Protection du circuit<\/a> r\u00e9agit principalement \u00e0 un courant excessif. La r\u00e9action s\u00fbre face \u00e0 <strong>D\u00e9faillance du r\u00e9seau \u00e9lectrique vs court-circuit<\/strong> Il convient de mettre hors tension, d\u2019identifier la ligne d\u00e9fectueuse et de proc\u00e9der \u00e0 des tests avant de r\u00e9armer.<\/p>\n<h2>Qu\u2019est-ce qu\u2019un d\u00e9faut \u00e0 la terre ?<\/h2>\n<p>Une d\u00e9faut \u00e0 la terre se produit lorsque le courant quitte son circuit de circulation pr\u00e9vu et atteint un \u00e9l\u00e9ment m\u00e9tallique mis \u00e0 la terre, un conducteur de terre, le sol ou une autre surface conductrice. Les causes courantes incluent les enceintes humides, l\u2019isolation endommag\u00e9e, des brins desserr\u00e9s, des connexions incorrectes entre le neutre et la terre en aval du point de livraison, ainsi que des \u00e9quipements dont la barri\u00e8re d\u2019isolation est d\u00e9faillante. Le courant de d\u00e9faut peut \u00eatre suffisamment faible pour ne pas d\u00e9clencher un disjoncteur classique, mais assez \u00e9lev\u00e9 pour engendrer un risque d\u2019\u00e9lectrisation.<\/p>\n<p>Un sol-<a href=\"https:\/\/chac-electric.com\/fr\/blog\/disjoncteur-et-interrupteur-de-defaut-de-connexion-a-la-masse\/\">Disjoncteur de protection contre les d\u00e9fauts \u00e0 la terre<\/a> Il compare les courants d\u2019entr\u00e9e et de sortie sur les conducteurs surveill\u00e9s. Si la diff\u00e9rence atteint le seuil de d\u00e9clenchement, l\u2019appareil se d\u00e9clenche rapidement. Le seuil pr\u00e9cis et le d\u00e9lai d\u00e9pendent du type d\u2019appareil et de la norme applicable. Le conducteur de mise \u00e0 la terre de l\u2019\u00e9quipement demeure essentiel ; un dispositif DDR ne rend pas une installation non mise \u00e0 la terre conforme aux exigences.<\/p>\n<figure class=\"wp-block-image size-full chac-paragraph-illustration\" style=\"margin:24px 0\"><img src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k.webp\" alt=\"Un chemin de retour non intentionnel peut cr\u00e9er un courant r\u00e9siduel ; exemple CHAC PXB6L-63 IEC RCBO\" width=\"1536\" height=\"864\" class=\"wp-image-5286\" loading=\"lazy\" decoding=\"async\" style=\"display:block;width:100%;height:auto\" srcset=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k.webp 1536w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k-300x169.webp 300w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k-1024x576.webp 1024w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k-768x432.webp 768w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k-18x10.webp 18w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline1-20261020-correction01-200k-600x338.webp 600w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption>Le courant r\u00e9siduel et le courant de charge du circuit sont des grandeurs diff\u00e9rentes.<\/figcaption><\/figure>\n<h2>Qu\u2019est-ce qu\u2019un court-circuit ?<\/h2>\n<p>Un court-circuit est une connexion de faible r\u00e9sistance entre des conducteurs qui devraient \u00eatre isol\u00e9s, par exemple entre la phase et le neutre ou entre phases. Le courant de d\u00e9faut disponible peut \u00eatre tr\u00e8s \u00e9lev\u00e9 et est limit\u00e9 par l\u2019imp\u00e9dance du transformateur, la longueur des conducteurs et la conception du syst\u00e8me. L\u2019\u00e9l\u00e9ment magn\u00e9tique ou instantan\u00e9 d\u2019un dispositif de protection contre les surintensit\u00e9s est destin\u00e9 \u00e0 interrompre ce type de d\u00e9faut, tandis que l\u2019\u00e9l\u00e9ment thermique r\u00e9agit en cas de surcharge prolong\u00e9e.<\/p>\n<p>Un court-circuit peut endommager l\u2019isolation, les bornes et les barres omnibus avant que l\u2019appareil de protection ne se d\u00e9clenche si le pouvoir de coupure est insuffisant. C\u2019est pourquoi le pouvoir de coupure ou le courant de court-circuit assign\u00e9 du disjoncteur doit \u00eatre conforme au courant de d\u00e9faut disponible au point d\u2019installation. Ne d\u00e9duisez pas cette valeur de la d\u00e9signation en amp\u00e8res figurant sur la poign\u00e9e.<\/p>\n<table>\n<thead>\n<tr>\n<th>Caract\u00e9ristique<\/th>\n<th>D\u00e9faut \u00e0 la terre<\/th>\n<th>Circuit court<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Chemin non intentionnel<\/td>\n<td>Conducteur vers la terre ou vers une partie conductrice expos\u00e9e<\/td>\n<td>Conducteur \u00e0 conducteur sous des potentiels diff\u00e9rents<\/td>\n<\/tr>\n<tr>\n<td>Risque typique<\/td>\n<td>Choc \u00e9lectrique, incendie, d\u00e9clenchements intempestifs, tension de contact<\/td>\n<td>\u00c9nergie d\u2019arc, dommages aux conducteurs, incendie<\/td>\n<\/tr>\n<tr>\n<td>D\u00e9tection<\/td>\n<td>Test de d\u00e9s\u00e9quilibre de courant ou d\u2019isolement<\/td>\n<td>D\u00e9clenchement en cas de courant de d\u00e9faut \u00e9lev\u00e9 et de surintensit\u00e9<\/td>\n<\/tr>\n<tr>\n<td>Premi\u00e8re action<\/td>\n<td>Mettre hors tension, isoler l\u2019humidit\u00e9 ou l\u2019isolation endommag\u00e9e<\/td>\n<td>D\u00e9s\u00e9nergiser, isoler les conducteurs et inspecter les dommages caus\u00e9s par la d\u00e9charge \u00e9lectrique.<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<table>\n<thead>\n<tr>\n<th>Sympt\u00f4me<\/th>\n<th>Direction possible<\/th>\n<th>Prochaine v\u00e9rification en toute s\u00e9curit\u00e9<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Voyages imm\u00e9diatement apr\u00e8s la r\u00e9initialisation<\/td>\n<td>Court-circuit, contact entre le neutre et la terre ou d\u00e9faillance d\u2019un appareil<\/td>\n<td>Verrouillez, isolez les charges et testez la continuit\u00e9.<\/td>\n<\/tr>\n<tr>\n<td>Voyages apr\u00e8s la pluie ou le lavage<\/td>\n<td>D\u00e9faut \u00e0 la terre d\u00fb \u00e0 l\u2019humidit\u00e9<\/td>\n<td>Inspectez les enceintes, les joints d\u2019\u00e9tanch\u00e9it\u00e9 et l\u2019isolation.<\/td>\n<\/tr>\n<tr>\n<td>Tours uniquement au d\u00e9marrage du moteur<\/td>\n<td>Courant d\u2019appel, rotor bloqu\u00e9 ou enroulement court-circuit\u00e9<\/td>\n<td>V\u00e9rifiez les donn\u00e9es de la plaque signal\u00e9tique et la protection du circuit du moteur.<\/td>\n<tr>\n<td>Le bouton de test \u00e9choue<\/td>\n<td>Probl\u00e8me de dispositif, d\u2019alimentation ou de c\u00e2blage<\/td>\n<td>Retirer du service et suivre la proc\u00e9dure d\u2019essai du fabricant.<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Comment les dispositifs de protection se r\u00e9partissent le travail<\/h2>\n<p>Un disjoncteur miniature standard prot\u00e8ge contre les surcharges et les courts-circuits dans la limite de ses caract\u00e9ristiques nominales. Un DDR, un DRCE ou un RCD surveille le courant r\u00e9siduel. Un DRCE combin\u00e9 int\u00e8gre \u00e0 la fois les fonctions de d\u00e9tection de courant r\u00e9siduel et de protection contre les surintensit\u00e9s lorsque sa norme de produit et son marquage l\u2019indiquent. La protection par AFCI d\u00e9tecte certains types d\u2019arcs \u00e9lectriques et ne remplace ni la protection contre les d\u00e9fauts \u00e0 la terre ni la protection contre les surintensit\u00e9s.<\/p>\n<p>Pour une application en panneau, un produit agr\u00e9\u00e9 <a href=\"https:\/\/chac-electric.com\/fr\/product\/cqb2-63-disjoncteur-miniature\/\"><strong>Disjoncteur miniature CHAC<\/strong><\/a> peut g\u00e9rer les surintensit\u00e9s lorsque sa tension, son nombre de p\u00f4les, sa courbe et ses capacit\u00e9s de coupure sont conformes au syst\u00e8me. Un dispositif tel que le <a href=\"https:\/\/chac-electric.com\/fr\/product\/disjoncteur-a-circuit-magnetique-pxl9-63\/\"><strong>Disjoncteur diff\u00e9rentiel PXL9-63<\/strong><\/a> peut \u00eatre \u00e9valu\u00e9 pour la protection contre les courants r\u00e9siduels, tandis que le <a href=\"https:\/\/chac-electric.com\/fr\/product\/pxb6l-63-disjoncteur-de-courant-residuel-avec-protection-contre-les-surintensites-type-electronique\/\">PXB6L-63 RCBO<\/a> devrait \u00eatre \u00e9valu\u00e9 en tenant compte de la protection combin\u00e9e et de l\u2019agencement de c\u00e2blage pr\u00e9vu.<\/p>\n<figure class=\"wp-block-image size-full chac-paragraph-illustration\" style=\"margin:24px 0\"><img src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k.webp\" alt=\"Les fonctions de protection doivent \u00eatre sp\u00e9cifi\u00e9es s\u00e9par\u00e9ment ; exemple CHAC PXB6L-63 IEC RCBO\" width=\"1536\" height=\"864\" class=\"wp-image-5287\" loading=\"lazy\" decoding=\"async\" style=\"display:block;width:100%;height:auto\" srcset=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k.webp 1536w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k-300x169.webp 300w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k-1024x576.webp 1024w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k-768x432.webp 768w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k-18x10.webp 18w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/10\/chac-section-4517-inline2-20261020-200k-600x338.webp 600w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption>Un disjoncteur miniature ordinaire n\u2019implique pas de protection contre les courants r\u00e9siduels.<\/figcaption><\/figure>\n<h2>L\u00e0 o\u00f9 le code n\u00e9cessite une protection particuli\u00e8re<\/h2>\n<p>L'adopt\u00e9 <a href=\"https:\/\/www.nfpa.org\/nec\" rel=\"nofollow noopener\" target=\"_blank\">NFPA 70 NEC<\/a> identifie les emplacements et les \u00e9quipements o\u00f9 une protection par GFCI ou AFCI est requise, notamment dans de nombreuses applications r\u00e9sidentielles, humides, ext\u00e9rieures et de protection des personnes. Les exigences varient selon l\u2019\u00e9dition et la juridiction. La norme IEC 61008-1 couvre les RCCB sans protection int\u00e9gr\u00e9e contre les surintensit\u00e9s, tandis que la norme IEC 61009-1 couvre les RCBO ; la norme IEC 60898-1 traite de certains disjoncteurs de surintensit\u00e9.<\/p>\n<p>Les normes d\u00e9finissent les performances des appareils et les m\u00e9thodes d\u2019essai, et non une autorisation universelle de c\u00e2blage. Le produit doit \u00eatre install\u00e9 conform\u00e9ment \u00e0 ses instructions, et l\u2019autorit\u00e9 comp\u00e9tente d\u00e9termine la conformit\u00e9 aux codes en vigueur. Les all\u00e9gations non fond\u00e9es concernant une protection \u201c anti-choc \u201d ou une protection universelle peuvent engendrer une responsabilit\u00e9 si le type d\u2019appareil, le r\u00e9glage du diff\u00e9rentiel ou l\u2019installation sont inappropri\u00e9s.<\/p>\n<h2>Comment devez-vous proc\u00e9der pour tester, r\u00e9initialiser et identifier la cause racine ?<\/h2>\n<p>Lorsqu\u2019un dispositif se d\u00e9clenche, d\u00e9branchez ou isolez les charges situ\u00e9es en aval, mettez la source hors tension et verrouillez\u2011la, puis v\u00e9rifiez la pr\u00e9sence d\u2019eau, de c\u00e2bles \u00e9cras\u00e9s, de surchauffe, de bornes desserr\u00e9es et de tout contact entre le neutre et la terre. Utilisez un multim\u00e8tre ou un testeur d\u2019isolement correctement dimensionn\u00e9 conform\u00e9ment \u00e0 la proc\u00e9dure en vigueur ; ne testez jamais un circuit sous tension de mani\u00e8re improvis\u00e9e. Ne r\u00e9armez qu\u2019une fois le d\u00e9faut localis\u00e9 et apr\u00e8s avoir v\u00e9rifi\u00e9 que le dispositif passe avec succ\u00e8s son test de fonctionnement.<\/p>\n<p>Enregistrez l\u2019heure, l\u2019\u00e9tat de la charge, les conditions m\u00e9t\u00e9orologiques et le signal du dispositif. Un d\u00e9clenchement survenant uniquement au d\u00e9marrage d\u2019un moteur laisse supposer un courant d\u2019appel ou un court-circuit, tandis qu\u2019un d\u00e9clenchement apr\u00e8s une pluie \u00e9voque une fuite ; toutefois, il ne s\u2019agit l\u00e0 que d\u2019indices, et non de preuves. Des r\u00e9armements r\u00e9p\u00e9t\u00e9s sans proc\u00e9der \u00e0 des tests peuvent transformer un d\u00e9faut ma\u00eetrisable en un arc \u00e9lectrique ou en un incendie.<\/p>\n<h2>Foire aux questions<\/h2>\n<h3>Comment savoir si une masse est en court-circuit ?<\/h3>\n<p>D\u00e9s\u00e9nergisez le circuit et faites v\u00e9rifier la continuit\u00e9 et l\u2019isolation entre les conducteurs et la terre par une personne qualifi\u00e9e. Contr\u00f4lez la pr\u00e9sence d\u2019humidit\u00e9, l\u2019\u00e9tat des gaines (absence de dommages), l\u2019int\u00e9grit\u00e9 des brins (absence de fils desserr\u00e9s) ainsi que les connexions entre le neutre et la terre en aval du point de liaison autoris\u00e9. Un simple signal sonore indiquant la continuit\u00e9 ne garantit pas la qualit\u00e9 de l\u2019isolation sous tension nominale.<\/p>\n<h3>Quelle est la gravit\u00e9 d\u2019un d\u00e9faut \u00e0 la terre ?<\/h3>\n<p>Cela peut \u00eatre extr\u00eamement grave, car des parties m\u00e9talliques expos\u00e9es peuvent se trouver sous tension et un d\u00e9faut peut persister en dessous du seuil de d\u00e9clenchement d\u2019un disjoncteur standard. Consid\u00e9rez chaque d\u00e9clenchement inexpliqu\u00e9 comme un incident de s\u00e9curit\u00e9. Isolez le circuit et effectuez des tests avant de r\u00e9tablir l\u2019alimentation.<\/p>\n<h3>Comment r\u00e9parer un court-circuit ou une prise de terre ?<\/h3>\n<p>Il n\u2019existe pas de proc\u00e9dure de r\u00e9initialisation universelle. Mettez le circuit hors tension, identifiez le conducteur ou l\u2019\u00e9quipement endommag\u00e9, r\u00e9parez-le ou remplacez-le en utilisant des pi\u00e8ces homologu\u00e9es, v\u00e9rifiez l\u2019isolation et la mise \u00e0 la terre, puis assurez-vous du bon fonctionnement des dispositifs de protection. Une d\u00e9cision finale doit \u00eatre prise par un \u00e9lectricien agr\u00e9\u00e9.<\/p>\n<h3>Un d\u00e9faut de terre fera-t-il disjoncter un interrupteur diff\u00e9rentiel ordinaire ?<\/h3>\n<p>Cela peut se produire, mais uniquement si le courant qui circule est suffisant pour atteindre la courbe de d\u00e9clenchement en surintensit\u00e9 du disjoncteur. Une faible fuite peut demeurer dangereuse sans provoquer le d\u00e9clenchement d\u2019un disjoncteur classique ; c\u2019est pourquoi une protection diff\u00e9rentielle (GFCI) ou une protection par courant r\u00e9siduel est utilis\u00e9e lorsque cela est requis.<\/p>\n<h3>Quelle est la diff\u00e9rence entre un d\u00e9faut \u00e0 la terre et un court-circuit, et comment cela fonctionne-t-il ?<\/h3>\n<p>Un d\u00e9faut \u00e0 la terre d\u00e9vie le courant vers la terre ou vers des parties conductrices expos\u00e9es ; un court-circuit met en communication des conducteurs par un chemin de faible imp\u00e9dance. Les dispositifs de protection contre les surintensit\u00e9s r\u00e9agissent aux courants \u00e9lev\u00e9s, tandis que les dispositifs \u00e0 courant r\u00e9siduel r\u00e9agissent aux d\u00e9s\u00e9quilibres. Le choix du dispositif appropri\u00e9 d\u00e9pend du risque et de l\u2019installation.<\/p>\n<h3>O\u00f9 la protection contre les d\u00e9fauts \u00e0 la terre et contre les courts-circuits est-elle requise ?<\/h3>\n<p>La protection contre les surintensit\u00e9s est obligatoire dans l\u2019ensemble des installations \u00e9lectriques, et la protection contre les d\u00e9fauts \u00e0 la terre est requise dans les locaux d\u00e9finis par le code adopt\u00e9 et les instructions du mat\u00e9riel. Les prescriptions relatives aux dispositifs de protection contre les arcs \u00e9lectriques (AFCI) visent certains risques d\u2019arc \u00e9lectrique. V\u00e9rifiez les dispositions applicables au niveau de la juridiction comp\u00e9tente, selon le type d\u2019occupation, le syst\u00e8me de tension et la derni\u00e8re \u00e9dition en vigueur.<\/p>\n<h2>Quelles sources officielles doivent-ils v\u00e9rifier les acheteurs ?<\/h2>\n<ol>\n<li><a href=\"https:\/\/www.nfpa.org\/nec\" rel=\"nofollow noopener\" target=\"_blank\">NFPA 70 NEC<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2310\" rel=\"nofollow noopener\" target=\"_blank\">IEC 61009-1<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2289\" rel=\"nofollow noopener\" target=\"_blank\">IEC 61008-1<\/a><\/li>\n<li><a href=\"https:\/\/www.osha.gov\/electrical\" rel=\"nofollow noopener\" target=\"_blank\">Ressources en mati\u00e8re de s\u00e9curit\u00e9 \u00e9lectrique d\u2019OSHA<\/a><\/li>\n<\/ol>\n<p>La distinction essentielle r\u00e9side dans le chemin de d\u00e9faut, et non dans l\u2019\u00e9tiquette appos\u00e9e sur la poign\u00e9e. Pour les choix coordonn\u00e9s en mati\u00e8re de protection contre les surintensit\u00e9s et les courants r\u00e9siduels, consultez CHAC Electric. <a href=\"https:\/\/chac-electric.com\/fr\/product\/disjoncteur-a-circuit-magnetique-pxl9-63\/\">produits de protection contre les d\u00e9fauts \u00e0 la terre<\/a> Contre l\u2019\u00e9tude du syst\u00e8me, veuillez contacter l\u2019\u00e9quipe technique pour obtenir la documentation d\u2019installation.<\/p>","protected":false},"excerpt":{"rendered":"<p>Comparez les causes des pannes de courant et des courts-circuits, la d\u00e9tection, les r\u00f4les des dispositifs de protection contre les surtensions (GFCI) et des dispositifs de protection contre les surintensit\u00e9s (AFCI), les applications de codes, les tests et les \u00e9tapes pratiques de r\u00e9initialisation et de testage s\u00e9curis\u00e9.<\/p>","protected":false},"author":1,"featured_media":5348,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[107,187,232,233],"class_list":["post-4517","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog","tag-circuit-protection","tag-afci","tag-ground-fault-vs-short-circuit","tag-gfci"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":8}},"acf":[],"_links":{"self":[{"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/posts\/4517","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/comments?post=4517"}],"version-history":[{"count":4,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/posts\/4517\/revisions"}],"predecessor-version":[{"id":5316,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/posts\/4517\/revisions\/5316"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/media\/5348"}],"wp:attachment":[{"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/media?parent=4517"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/categories?post=4517"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/chac-electric.com\/fr\/wp-json\/wp\/v2\/tags?post=4517"}],"curies":[{"name":"Bien jou\u00e9","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}