CQB2LE-125 Pemutus Sirkuit Arus Sisa dengan Perlindungan Arus Berlebih – Jenis Elektronik
Itu CQB2LE-125 RCBO provides overload, short-circuit and residual-current protection within its published 63A / 80A / 100A / 125A range. Selection should be based on the circuit voltage, conductor, load behaviour, prospective fault current and applicable installation rules—not the ampere rating alone.
Gambaran Produk
CQB2LE-125 is an RCBO for 230/400V AC distribution circuits. It combines thermal-magnetic overcurrent protection with residual-current protection in one device. The published range covers 63A / 80A / 100A / 125A, 1P+N / 2P / 3P / 3P+N / 4P, C / D curves and 30 / 50 / 75 / 100 / 300mA sensitivity options. The saved model data describes the residual-current or construction type as Electronic type; waveform type is not stated in the saved technical table.
The CQB2LE-125 is a 125A RCBO option for high current RCBO projects that require integral overcurrent and residual-current protection.
The saved model record lists IEC 60947-2; GB/T 14048.2 as the applicable standard reference. It also lists CCC certification; scope must be confirmed for the ordered configuration.
Fitur Utama
Aplikasi Biasa
Typical use is in final or sub-distribution circuits where both overcurrent and residual-current protection are required. The project must still confirm the expected residual-current waveform, sensitivity, neutral arrangement, pole configuration, fault level, conductor size, enclosure conditions and local wiring rules.
Permohonan dan Panduan Pemilihan
Use the verified model values below to create a shortlist, then validate the complete circuit. Product ratings do not replace conductor calculations, a fault-current study, coordination review or local installation requirements.
| Titik pemilihan | CQB2LE-125 reference | Hal yang harus dipastikan oleh proyek tersebut |
|---|---|---|
| Rated current | 63A / 80A / 100A / 125A | Design current, conductor ampacity, installation method, ambient temperature and grouping |
| Voltage and frequency | 230/400V AC; 50Hz | Supply system and equipment rating |
| Konfigurasi tiang | 1P+N / 2P / 3P / 3P+N / 4P | Conductors to be switched/protected, including neutral treatment |
| Trip curve | C / D | Load inrush and required disconnection performance |
| Residual-current selection | 30 / 50 / 75 / 100 / 300mA; Electronic type; waveform type is not stated in the saved technical table | Expected waveform, sensitivity, purpose and local rules |
| Kapasitas pemecahan | 10kA or 6kA lower type (Icu) | Prospective short-circuit current and protection coordination |
Protection Scope
An RCBO combines overcurrent and residual-current protection; it is not simply an MCB with a different label.
MCB vs RCBO
Compare Protection Functions →
Residual-Current Selection
Published options: 30 / 50 / 75 / 100 / 300mA. Confirm sensitivity and waveform type for the actual circuit and market.
Sensitivity & Type
Review Selection Support →
Breaking Capacity and Curve
10kA or 6kA lower type (Icu); C / D curves. Both fault level and load inrush must be checked.
Fault Level & Inrush
Compare Breaking Capacity →
Pole and Wiring Arrangement
Published pole options: 1P+N / 2P / 3P / 3P+N / 4P. Use the exact model diagram; do not assume neutral routing.
Poles & Neutral
Confirm Wiring Data →
Panduan Pemesanan
- Specify the exact model: CQB2LE-125.
- State the required current rating within 63A / 80A / 100A / 125A.
- Confirm pole arrangement: 1P+N / 2P / 3P / 3P+N / 4P.
- Confirm trip curve: C / D.
- Confirm residual-current sensitivity and type from the published 30 / 50 / 75 / 100 / 300mA options.
- Provide system voltage, expected fault level, destination market, quantity and document requirements.
Pengujian Instalasi dan Koordinasi
- Use the exact model drawing and instructions; do not infer supply direction, neutral routing or terminal positions from another product.
- Verify conductor material and cross-section against the circuit calculation and published terminal data.
- Confirm fault level, upstream/downstream coordination, enclosure temperature, grouping, altitude and clearances.
- Installation, isolation, testing and maintenance must be carried out by qualified personnel under applicable rules.
Penamaan tipe

Tripping curves

Dimensi (mm)

Spesifikasi Teknis
| Parameter | |
| Voltan yang diukur | 230V~ (1P+N/2P), 400V~ (3P/3P+N/4P) |
| Rated current | 63A, 80A, 100A, 125A |
| Number of poles | 1P+N, 2P, 3P, 3P+N, 4P |
| Rated breaking capacity Icu (A) | 10000 A, 6000 A (Lower type) |
| Rated sensitivity IΔn | 30 mA, 50 mA, 75 mA, 100 mA, 300 mA |
| Mechanical & Electrical life | Mechanical ≥ 8500, Electrical ≥ 1500 |
| Tripping curves | C, D |
| Tightening torque (N·m) | 3.5 |
| Pollution degree | 2 |
| Degree of protection | IP20 |
| Overvoltage category | Ⅲ |
| Standar | IEC 60947-2, GB/T 14048.2 |
| Sertifikasi | CCC |
Tripping characteristics (Reference temperature 30°C)
| Item | Tripping Curve | Test current In(A) | Initial Status | Time limit for tripping or non-tripping | Expected result | Remarks |
| a | C, D | 1.05In | Cold | 1h(In≤63A) 2h(In>63A) |
Non-tripping | Current smoothly rises to specified value within 5s |
| b | C, D | 1.3In | Following item a test | 1h(In≤63A) 2h(In>63A) |
Tripping | |
| c | C, D | 2In | Cold | 1s<t<300s | Tripping | |
| d | C | 8In×80% | Cold | t ≤ 0.2s | Non-tripping | Switch on the power supply by closing the auxiliary switch |
| D | 12In×80% | |||||
| e | C | 8In×80% | Cold | t < 0.2s | Tripping | Switch on the power supply by closing the auxiliary switch |
| D | 12In×80% |
Note: The term “cold” means that the test is carried out at a reeference calibration temperature without load before the test.
Persyaratan konduktor dan bagian penampang
| Sisi pelipis tembaga (mm2) | Rated current In(A) |
| 16 | 63A |
| 25 | 80A |
| 35 | 100A |
| 50 | 125A |
Mengapa Memilih CHAC
Dengan pengalaman manufaktur lebih dari 30 tahun, 1100+ karyawan, dan 100M+ tiang
kapasitas tahunan dan produksi otomatis 90% unit, CHAC memberikan kapasitas produksi yang stabil dan ketat
Pengendalian kualitas untuk pelanggan OEM/ODM global. Sistem manufaktur internal kami mendukung jangka panjang
Kerjasama untuk merek-merek listrik, importir dan distributor.
30+
BERKALI-KALI BERKEMBANG
Mengkhususkan diri dalam manufaktur listrik tegangan rendah
1100+
KARYAWAN
Tim profesional memastikan kualitas dan pengiriman yang stabil
100 juta+
Kapasitas Bulanan POKER
Kapasitas produksi berskala besar untuk memenuhi permintaan global
90%
PENGELOLAAN PRODUKSI AUTOMATIS
Otomasi canggih untuk efisiensi dan konsistensi yang tinggi

Barisan Perakitan Otomatis

Laboratorium Pengujian

Injeksi & Stamping

Pemeriksaan Kualitas





Sistem kontrol kualitas yang ketat memastikan setiap produk memenuhi standar global.
Apa yang Dapat Kami Sesuaikan?
For CQB2LE-125 projects, CHAC can review private-label marking, packaging, approved appearance options, published 63A / 80A / 100A / 125A electrical configurations and technical-document requirements. Requests outside the published range are subject to engineering evaluation, testing, minimum order quantity and project feasibility.
Logo & Branding
Pilihan penandaan merek pribadi dan plakat nama tunduk pada pemeriksaan karya seni dan persetujuan sampel.

Kemasan
Kustomisasi
Kotak karton, label, dan manual dapat disiapkan sesuai spesifikasi pesanan yang telah disetujui dan pasar tujuan.

Elektrik
Kustomisasi
Select from the published 63A / 80A / 100A / 125A, 1P+N / 2P / 3P / 3P+N / 4P and C / D options; non-standard requests require technical evaluation.

Produk
Penampilan
Appearance options can be reviewed subject to tooling, minimum order quantity, marking requirements and technical feasibility.

Sertifikasi
Dukungan
Datasheets, drawings and verified certificate information are supplied for the applicable approved configuration.

Teknologi
Pembangunan
Penunjang proyek dapat mencakup review desain, evaluasi sampel, pengujian, dan perencanaan produksi, dengan ketentuan persetujuan teknis.

Unduh
Breaker Sederhana Seri CQB2
Complete product overview for low-voltage electrical components and product selection reference.
Butuh Dokumen Teknis?
Hubungi kami untuk mendapatkan data spesifikasi, sertifikat, gambar, panduan pemilihan, atau dukungan proyek OEM/ODM.
CQB2LE-125 Product FAQ
What is the CQB2LE-125 RCBO?
The CQB2LE-125 combines overload and short-circuit protection with residual-current protection. Its verified range is 63A / 80A / 100A / 125A with 1P+N / 2P / 3P / 3P+N / 4P configurations; the exact ordered option must match the circuit and local rules.
How does the CQB2LE-125 RCBO work?
A thermal-magnetic mechanism responds to overload and short-circuit conditions, while the residual-current function monitors imbalance between conductors and trips when the applicable threshold is reached. It does not remove the need for correct earthing, circuit design or testing.
How is the CQB2LE-125 RCBO different from an MCB or RCCB?
An MCB provides overcurrent protection but not residual-current protection. An RCCB provides residual-current protection but normally needs separate overcurrent protection. The CQB2LE-125 combines both functions in one product, within its published ratings.
Can the CQB2LE-125 RCBO be used as a circuit breaker?
It can provide the overcurrent and residual-current functions stated for the model, but only when 230/400V AC, 63A / 80A / 100A / 125A, 10kA or 6kA lower type (Icu) and the residual-current requirements all suit the circuit. It should not be treated as a universal replacement for every breaker.
What are the selection limitations of the CQB2LE-125 RCBO?
The principal checks are residual-current sensitivity (30 / 50 / 75 / 100 / 300mA), residual-current or construction type (Electronic type; waveform type is not stated in the saved technical table), trip curve (C / D), pole arrangement (1P+N / 2P / 3P / 3P+N / 4P) and short-circuit data (10kA or 6kA lower type (Icu)). Board space, neutral handling, coordination and destination-market rules also have to be verified.
How should the CQB2LE-125 RCBO be wired and tested?
Use only the diagram and terminal identification supplied for the exact ordered model. Confirm supply direction, protected neutral arrangement, conductor size, torque and isolation procedure, then perform the prescribed test-button and functional checks. Qualified personnel should complete the work under local rules.
Confirm the Right CQB2LE-125 Configuration
Send the current rating, poles, trip curve, system voltage, expected fault level, destination market and quantity, plus residual-current sensitivity and type. CHAC will review the request against the published model range.