Pemutus Sirkuit Berkas DC Seri CQM5NEZ

Pemutus sirkuit CHAC CQM5NEZ DC tersedia dengan unit trip magnetik saja atau termal-magnetik untuk rangkaian DC 1500V. Pilih versi termal-magnetik jika memerlukan perlindungan overload maupun short-circuit. Frame 350A dan 630A mencakup arus nominal mulai dari 63A hingga 630A, dengan kapasitas pemutusan yang ditentukan oleh frame dan versi M/H.

Model:
CQM5NEZ-350 / CQM5NEZ-630
Polandia:
2P
Nilai arus:
63–350A (350 frame); 350 / 400 / 500 / 630A (630 frame)
Voltan yang diukur:
1500V DC
Breaking Capacity:
Icu = Ics pada tegangan DC 1500 V: 20kA (350 M / 630 M); 30kA (350 H), τ = 2ms
Unit Perjalanan:
Hanya menggunakan magnet atau menggunakan magnet termal, sesuai dengan kode rilis
Tingkat tegangan isolasi:
1800V
Pengaturan:
One-Stop Service OEM/ODM

Product Overview

The CHAC CQM5NEZ 1500V DC molded case circuit breaker uses two-pole 350A and 630A frames. Magnetic-only and thermal-magnetic releases address different protection designs, while the M/H code identifies the available breaking-capacity version.

For importers, distributors and equipment manufacturers, CHAC can review the requested configuration against the circuit requirements and destination-market documents. Agree the exact model, drawings and marking requirements before sample approval or a repeat order.

Key Selection Points

  • Frame and current: 350 frame: 63–350A; 630 frame: 350/400/500/630A. Confirm the exact available current step.
  • Breaking capacity: 350 M: 20kA; 350 H: 30kA; 630 M: 20kA. Values are at DC1500V, Ics = Icu, with the stated 2ms time constant.
  • Trip function: Magnetic-only or thermal-magnetic. Confirm whether integral overload protection is required.
  • Terminations: 350: M8, 15N·m ±5%; 630: M10, 25N·m ±5%. Use the matching terminal and torque instructions for the selected frame.

Typical Applications

Evaluate CQM5NEZ for DC distribution assemblies where its documented interruption duty matches the circuit. For battery or energy-storage projects, include the prospective fault current and DC time constant in the review; a voltage match alone is insufficient.

Applications and Selection Guide

Selection item CQM5NEZ configuration Hal yang harus diverifikasi
Frame and current 350 frame: 63–350A; 630 frame: 350/400/500/630A Confirm the exact available current step.
Kapasitas pemecahan 350 M: 20kA; 350 H: 30kA; 630 M: 20kA Values are at DC1500V, Ics = Icu, with the stated 2ms time constant.
Trip function Magnetic-only or thermal-magnetic Confirm whether integral overload protection is required.
Terminations 350: M8, 15N·m ±5%; 630: M10, 25N·m ±5% Use the matching terminal and torque instructions for the selected frame.

Use these checks to compare the protection function, configuration and related CHAC products before specifying CQM5NEZ. Related products are selection alternatives or system components, not automatic replacements.

Compare CQD5NEZ for the required function

The CHAC CQD5NEZ DC isolator switch is designed for circuit isolation at up to 1500V DC. Two frame sizes cover rated currents from 80A to 630A, with front or side operation to suit the equipment layout.

Related ProductSystem DesignVerify Compatibility

Compare CQM5HU for the required function

The CHAC CQM5HU molded case circuit breaker offers magnetic-only and thermal-magnetic configurations for 800V and 1140V AC distribution circuits. Select a thermal-magnetic version when both overload and short-circuit protection are required. Its 320A and 630A frames offer different current ranges and breaking capacities, so selection should match the system voltage, frame and trip unit.

Related ProductSystem DesignVerify Compatibility

Need Help Specifying CQM5NEZ?

Send the circuit requirements, selected configuration, destination market and quantity for a model-specific review.

Minta Penawaran Harga

Check the DC fault duty as well as the voltage

DC interruption depends on circuit conditions as well as the nominal voltage. The CQM5NEZ data states a 2ms time constant for its published short-circuit capacities. Submit the project fault level and time constant for engineering review, especially for battery-fed systems.

Keep the frame and M/H code together

The 30kA rating belongs to the 350 H configuration; it is not a series-wide rating. A 630 frame does not automatically have a higher breaking capacity. Include frame, capacity code, trip function, current and accessory requirements in the purchase order.

How to Specify a CQM5NEZ Order

Use the configuration details below in the purchase specification. Keep the approved drawing revision and product identification with the order so repeat deliveries can be checked consistently.

Order detail Information to include
Frame and current 350 frame: 63–350A; 630 frame: 350/400/500/630A — Confirm the exact available current step.
Kapasitas pemecahan 350 M: 20kA; 350 H: 30kA; 630 M: 20kA — Values are at DC1500V, Ics = Icu, with the stated 2ms time constant.
Trip function Magnetic-only or thermal-magnetic — Confirm whether integral overload protection is required.
Terminations 350: M8, 15N·m ±5%; 630: M10, 25N·m ±5% — Use the matching terminal and torque instructions for the selected frame.
Project and documents Supply the application, installation conditions and destination-market document requirements.
Quantity and identification State the quantity, sample requirement, packaging language and any proposed branding; confirm feasibility before approval.

Check Installation Fit Before Approval

  • Use the CQM5NEZ dimension drawing to verify mounting, terminal access, operating clearance and conductor bending space.
  • Confirm conductor preparation, terminal compatibility and tightening instructions for the exact configuration. A conductor reference table does not replace project cable sizing.
  • Review temperature, enclosure conditions and the protective arrangement with the equipment designer. Do not infer compatibility from a similar model name.
  • Have qualified personnel install and verify the equipment using the model instructions and applicable isolation and testing procedures.

Type designation

No. Code Description
① CQ Company Code
② M Pemutus Sirkuit dengan Case yang Diproses
③ 5 Design Code
④ NEZ New Energy – DC
⑤ 350 / 630 Frame Size
⑥ M / H Breaking Capacity Code: M = Standard Type; H = High Breaking Type
⑦ 2 Number of Poles: 2P
⑧ 2/3 Release Code: 2 = Magnetic Only; 3 = Thermal-Magnetic
⑨ □ Internal Accessory Code: See Accessory Code Reference
⑩ □ Operating Mode:Direct handle / Optional rotary handle
⑪ □ Rated Current
⑫ □ Rated Voltage
⑬ □ Accessory Voltage

Operating Conditions

Operating Altitude ≤ 5000 m
Storage Temperature -40℃ to +75℃
Relative Humidity ≤ 50% at +40℃; up to 90% at +20℃
Pollution Degree 3
Protection Degree IP20
Pemasangan Vertical or horizontal
Vertical Installation Inclination ≤ 5°

Accessory List

Code Accessory
0 None
10 Shunt Release
20 Auxiliary Contact
40 Shunt Release + Auxiliary Contact

Technical Specifications

Parameter CQM5NEZ-350 CQM5NEZ-630
Frame Size 350 630
Rated Current In (A) 63, 80, 100, 125, 140, 160, 180, 200, 225, 250, 280, 315, 320, 350 350, 400, 500, 630
Number of Poles 2P 2P
Rated Operational Voltage Ue DC1500V DC1500V
Rated Insulation Voltage Ui 1800V 1800V
Rated Impulse Withstand Voltage Uimp 12kV 12kV
Breaking Capacity Class M / H M
Ics = 100% Icu @ DC1500V M: 20kA / H: 30kA (τ=2ms) 20kA (τ=2ms)
Electrical Endurance 1,000 cycles 1,000 cycles
Mechanical Endurance 10,000 cycles 5,000 cycles
Terminal Screw M8 M10
Terminal Tightening Torque 15N·m (±5%) 25N·m (±5%)
Mounting Screw M4 M4
Mounting Screw Torque 1.5N·m (±5%) 1.5N·m (±5%)
Overall Dimensions (L×W×H) 200 × 83 × 132mm 205 × 102 × 167mm

Recommended Conductor Cross-Section

Rated Current In (A) 63 80 100 125 140/160 180/200/225 250 315 320/350 400 500 630
Conductor Cross-Section (mm²) 16 25 35 50 70 95 120 185 185 240 2×50 2×95

Time-current characteristic curve

Overall and mounting dimensions

CQM5NEZ-350

CQM5NEZ-630

Mengapa Memilih CHAC

CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQM5NEZ, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.

01

CONFIRM THE SPECIFICATION

Agree the CQM5NEZ configuration, circuit duty and installation requirements.

02

REVIEW THE DOCUMENTS

Confirm model-specific drawings and destination-market requirements.

03

APPROVE THE SAMPLE

Record the accepted configuration and marking requirements.

04

DEFINE ORDER CHECKS

Agree packaging, identification and delivery requirements in the quotation.

CHAC Automated Assembly Line

Barisan Perakitan Otomatis

CHAC Testing Laboratory

Laboratorium Pengujian

CHAC Injection & Stamping

Injeksi & Stamping

CHAC Quality Inspection

Pemeriksaan Kualitas

Apa yang Dapat Kami Sesuaikan?

Discuss CQM5NEZ product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.

Logo & Branding

Submit logo artwork and marking requirements for review against the available print area and mandatory product markings.

CHAC CQM5NEZ product view

Packaging & Manuals

Define carton labels, packaging language, product identification and instruction requirements for the destination market.

CHAC CQM5NEZ product view

Configuration Selection

Specify CQM5NEZ with the required frame and current, operating conditions and protection duty. Confirm the complete order combination.

CHAC CQM5NEZ product view

Assembly Requirements

Provide the mounting and connection requirements for review. Changes to the housing, terminals or operating arrangement require engineering approval.

CHAC CQM5NEZ product view

Market Documentation

Request documents covering the exact CQM5NEZ model and destination market. A standard reference alone is not evidence of certification.

CHAC CQM5NEZ product view

Sample Approval

Agree the sample specification, drawing revision and acceptance criteria before confirming a production order.

CHAC CQM5NEZ product view

Technical Documents and Support

DOC

CQM5NEZ Technical Documents

Request the CQM5NEZ datasheet, configuration drawing, installation instructions and available model-specific market documents.Request Datasheet

SUP

Need Technical Documents?

Send the application, electrical requirements, assembly layout and destination market for configuration and document review.Hubungi Kami

CQM5NEZ Product FAQ

What is the difference between CQM5NEZ M and H?

The codes identify breaking-capacity versions. At DC1500V and the stated 2ms time constant, the 350 frame lists M at 20kA and H at 30kA. The 630 frame lists M at 20kA. Confirm the exact ordered combination.

Is a 1500V DC MCCB suitable for any battery system?

No. Verify prospective fault current, circuit time constant, current direction, wiring and the protective coordination. The voltage label alone does not establish suitability for every energy-storage circuit.

Can the magnetic-only version provide overload protection?

Not by itself. Specify the thermal-magnetic release when integral overload protection is needed, or provide a separately coordinated overload device. Include the release code in the order.

How do I choose the CQM5NEZ current rating?

Start with load current and conductor capacity, then check trip function, enclosure temperature and protection coordination. Use an available current step within the chosen frame; frame size alone is not the circuit protection setting.

Can I copy a cable size from the CQM5NEZ table?

Treat the conductor table as a product reference. Final sizing also depends on installation method, conductor material, temperature, grouping, voltage drop, short-circuit duty and local rules. Check terminal compatibility and the model-specific torque.

What should a distributor specify when ordering CQM5NEZ?

State frame, rated current, operating voltage, breaking-capacity version, trip function and accessory voltages. Include drawings, destination-market documents, quantity and marking requirements; approve the exact configuration before a repeat order.

Specify the Right CQM5NEZ Configuration

Send CHAC your required configuration, application, destination market and estimated quantity. We will review the requested specification and provide the relevant technical documents and commercial proposal.

Minta Penawaran Harga