PXB6L-63 Electromagnetic Residual Current Operated Circuit Breaker
Itu PXB6L-63 RCBO menyediakan perlindungan dari overload, korsleting, dan sisa arus dalam kisaran 6A–63A yang tercantum dalam spesifikasinya. Pilihan harus didasarkan pada tegangan sirkuit, konduktor, perilaku beban, arus malfungsi yang diprediksi, dan aturan instalasi yang berlaku—bukan hanya berdasarkan rating ampere saja.
Gambaran Produk
PXB6L-63 is an RCBO for 230V AC (1P+N/2P) or 400V AC (3P+N/4P) distribution circuits. It combines thermal-magnetic overcurrent protection with residual-current protection in one device. The published range covers 6A–63A, 1P+N / 2P / 3P+N / 4P, B / C / D curves and 30 / 50 / 100 / 300mA sensitivity options. The saved model data describes the residual-current or construction type as Type AC / Type A; electromagnetic construction.
The PXB6L-63 supports 3 phase RCBO projects through its 3P+N RCBO option, alongside 1P+N, 2P and 4P configurations.
The saved model record lists IEC 61009-1; GB/T 16917.1 as the applicable standard reference. It also lists CE, CB, CCC and DEKRA certification; scope must be confirmed for the ordered configuration.
Fitur Utama
Aplikasi Biasa
Typical use is in final or sub-distribution circuits where both overcurrent and residual-current protection are required. The project must still confirm the expected residual-current waveform, sensitivity, neutral arrangement, pole configuration, fault level, conductor size, enclosure conditions and local wiring rules.
Permohonan dan Panduan Pemilihan
Use the verified model values below to create a shortlist, then validate the complete circuit. Product ratings do not replace conductor calculations, a fault-current study, coordination review or local installation requirements.
| Titik pemilihan | PXB6L-63 reference | Hal yang harus dipastikan oleh proyek tersebut |
|---|---|---|
| Rated current | 6A–63A | Design current, conductor ampacity, installation method, ambient temperature and grouping |
| Voltage and frequency | 230V AC (1P+N/2P) or 400V AC (3P+N/4P); 50/60Hz | Supply system and equipment rating |
| Konfigurasi tiang | 1P+N / 2P / 3P+N / 4P | Conductors to be switched/protected, including neutral treatment |
| Trip curve | B / C / D | Load inrush and required disconnection performance |
| Residual-current selection | 30 / 50 / 100 / 300mA; Type AC / Type A; electromagnetic construction | Expected waveform, sensitivity, purpose and local rules |
| Kapasitas pemecahan | 6kA Ics | Prospective short-circuit current and protection coordination |
Protection Scope
An RCBO combines overcurrent and residual-current protection; it is not simply an MCB with a different label.
MCB vs RCBO
Compare Protection Functions →
Residual-Current Selection
Published options: 30 / 50 / 100 / 300mA. Confirm sensitivity and waveform type for the actual circuit and market.
Sensitivity & Type
Review Selection Support →
Breaking Capacity and Curve
6kA Ics; B / C / D curves. Both fault level and load inrush must be checked.
Fault Level & Inrush
Compare Breaking Capacity →
Pole and Wiring Arrangement
Published pole options: 1P+N / 2P / 3P+N / 4P. Use the exact model diagram; do not assume neutral routing.
Poles & Neutral
Confirm Wiring Data →
Panduan Pemesanan
- Specify the exact model: PXB6L-63.
- State the required current rating within 6A–63A.
- Confirm pole arrangement: 1P+N / 2P / 3P+N / 4P.
- Confirm trip curve: B / C / D.
- Confirm residual-current sensitivity and type from the published 30 / 50 / 100 / 300mA options.
- Provide system voltage, expected fault level, destination market, quantity and document requirements.
Ordering Specification
Please specify the following when ordering:
- Product Model: PXB6L-63
- Number of Poles: 1P+N,2P,3P+N,4P
- Rated Current & Tripping Curve: e.g., C/25A
- Tripping Curve (Type): B, C, D
- Rated Current (In): 6A, 10A, 16A, 20A, 25A, 32A,40A, 50A, 63A
- Residual Current Operation:
- Residual Current Type: AC, A
- Rated Residual Operating Current (IΔn): 30mA, 50mA,100mA, 300mA
- Quantity: e.g., 100 pcs
- PXB6L-63 1P+N C/25A 30mA AC 100 pcs
The quantity shown is an ordering example, not a minimum order quantity.
Pengujian Instalasi dan Koordinasi
The conductor table is a product reference. Final sizing depends on installation method, ambient temperature, grouping, voltage drop, conductor material and local rules.
- Use the exact model drawing and instructions; do not infer supply direction, neutral routing or terminal positions from another product.
- Verify conductor material and cross-section against the circuit calculation and published terminal data.
- Confirm fault level, upstream/downstream coordination, enclosure temperature, grouping, altitude and clearances.
- Installation, isolation, testing and maintenance must be carried out by qualified personnel under applicable rules.
Penamaan tipe

Tripping curves

Dimensi (mm)

Spesifikasi Teknis
| Parameter | Spesifikasi |
|---|---|
| Rated Voltage (V) | 230V~(1P+N、2P)/400V~(3P+N、4P) |
| Rated Current (A) | 6、10、16、20、25、32、40、50、63 |
| Number of Poles | 1P+N, 2P, 3P+N, 4P |
| Rated Short-Circuit Breaking Capacity Ics(A) | 6000A |
| Rated Residual Operating Current IΔn(mA) | 30、50、100、300 |
| Rated Residual Non-Operating Current ΔIΔno(mA) | 0.5IΔn |
| Rated Residual Make and Break Capacity IΔm(A) | 2000A |
| Residual Current Tripping Time | ≤0.03s |
| Residual Current Trip Type | AC Type、A Type |
| Mechanical Endurance | ≥6000 |
| Electrical Endurance | ≥4000 |
| Tripping curves | B、C、D |
| Pollution Degree | 2 |
| Protection Class | IP 20 |
| Installation Category | Ⅲ |
| Standar | IEC61009-1, GB/T16917.1 |
| Sertifikasi | CE CB CCC|DEKRA Certified |
Tripping Characteristics (Reference Temperature: 30°C)
| Test | Rated Current In (A) | Initial State | Test Current | Tripping / Non-Tripping Time | Hasilnya | Curve / Remarks |
|---|---|---|---|---|---|---|
| Delay | ≤63 | Cold | 1.13In | ≤1h | Non-tripping | |
| Delay | ≤63 | Following previous test | 1.45In | <1h | Tripping | Current smoothly rises to specified value in 5s |
| Delay | ≤32 | Cold | 2.55In | 1<t<60s | Tripping | |
| Delay | >32 | Cold | 2.55In | 1<t<120s | Tripping | |
| Instantaneous | Any value | Cold | 3、5、10In | ≤0.1s | Non-tripping | B、C、D |
| Instantaneous | Any value | Cold | 5、10、20In | <0.1s | Tripping | B、C、D |
Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.
Persyaratan konduktor dan bagian penampang
| Copper cross-section(mm²) | Rated current In(A) |
|---|---|
| 1 | In≤6 |
| 1.5 | 6<In≤13 |
| 2.5 | 13<In≤20 |
| 4 | 20<In≤25 |
| 6 | 25<In≤32 |
| 10 | 32<In≤50 |
| 16 | 50<In≤63 |
Mengapa Memilih CHAC
Dengan pengalaman manufaktur lebih dari 30 tahun, 1100+ karyawan, dan 100M+ tiang
kapasitas tahunan dan produksi otomatis 90% unit, CHAC memberikan kapasitas produksi yang stabil dan ketat
Pengendalian kualitas untuk pelanggan OEM/ODM global. Sistem manufaktur internal kami mendukung jangka panjang
Kerjasama untuk merek-merek listrik, importir dan distributor.
30+
BERKALI-KALI BERKEMBANG
Mengkhususkan diri dalam manufaktur listrik tegangan rendah
1100+
KARYAWAN
Tim profesional memastikan kualitas dan pengiriman yang stabil
100 juta+
Kapasitas Bulanan POKER
Kapasitas produksi berskala besar untuk memenuhi permintaan global
90%
PENGELOLAAN PRODUKSI AUTOMATIS
Otomasi canggih untuk efisiensi dan konsistensi yang tinggi

Barisan Perakitan Otomatis

Laboratorium Pengujian

Injeksi & Stamping

Pemeriksaan Kualitas





Sistem kontrol kualitas yang ketat memastikan setiap produk memenuhi standar global.
Apa yang Dapat Kami Sesuaikan?
For PXB6L-63 projects, CHAC can review private-label marking, packaging, approved appearance options, published 6A–63A electrical configurations and technical-document requirements. Requests outside the published range are subject to engineering evaluation, testing, minimum order quantity and project feasibility.
Logo & Branding
Pilihan penandaan merek pribadi dan plakat nama tunduk pada pemeriksaan karya seni dan persetujuan sampel.

Kemasan
Kustomisasi
Kotak karton, label, dan manual dapat disiapkan sesuai spesifikasi pesanan yang telah disetujui dan pasar tujuan.

Elektrik
Kustomisasi
Select from the published 6A–63A, 1P+N / 2P / 3P+N / 4P and B / C / D options; non-standard requests require technical evaluation.

Produk
Penampilan
Appearance options can be reviewed subject to tooling, minimum order quantity, marking requirements and technical feasibility.

Sertifikasi
Dukungan
Datasheets, drawings and verified certificate information are supplied for the applicable approved configuration.

Teknologi
Pembangunan
Penunjang proyek dapat mencakup review desain, evaluasi sampel, pengujian, dan perencanaan produksi, dengan ketentuan persetujuan teknis.

Unduh
PXB6 Series Miniature Circuit Breaker
Complete product overview for low-voltage electrical components and product selection reference.
Butuh Dokumen Teknis?
Hubungi kami untuk mendapatkan data spesifikasi, sertifikat, gambar, panduan pemilihan, atau dukungan proyek OEM/ODM.
PXB6L-63 Product FAQ
What is the PXB6L-63 RCBO?
The PXB6L-63 combines overload and short-circuit protection with residual-current protection. Its verified range is 6A–63A with 1P+N / 2P / 3P+N / 4P configurations; the exact ordered option must match the circuit and local rules.
How does the PXB6L-63 RCBO work?
A thermal-magnetic mechanism responds to overload and short-circuit conditions, while the residual-current function monitors imbalance between conductors and trips when the applicable threshold is reached. It does not remove the need for correct earthing, circuit design or testing.
How is the PXB6L-63 RCBO different from an MCB or RCCB?
An MCB provides overcurrent protection but not residual-current protection. An RCCB provides residual-current protection but normally needs separate overcurrent protection. The PXB6L-63 combines both functions in one product, within its published ratings.
Can the PXB6L-63 RCBO be used as a circuit breaker?
It can provide the overcurrent and residual-current functions stated for the model, but only when 230V AC (1P+N/2P) or 400V AC (3P+N/4P), 6A–63A, 6kA Ics and the residual-current requirements all suit the circuit. It should not be treated as a universal replacement for every breaker.
What are the selection limitations of the PXB6L-63 RCBO?
The principal checks are residual-current sensitivity (30 / 50 / 100 / 300mA), residual-current or construction type (Type AC / Type A; electromagnetic construction), trip curve (B / C / D), pole arrangement (1P+N / 2P / 3P+N / 4P) and short-circuit data (6kA Ics). Board space, neutral handling, coordination and destination-market rules also have to be verified.
How should the PXB6L-63 RCBO be wired and tested?
Use only the diagram and terminal identification supplied for the exact ordered model. Confirm supply direction, protected neutral arrangement, conductor size, torque and isolation procedure, then perform the prescribed test-button and functional checks. Qualified personnel should complete the work under local rules.
Confirm the Right PXB6L-63 Configuration
Send the current rating, poles, trip curve, system voltage, expected fault level, destination market and quantity, plus residual-current sensitivity and type. CHAC will review the request against the published model range.












