PXB6-40 Miniature Circuit Breaker

Product Features

■ Enhanced Safety Design: Compact 1P+N configuration with simultaneous phase and neutral disconnection for improved maintenance safety.

■ Dual Electrical Protection: Integrated overload and short-circuit protection provides reliable circuit protection.

■ Reliable Isolation: Provides effective electrical isolation in the OFF position for safer maintenance.

■ Versatile Applications: Suitable for industrial, commercial, high-rise building, and residential electrical systems.

Ordering Specification

Please specify the following when ordering:

1.Product Model: PXB6-40

2.Number of Poles: 1P+N

3.Rated Current & Tripping Curve: [e.g., C/16A]

  • Tripping Curve (Type): B, C, D
  • Rated Current (In): 6, 10, 16, 20, 25, 32, 40A

5.Quantity: [e.g., 100 pcs]

Ordering Example:

PXB6-40 1P+N C/16A 100 pcs

Technical Specifications

Parameter
Rated Voltage (V) 230/240V
Rated Insulation Voltage (Ui) 400V
Rated Impulse Withstand Voltage (Uimp) 4000V
Rated Current (In) 6、10、16、20、25、32、40
Rated Frequency 50/60Hz
Number of Poles 1P+N
Rated Short-Circuit Breaking Capacity (Icn = Ics) 4500A
Mechanical Endurance ≥10000
Electrical Endurance ≥4000
Instantaneous Tripping Type B、C、D
Grid Spacing 50mm
Degree of Protection IP 20
Standards Compliance IEC60898-1,GB/T 10963.1
Certificazione CE·CB·CCC | DEKRA Certified

Tripping Characteristics (Reference Temperature: 30℃)

Item Tripping Curve Test Current (A) Initial Status Time limit for tripping or non-tripping Expected result Remarks
a B,C,D 1.13ln Cold t ≤ 1h Non-tripping Current smoothly rises to specified value within 5s
b B,C,D 1.45ln Following item a test t < 1h Tripping
c B,C,D 2.55ln Cold 1s < t < 60s (ln ≤ 32A) Tripping
1s < t < 120s (ln >32A)
d B 3ln Cold t ≤ 0.1s Non-tripping Switch on the power supply by closing the auxiliary switch
C 5ln
D 10ln
e B 5ln Cold t < 0.1s Tripping Switch on the power supply by closing the auxiliary switch
C 10ln
D 20ln

Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.

Conductor requirements and cross section

Copper cross-section(mm2) Rated current ln(A)
1 ln≤6
1.5 6 < ln≤13
2.5 13 < ln≤20
4 20 < ln≤25
6 25 < ln≤32
10 32 < ln≤40

Type designation

Tripping curves

Dimensions(mm)