{"id":3400,"date":"2026-08-06T09:00:00","date_gmt":"2026-08-06T09:00:00","guid":{"rendered":"https:\/\/chac-electric.com\/blog\/type-b-mcb-selection-for-panels\/"},"modified":"2026-10-14T06:50:16","modified_gmt":"2026-10-14T06:50:16","slug":"type-b-mcb-selection-for-panels","status":"publish","type":"post","link":"https:\/\/chac-electric.com\/pt\/blog\/type-b-mcb-selection-for-panels\/","title":{"rendered":"Quest\u00f5es de Sele\u00e7\u00e3o de Disjuntores (MCB) Tipo B para Quadros de Distribui\u00e7\u00e3o"},"content":{"rendered":"<p>Type B MCB selection is a trip-curve decision tied to the load, cable and fault conditions. Under IEC 60898-1, Type B describes a magnetic tripping range of 3\u20135 times rated current for products within that standard\u2019s scope; it is not a shortcut for approving every lighting, motor or electronic load.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-large wp-image-3432 aligncenter\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4-1024x683.webp\" alt=\"Quest\u00f5es de Sele\u00e7\u00e3o de Disjuntores (MCB) Tipo B para Quadros de Distribui\u00e7\u00e3o\" width=\"1024\" height=\"683\" srcset=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4-1024x683.webp 1024w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4-300x200.webp 300w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4-768x512.webp 768w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4-18x12.webp 18w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4-600x400.webp 600w, https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/4.webp 1536w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><\/p>\n<h2 id=\"contents\">Separate the trip curve from the rest of the protection design<\/h2>\n<p>Record the load type, normal current, expected inrush, conductor capacity, prospective short-circuit current, disconnection time and <a href=\"https:\/\/chac-electric.com\/pt\/blog\/6ka-vs-10ka-mcb-breaking-capacity\/\">capacidade de quebra<\/a> before comparing curves. The <strong><a href=\"https:\/\/chac-electric.com\/pt\/mcb\/\">MCB category<\/a><\/strong> can then be narrowed to models whose marked curve and ratings match the schedule.<\/p>\n<h2 id=\"part-1-what-decision-does-a-type-b-mcb-review-support\">What does a Type B review actually decide?<\/h2>\n<p>It decides whether the instantaneous magnetic behaviour is suitable for the circuit\u2019s expected inrush and fault conditions. It does not decide pole count, residual-current type, enclosure size or compliance by itself.<\/p>\n<h2 id=\"part-2-which-load-and-circuit-inputs-should-be-collected-first\">Which load and circuit inputs should be collected first?<\/h2>\n<p>Collect steady-state current, cable installation method, ambient and grouping conditions, load technology, transformer or motor starting behaviour, fault-loop impedance and the applicable installation rules. An apparently low-current circuit can still have an inrush profile that affects curve selection.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/07\/cqb2-63-series-miniature-circuit-breakers-for-power-systems-cqb2-63-4-600x600.webp\" alt=\"Disjuntor Miniatura CQB2-63\" \/><\/p>\n<h2 id=\"part-3-how-should-curve-intent-be-written-on-the-drawing\">How should the curve intent appear on the schedule?<\/h2>\n<p>List the curve, rated current, pole configuration, voltage, breaking capacity and standard as separate fields. The selected model\u2019s marking and datasheet should be returned with the quotation so the reviewer can see exactly what was proposed.<\/p>\n<h2 id=\"part-4-where-do-nuisance-trip-and-discrimination-questions-appear\">Where do nuisance trips and discrimination enter the review?<\/h2>\n<p>A higher magnetic threshold may reduce nuisance operation during inrush, but it can also make the required disconnection harder to achieve under a low fault current. Check the worst-case fault-loop impedance and coordination rather than choosing the curve from stock availability.<\/p>\n<h2 id=\"part-5-what-belongs-in-a-type-b-mcb-rfq\">What should a Type B request contain?<\/h2>\n<p>Send the circuit schedule, load description, current, conductor details, supply voltage, fault level, trip curve, breaking capacity, <a href=\"https:\/\/chac-electric.com\/pt\/blog\/selecao-de-dr-de-tres-polos-vs-quatro-polos\/\">pole arrangement<\/a> and required documents. Avoid using \u201cType B\u201d without stating whether the request concerns an MCB curve rather than an RCD waveform type.<\/p>\n<h2 id=\"part-6-which-chac-product-route-starts-the-sourcing-discussion\">Which CHAC product page should be checked first?<\/h2>\n<p>Review the <strong><a href=\"https:\/\/chac-electric.com\/pt\/product\/cqb2-63-miniature-circuit-breaker\/\">CQB2-63 MCB page<\/a><\/strong> for the exact model information available, then compare the requested curve and ratings with the project schedule. Do not generalize one model\u2019s data to the entire category.<\/p>\n<h2 id=\"part-7-where-does-type-b-curve-selection-need-a-protection-revisit\">When should curve selection return to the protection designer?<\/h2>\n<p>Return to the designer when the circuit includes motors, transformers, LED drivers, long cable runs, high fault levels or a local rule that changes the disconnection calculation. The <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66269\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60898-1 publication record<\/a> is a standards reference, not a product approval.<\/p>\n<p>The final <strong>Type B trip curve<\/strong> decision should therefore be visible beside the rated current, breaking capacity and fault-loop assumptions, rather than hidden in a supplier\u2019s model code.<\/p>\n<h2 id=\"faqs\">FAQs<\/h2>\n<h3>What does Type B refer to on an MCB?<\/h3>\n<p>It refers to a trip-curve intent defined by the product standard family and confirmed on the selected model markings.<\/p>\n<h3>Can Type B be chosen because it is commonly stocked?<\/h3>\n<p>Stock availability is not a design approval; match the curve to the circuit and project rules first.<\/p>\n<h3>How is this different from pole-count selection?<\/h3>\n<p>Pole count and trip curve answer different questions and should be specified as separate RFQ fields.<\/p>\n<h3>What load information helps the curve review?<\/h3>\n<p>Provide load type, expected inrush context, and the circuit schedule notes that define operating expectations.<\/p>\n<h3>What should the supplier confirm in writing?<\/h3>\n<p>Confirm the proposed model identification, marked trip curve, and the documents requested in the RFQ.<\/p>\n<h3>When should the curve decision be locked?<\/h3>\n<p>Lock it after the load list and protection review are complete, before the panel bill of materials is released.<\/p>\n<h2 id=\"references\">Refer\u00eancias<\/h2>\n<ul>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66269\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60898-1 MCB requirements<\/a><\/li>\n<li><a href=\"https:\/\/eshop.se.com\/sg\/miniaturecircuitbreakermcbeasy9pro1p25abcurve6000aiecen60898-1-ez9f27125.html\" rel=\"nofollow noopener\" target=\"_blank\">Schneider Electric Type B example and product data<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66277\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60947-2 industrial circuit-breakers<\/a><\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<p>Type B MCB selection is a trip-curve decision tied to the load, cable and fault conditions. Under IEC 60898-1, Type B describes a magnetic tripping range of 3\u20135 times rated current for products within that standard\u2019s scope; it is not a shortcut for approving every lighting, motor or electronic load. Separate the trip curve from [&hellip;]<\/p>\n","protected":false},"author":10,"featured_media":3432,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[],"class_list":["post-3400","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":8}},"acf":[],"_links":{"self":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts\/3400","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/users\/10"}],"replies":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/comments?post=3400"}],"version-history":[{"count":4,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts\/3400\/revisions"}],"predecessor-version":[{"id":4834,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts\/3400\/revisions\/4834"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/media\/3432"}],"wp:attachment":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/media?parent=3400"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/categories?post=3400"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/tags?post=3400"}],"curies":[{"name":"bom jogo","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}