{"id":3857,"date":"2026-08-28T00:00:00","date_gmt":"2026-08-28T00:00:00","guid":{"rendered":"https:\/\/chac-electric.com\/?p=3857"},"modified":"2026-08-28T00:00:00","modified_gmt":"2026-08-28T00:00:00","slug":"devo-usar-uma-caixa-de-derivacao-de-plastico-ou-de-metal","status":"publish","type":"post","link":"https:\/\/chac-electric.com\/pt\/blog\/should-i-use-plastic-or-metal-junction-box\/","title":{"rendered":"Devo utilizar uma caixa de deriva\u00e7\u00e3o de pl\u00e1stico ou de metal?"},"content":{"rendered":"<p>Quando a Elena, uma engenheira de sistemas de controlo em Monterrey, especificou uma caixa de jun\u00e7\u00e3o compacta para uma linha de embalamento de alimentos, escolheu um inv\u00f3lucro n\u00e3o met\u00e1lico e avan\u00e7ou com a instala\u00e7\u00e3o. Durante a coloca\u00e7\u00e3o em servi\u00e7o, o sinal do variador de velocidade (VFD) ficou com interfer\u00eancias, a tampa empenou perto de um motor quente e um bucim de cabo soltou-se ap\u00f3s lavagens repetidas. A solu\u00e7\u00e3o r\u00e1pida foi substituir a caixa, mas a investiga\u00e7\u00e3o detetou um problema de especifica\u00e7\u00e3o: o anexo tinha ignorado a liga\u00e7\u00e3o equipotencial, a compatibilidade eletromagn\u00e9tica (EMC), a temperatura e a carga nas entradas. O material correto era uma decis\u00e3o de sistema, e n\u00e3o um simples veredito de qualidade do produto.<\/p>\n<p><strong>Resumo:<\/strong> A <strong>caixa de deriva\u00e7\u00e3o met\u00e1lica<\/strong> \u00e9 habitualmente o ponto de partida mais seguro onde a liga\u00e7\u00e3o equipotencial, a blindagem, o impacto ou a dissipa\u00e7\u00e3o t\u00e9rmica importam; uma caixa de pl\u00e1stico devidamente selecionada pode ser a melhor resposta para a corros\u00e3o, o peso e o isolamento el\u00e9trico. Confirme o ambiente de instala\u00e7\u00e3o, o volume de condutores, o m\u00e9todo de liga\u00e7\u00e3o \u00e0 terra e as evid\u00eancias de ensaio do inv\u00f3lucro antes de encomendar. O artigo 314 da NFPA 70 rege muitas decis\u00f5es relativas a caixas e ao volume de condutores nos Estados Unidos, enquanto a IEC 60670-1 e a IEC 60529 abordam as expectativas relativas a inv\u00f3lucros e \u00e0 prote\u00e7\u00e3o contra penetra\u00e7\u00e3o em projetos baseados nas normas IEC.<\/p>\n<figure class=\"article-hero\"><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/chac-metal-plastic-junction-box-scene-20260828.webp\" alt=\"Controls engineer comparing a plastic and metal junction box beside a low-voltage distribution panel.\" \/><\/figure>\n<p>Uma caixa de jun\u00e7\u00e3o protege emendas, terminais e transi\u00e7\u00f5es, mantendo um sistema el\u00e9trico oper\u00e1vel. \u201cPl\u00e1stico\u201d pode significar PVC, policarbonato, ABS ou um pol\u00edmero refor\u00e7ado com fibra de vidro; \u201cmetal\u201d pode significar a\u00e7o galvanizado, a\u00e7o inoxid\u00e1vel, alum\u00ednio ou uma liga revestida. Encare o inv\u00f3lucro como parte da prote\u00e7\u00e3o do circuito e do m\u00e9todo de instala\u00e7\u00e3o, e n\u00e3o como uma cobertura decorativa.<\/p>\n<h2>Comece pelo ambiente, n\u00e3o pelo r\u00f3tulo do material<\/h2>\n<p>Percorra o local de montagem proposto e registe as piores condi\u00e7\u00f5es cred\u00edveis. Salas limpas interiores, f\u00e1bricas poeirentas, coberturas exteriores, locais costeiros, zonas de lavagem e \u00e1reas perigosas classificadas criam requisitos muito diferentes. Uma caixa de pol\u00edmero n\u00e3o enferruja, mas alguns pl\u00e1sticos amolecem, fendilham ou perdem resist\u00eancia ao impacto sob exposi\u00e7\u00e3o \u00e0 radia\u00e7\u00e3o ultravioleta ou contacto com solventes. Uma caixa de a\u00e7o pode fornecer uma barreira robusta, mas uma extremidade cortada e desprotegida pode corroer rapidamente em ambientes com n\u00e9voa salina.<\/p>\n<p>Especifique o grau de prote\u00e7\u00e3o (IP) pretendido utilizando o regime aplic\u00e1vel ao projeto. A norma IEC 60529 define o c\u00f3digo IP atrav\u00e9s da prote\u00e7\u00e3o contra s\u00f3lidos e \u00e1gua; uma classifica\u00e7\u00e3o IP s\u00f3 \u00e9 v\u00e1lida quando o conjunto completo \u2014 tampa, junta, buchas, tamp\u00f5es e interface de montagem \u2014 tiver sido avaliado. Os tipos de inv\u00f3lucro NEMA constituem um sistema de classifica\u00e7\u00e3o norte-americano separado, pelo que n\u00e3o deve converter um n\u00famero IP num tipo NEMA por mera suposi\u00e7\u00e3o. Pergunte ao fornecedor quais os testes e detalhes de constru\u00e7\u00e3o que sustentam a classifica\u00e7\u00e3o declarada.<\/p>\n<p>Para locais corrosivos, compare a exposi\u00e7\u00e3o qu\u00edmica real e o regime de limpeza. O a\u00e7o inoxid\u00e1vel pode superar o a\u00e7o pintado, enquanto um policarbonato compat\u00edvel pode evitar problemas galv\u00e2nicos. Verifique a caixa, a junta, o bucim, o conduta e os fixadores como um \u00fanico conjunto de materiais. \u201cResistente \u00e0 corros\u00e3o\u201d n\u00e3o \u00e9 uma certifica\u00e7\u00e3o universal; associe-a a um material, acabamento e limite de teste ou de aplica\u00e7\u00e3o declarados.<\/p>\n<h2>A equipotencialidade, a liga\u00e7\u00e3o \u00e0 terra e a compatibilidade eletromagn\u00e9tica (CEM) s\u00e3o fun\u00e7\u00f5es de conce\u00e7\u00e3o<\/h2>\n<h3>Quando o metal ajuda<\/h3>\n<p>Um inv\u00f3lucro condutor pode ser ligado ao sistema de terra de prote\u00e7\u00e3o, criando um caminho de defeito de baixa imped\u00e2ncia quando instalado com ferragens de liga\u00e7\u00e3o homologadas ou aprovadas. Os Artigos 250 e 314 da NFPA 70 abordam a liga\u00e7\u00e3o \u00e0 terra, a equipotencialidade e a instala\u00e7\u00e3o de caixas em trabalhos nos E.U.A.; o m\u00e9todo exato depende do m\u00e9todo de cablagem, da constru\u00e7\u00e3o da caixa e das emendas locais. Uma caixa met\u00e1lica n\u00e3o fica automaticamente ligada \u00e0 terra por contacto com um suporte pintado ou com uma contraporca de tubo corrugado solta \u2014 verifique a continuidade desde o inv\u00f3lucro at\u00e9 ao condutor de prote\u00e7\u00e3o do equipamento.<\/p>\n<p>O metal tamb\u00e9m pode ajudar a conter o ru\u00eddo irradiado por variadores de velocidade, contactores e fontes de alimenta\u00e7\u00e3o comutada. O desempenho de compatibilidade eletromagn\u00e9tica (EMC) continua a depender do encaminhamento dos cabos, do desenho dos bucins, da termina\u00e7\u00e3o da blindagem, das uni\u00f5es das portas e da liga\u00e7\u00e3o equipotencial \u00e0s frequ\u00eancias corretas. Uma caixa de a\u00e7o fina com bucins de pl\u00e1stico e um terminal de cabo (\u00abpigtail\u00bb) comprido pode ter um desempenho pior do que um inv\u00f3lucro de pol\u00edmero bem concebido com uma segrega\u00e7\u00e3o rigorosa dos cabos. Encare a blindagem como um item de teste do sistema, e n\u00e3o como uma promessa baseada no material.<\/p>\n<h3>Quando o pl\u00e1stico \u00e9 intencional<\/h3>\n<p>O pl\u00e1stico \u00e9 isolante, pelo que n\u00e3o se pode tornar numa superf\u00edcie sob tens\u00e3o acidental e pode simplificar a coordena\u00e7\u00e3o do isolamento. N\u00e3o elimina a necessidade de uma terra de prote\u00e7\u00e3o: as pe\u00e7as condutoras expostas no interior da caixa, os bucins met\u00e1licos, as calhas DIN ou as blindagens ainda podem necessitar de liga\u00e7\u00e3o equipotencial. Onde for utilizada uma caixa de pl\u00e1stico, especifique como as entradas met\u00e1licas e o hardware interno s\u00e3o ligados, e documente a separa\u00e7\u00e3o entre os circuitos de pot\u00eancia e de sinal.<\/p>\n<p>Para instrumenta\u00e7\u00e3o ou medi\u00e7\u00e3o sens\u00edvel, pe\u00e7a o plano de EMC do projeto. Utilize uma caixa condutora, blindagem interna ou entrada filtrada apenas onde a avalia\u00e7\u00e3o de risco o justificar. Para uma uni\u00e3o seca b\u00e1sica, o pl\u00e1stico pode ser adequado e mais f\u00e1cil de instalar.<\/p>\n<h2>Comparar o calor, o impacto e a vida \u00fatil<\/h2>\n<p>O comportamento t\u00e9rmico \u00e9 frequentemente descurado. Os condutores e os terminais geram calor; as paredes met\u00e1licas geralmente dissipam-no melhor do que os pol\u00edmeros, mas a \u00e1rea da parede, a cor, a ventila\u00e7\u00e3o e a montagem tamb\u00e9m importam. Utilize os limites de temperatura do fabricante e as regras de desclassifica\u00e7\u00e3o do projeto; numa caixa exposta ao sol, o ganho solar pode ser dominante, independentemente do material.<\/p>\n<p>O impacto e a vibra\u00e7\u00e3o favorecem um design de material e de parede adequado ao perigo. O a\u00e7o resiste ao esmagamento e a golpes de ferramentas; os pl\u00e1sticos de engenharia podem absorver impactos sem amassar ou expor o metal nu. Analise as evid\u00eancias relevantes de testes de impacto, a durabilidade das dobradi\u00e7as e dos fechos, e a reten\u00e7\u00e3o dos elementos de fixa\u00e7\u00e3o. Em maquinaria, adicione al\u00edvio de tens\u00e3o para que o movimento dos cabos n\u00e3o seja transferido diretamente para a parede da caixa ou para o bloco de terminais.<\/p>\n<p>O custo do ciclo de vida inclui m\u00e3o de obra, substitui\u00e7\u00e3o, inspe\u00e7\u00e3o e tempo de inatividade \u2014 e n\u00e3o apenas o pre\u00e7o unit\u00e1rio. Uma caixa de pol\u00edmero mais leve pode reduzir o tempo de instala\u00e7\u00e3o e o frete, enquanto o metal pode resistir a uma f\u00e1brica mais agressiva. Compare os intervalos de assist\u00eancia, a comunalidade de pe\u00e7as sobressalentes, a substitui\u00e7\u00e3o de juntas, o tratamento contra a corros\u00e3o e o acesso para manuten\u00e7\u00e3o. Solicite um or\u00e7amento para o projeto com o material e os testes necess\u00e1rios.<\/p>\n<table>\n<caption>Compara\u00e7\u00e3o de materiais para decis\u00f5es de caixas de jun\u00e7\u00e3o B2B<\/caption>\n<thead>\n<tr>\n<th>Dimens\u00e3o de decis\u00e3o<\/th>\n<th>Inv\u00f3lucro de pl\u00e1stico<\/th>\n<th>Inv\u00f3lucro met\u00e1lico<\/th>\n<th>Quest\u00e3o de contrata\u00e7\u00e3o p\u00fablica<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Corros\u00e3o<\/td>\n<td>Bom contra muitos ambientes aquosos; verificar solventes e UV.<\/td>\n<td>O acabamento e a liga determinam o desempenho; as op\u00e7\u00f5es em a\u00e7o inoxid\u00e1vel adequam-se a exposi\u00e7\u00f5es severas.<\/td>\n<td>Que qu\u00edmicos, sal e agentes de limpeza est\u00e3o presentes?<\/td>\n<\/tr>\n<tr>\n<td>Equilibra\u00e7\u00e3o de potenciais e compatibilidade eletromagn\u00e9tica<\/td>\n<td>Isolamento por predefini\u00e7\u00e3o; as entradas met\u00e1licas necessitam de uma liga\u00e7\u00e3o equipotencial definida.<\/td>\n<td>Pode fornecer uma blindagem colada e um percurso de defeito quando a continuidade for verificada.<\/td>\n<td>Onde \u00e9 que a terra de prote\u00e7\u00e3o \u00e9 ligada e testada?<\/td>\n<\/tr>\n<tr>\n<td>Impacto e vibra\u00e7\u00e3o<\/td>\n<td>Escolha um pol\u00edmero resistente a impactos e pontos de fixa\u00e7\u00e3o refor\u00e7ados.<\/td>\n<td>Normalmente resistente a esmagamento; amolgadas e danos no revestimento necessitam de inspe\u00e7\u00e3o.<\/td>\n<td>Que evid\u00eancia de impacto, bin\u00e1rio e vibra\u00e7\u00e3o est\u00e1 dispon\u00edvel?<\/td>\n<\/tr>\n<tr>\n<td>Comportamento t\u00e9rmico<\/td>\n<td>Condutividade mais baixa; verificar os limites de aumento de temperatura e de amolecimento.<\/td>\n<td>Normalmente dissipa melhor o calor; a temperatura da superf\u00edcie e a redu\u00e7\u00e3o de pot\u00eancia (derating) continuam a aplicar-se.<\/td>\n<td>Qual \u00e9 a dissipa\u00e7\u00e3o interna m\u00e1xima e a temperatura ambiente?<\/td>\n<\/tr>\n<tr>\n<td>Instala\u00e7\u00e3o<\/td>\n<td>Leve e f\u00e1cil de furar; evite estilha\u00e7ar e apertar em demasia.<\/td>\n<td>Pode necessitar de rebarbagem, pontes de liga\u00e7\u00e3o equipotencial e prote\u00e7\u00e3o contra a corros\u00e3o.<\/td>\n<td>Que gl\u00e2ndulas, ferramentas e acess\u00f3rios de uni\u00e3o s\u00e3o aprovados?<\/td>\n<\/tr>\n<tr>\n<td>Ciclo de vida \/ TCO<\/td>\n<td>Pode reduzir a m\u00e3o de obra e o peso; a substitui\u00e7\u00e3o depende da vida \u00fatil face aos UV e aos produtos qu\u00edmicos.<\/td>\n<td>Pode custar mais a manusear, mas pode reduzir o tempo de inatividade relacionado com danos.<\/td>\n<td>Qual \u00e9 a estrat\u00e9gia de manuten\u00e7\u00e3o e pe\u00e7as sobressalentes a cinco anos?<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Dimensionar a caixa para condutores, profundidade e entradas<\/h2>\n<p>The most common field error is choosing by outside dimensions alone. Calculate conductor volume under the applicable code, including insulated conductors, internal clamps, grounding conductors, and fittings. Leave room for bending radius and a technician\u2019s hand; a box that technically fits may still force sharp bends or damaged insulation. For U.S. installations, NFPA 70 Article 314.16 provides box-fill rules and 314.28 addresses larger raceway bodies and angle pulls. For other markets, use the adopted wiring rules and the equipment maker\u2019s instructions.<\/p>\n<p>Depth matters when terminals, DIN rail, ferrules, or shield clamps project into the enclosure. Confirm the usable internal depth after the gasket, cover, mounting plate, and cable-gland nut are installed. Count entries by function: power, control, sensor, drain, and spare. Maintain separation between high-energy and low-level circuits, and reserve blanking plugs for unused holes so the ingress rating is not compromised.<\/p>\n<table>\n<caption>Application and dimension worksheet (confirm final dimensions with the supplier)<\/caption>\n<thead>\n<tr>\n<th>Aplica\u00e7\u00e3o<\/th>\n<th>Useful starting envelope<\/th>\n<th>Depth\/entry considerations<\/th>\n<th>Evid\u00eancia a solicitar<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Simple indoor splice<\/td>\n<td>Small box sized from conductor volume plus bend space<\/td>\n<td>One or two glands; keep a spare entry sealed<\/td>\n<td>Fill calculation, temperature range, installation instructions<\/td>\n<\/tr>\n<tr>\n<td>Control-panel branch wiring<\/td>\n<td>Medium box with room for terminals or DIN rail<\/td>\n<td>Allow wire duct exit, ferrule clearance, and shield routing<\/td>\n<td>Internal drawing, terminal compatibility, EMC guidance<\/td>\n<\/tr>\n<tr>\n<td>Outdoor sensor junction<\/td>\n<td>Weatherproof envelope selected for cable count and solar load<\/td>\n<td>UV-stable gasket, downward entries, drain strategy<\/td>\n<td>IP\/NEMA test basis, UV and impact information<\/td>\n<\/tr>\n<tr>\n<td>Industrial motor\/VFD area<\/td>\n<td>Metal or reinforced polymer sized for heat and segregation<\/td>\n<td>Large bend radius, strain relief, shield termination, bonding point<\/td>\n<td>Temperature-rise data, bonding method, EMC test plan<\/td>\n<\/tr>\n<tr>\n<td>Wash-down or corrosive process<\/td>\n<td>Material and gasket selected from chemical compatibility review<\/td>\n<td>Avoid crevices; specify stainless or compatible polymer hardware<\/td>\n<td>Material data, gasket compound, cleaning-chemical limits<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>For a quick design review, document the maximum conductor count, largest conductor size, entry diameters, internal devices, ambient range, and target IP or NEMA classification. Then ask for a drawing showing usable\u2014not merely external\u2014dimensions. This is the practical meaning of <strong>metal electrical junction box sizes<\/strong>: the correct size satisfies fill, bend, heat, entry, and service clearances together.<\/p>\n<h2>Read standards and certification claims precisely<\/h2>\n<p>Standards have different jobs. NFPA 70 is an installation code adopted and amended by the authority having jurisdiction (AHJ); it is not a product certificate. IEC 60670-1 sets general requirements and tests for boxes and enclosures for electrical accessories in household and similar fixed installations, while IEC 60529 defines the IP Code test classification. UL 514A covers metallic outlet boxes and fittings, and UL 514C covers nonmetallic outlet boxes, flush-device boxes, and covers within its scope. A reference to a standard does not, by itself, prove that a particular model is certified or listed.<\/p>\n<p>Ask for the exact model, edition, scope, and certificate or listing database entry where certification is required. Verify that the tested configuration includes the cover, gasket, glands, and accessories you will buy. A supplier may provide a design tested to an IEC method without holding a UL certification; conversely, a listed box may still be unsuitable for a project\u2019s IP, chemical, or temperature requirement. The AHJ, utility, insurer, or end customer may impose additional rules, so confirm the destination-market requirement before purchase.<\/p>\n<h2>A procurement workflow that prevents rework<\/h2>\n<ol>\n<li>Write an environment brief: indoor\/outdoor, UV, water, dust, chemicals, impact, vibration, ambient temperature, and hazardous-area status.<\/li>\n<li>Complete the electrical brief: conductor sizes and counts, circuit voltage, fault level, grounding method, EMC risk, terminals, and cable-entry types.<\/li>\n<li>Set measurable acceptance criteria: usable dimensions, fill and bend allowance, target IP\/NEMA type, material\/finish, impact or heat evidence, and required markings.<\/li>\n<li>Request a drawing, bill of materials, test reports, and certification details for the exact configuration; identify what remains the installer\u2019s responsibility.<\/li>\n<li>Run a sample installation and continuity, ingress, torque, and thermal checks before releasing a repeat order.<\/li>\n<\/ol>\n<p>CHAC Electric can be considered when a project needs configurable low-voltage enclosure options and clear application documentation. Its CQMG03 series public information describes tidy cabinet wiring and centralized wire splitting for low-voltage distribution panels and industrial control equipment; treat that as an application fit, then confirm the exact model, dimensions, materials, and evidence for your project. For a broader comparison, see the <a href=\"https:\/\/chac-electric.com\/pt\/blogue\/distribution-box-vs-junction-box-installation-guide\/\"><strong>electric junction box<\/strong><\/a> guide and the <a href=\"https:\/\/chac-electric.com\/pt\/blogue\/outdoor-electrical-junction-box-selection\/\"><strong>outdoor electrical junction box<\/strong><\/a> article.<\/p>\n<figure class=\"article-hero\"><img decoding=\"async\" src=\"https:\/\/chac-electric.com\/wp-content\/uploads\/2026\/08\/chac-junction-box-material-reference-20260828.webp\" alt=\"Procurement team reviewing enclosure dimensions, cable entries, and bonding notes for an industrial junction-box order.\" \/><\/figure>\n<h2>Frequently asked questions<\/h2>\n<h3>Which is better, plastic or metal junction boxes?<\/h3>\n<p>Neither is universally better. Choose metal when verified bonding, EMC shielding, heat spreading, or high impact resistance is central; choose a compatible plastic when corrosion, weight, or electrical isolation dominates. Confirm the complete assembly\u2019s ingress, temperature, and impact evidence.<\/p>\n<h3>Do metal junction boxes need to be grounded?<\/h3>\n<p>Usually, yes, when the box is an exposed conductive part within the applicable wiring rules. Bond it to the protective earthing conductor using the specified screw, clip, jumper, or listed fitting, and verify continuity after painting or modifications. The AHJ and adopted code determine the final method.<\/p>\n<h3>Are plastic junction boxes safe?<\/h3>\n<p>They can be safe when their material, temperature, impact, flammability, ingress, and conductor-volume limits match the installation. Plastic does not remove the need to bond internal metal parts or to protect cables from strain and abrasion. Use the manufacturer&#8217;s instructions and the project code rather than relying on the word &#8220;plastic.&#8221;<\/p>\n<h3>What size junction box should I use?<\/h3>\n<p>Calculate required conductor volume, then add space for fittings, grounding conductors, terminals, bend radius, heat, and service access. Check usable internal dimensions and entry layout, not only the outside length, width, and depth. Have the calculation reviewed against NFPA 70 Article 314 or the locally adopted wiring standard.<\/p>\n<p>For product-family context, review CHAC\u2019s <a href=\"https:\/\/chac-electric.com\/pt\/product\/cqmg20c-series-distribution-box\/\">CQMG20C series distribution box<\/a>, then send the project environment, conductor schedule, preferred material, and destination market to the supplier for a configuration check. The best box is the one whose selection logic remains visible after installation: right material, right bond, right volume, and right evidence.<\/p>\n<h2>Refer\u00eancias<\/h2>\n<ol>\n<li><a href=\"https:\/\/www.nfpa.org\/codes-and-standards\/nfpa-70-standard-development\/70\" rel=\"nofollow noopener\" target=\"_blank\">NFPA 70, National Electrical Code (Articles 250 and 314)<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/6029\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60670-1, Boxes and enclosures for electrical accessories<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2452\" rel=\"nofollow noopener\" target=\"_blank\">IEC 60529, Degrees of protection provided by enclosures (IP Code)<\/a><\/li>\n<li><a href=\"https:\/\/www.shopulstandards.com\/ProductDetail.aspx?productId=UL514A\" rel=\"nofollow noopener\" target=\"_blank\">UL 514A, Metallic Outlet Boxes, Electrical<\/a><\/li>\n<li><a href=\"https:\/\/www.shopulstandards.com\/ProductDetail.aspx?productId=UL514C\" rel=\"nofollow noopener\" target=\"_blank\">UL 514C, Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers<\/a><\/li>\n<\/ol>\n<p>Choose the box by the conditions it must survive, the conductors it must contain, and the evidence an inspector can verify. For a project-ready conversation about the CQMG03 connection solution, visit <a href=\"https:\/\/chac-electric.com\/pt\/product\/cqmg03-series-distribution-junction-box-connection-solutions\/\">CHAC\u2019s CQMG03 series distribution junction box connection solutions<\/a> and contact the team with your drawings and schedule.<\/p>","protected":false},"excerpt":{"rendered":"<p>Caixa de deriva\u00e7\u00e3o em pl\u00e1stico ou metal? Compare a liga\u00e7\u00e3o \u00e0 terra, EMC, IP\/NEMA, corros\u00e3o, impacto, dimensionamento, normas, custo do ciclo de vida e aquisi\u00e7\u00e3o para projetos B2B.<\/p>","protected":false},"author":1,"featured_media":3855,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[],"class_list":["post-3857","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":7}},"acf":[],"_links":{"self":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts\/3857","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/comments?post=3857"}],"version-history":[{"count":1,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts\/3857\/revisions"}],"predecessor-version":[{"id":3878,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/posts\/3857\/revisions\/3878"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/media\/3855"}],"wp:attachment":[{"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/media?parent=3857"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/categories?post=3857"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/chac-electric.com\/pt\/wp-json\/wp\/v2\/tags?post=3857"}],"curies":[{"name":"bom jogo","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}