PXB6LE-63B Electronic Residual Current Operated Circuit-Breaker with Overcurrent Protection

Product Features

■ Earth Leakage Protection – Detects electric shock or leakage current and cuts off power rapidly.

■ Overload Protection – Prevents equipment damage from circuit overload.

■ Short-Circuit Protection – Responds to short-circuit faults for enhanced safety.

■ Fast Response – Leakage tripping time ≤0.3s to ensure personal safety.

Ordering Specification

Please specify the following when ordering:

1.Product Model: PXB6LE-63B

2.Number of Poles: 1P+N, 2P, 3P+N, 4P

  • Rated Current & Tripping Curve: [e.g., C/25A]
  • Tripping Curve (Type): B, C, D

3.Rated Current (In): 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A

  • Residual Current Operation:
  • Residual Current Type: B

4.Rated Residual Operating Current (IΔn): 30mA, 50mA, 100mA, 300mA

Quantity: [e.g., 100 pcs

5.Ordering Example:

PXB6LE-63B 1P+N C/25A 30mA B 100 pcs

Technical Specifications

Parameter
Rated Voltage (V) 230V~(1P+N、2P)/400V~(3P+N、4P)
Rated Current (A) 6、10、16、20、25、32、40、50、63
Number of Poles 1P+N, 2P, 3P+N, 4P
Rated Short-Circuit Breaking Capacity Ics(A) 6000A
Rated Residual Operating Current IΔn(mA) 30、50、100、300
Rated Residual Non-Operating Current IΔno(mA) 0.5IΔn
Rated Residual Make and Break Capacity IΔm(A) 3000A
Residual Current Tripping Threshold ≤0.3s
Residual Current Trip Type B Type
Mechanical Endurance ≥4000
Electrical Endurance ≥4000
Tripping curves B、C、D
Pollution Degree 2
Protection Class IP 20
Installation Category Ⅲ
Standards IEC61008-1, IEC62423
Сертификация CE CB CCC|DEKRA Certified

Tripping Characteristics (Reference Temperature: 30℃)

Item Tripping Curve Test Current (A) Initial Status Time limit for tripping or non-tripping Expected result Remarks
Delay ≤63 Cold 1.13In ≤1h Non-tripping
Delay ≤63 Following previous test 1.45In <1h Tripping Current smoothly rises to specified value in 5s
Delay ≤32 Cold 2.55In 1<t<60s Tripping
Delay >32 Cold 2.55In 1<t<120s Tripping
Instantaneous Any value Cold 3、5、10In ≤0.1s Non-tripping B、C、D
Instantaneous Any value Cold 5、10、20In <0.1s Tripping B、C、D

Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.

Conductor requirements and cross section

Copper cross-section(mm²) Rated current In(A)
1 In≤6
1.5 6<In≤13
2.5 13<In≤20
4 20<In≤25
6 25<In≤32
10 32<In≤50
16 50<In≤63

Type designation

Tripping curves

Dimensions(mm)