Электромагнитный предохранитель с функцией защиты от остаточного тока PXL6-100B
Product Features
■ High-Current Range: Industrial-grade with multiple high-rated current options up to 100A.
■ Strong Protection: Powerful 6kA short-circuit breaking capacity for severe fault conditions.
■ Rugged & Reliable: High mechanical life for demanding and frequent operation.
■ System Flexibility: Available in 1P+N, 3P, 3P+N configurations for single or three-phase systems.
Technical Specifications
| Parameter | |
| Rated Voltage | 230V AC(1P+N); 400V AC(3P、3P+N) |
| Rated Current (A) | 10A、16A、20A、25A、32A、40A、50A、63A、80A、100A |
| Rated Residual Operating Current | 10mA(10A~40A), 30mA, 100mA, 400mA |
| Rated Residual Non-Operating Current | 0.5IΔn |
| Type of Residual Current(with DC component) | B type |
| Number of Poles | 1P+N、3P、3P+N |
| Rated Conditional Short-Circuit Current | 6000A |
| Rated Conditional Residual Short-Circuit Current | 6000A |
| Rated Making and Breaking Capacity | 630A(In≤63A); 10In(In>63A) |
| Rated Residual Making and Breaking Capacity | 630A(In≤63A); 10In(In>63A) |
| Tightening Torque | (2.5~3.0)N.m |
| Protection Class | IP20 |
| Pollution Degree | 2 |
| Installation Category | Ⅱ |
| Standards | GB 16916.1, IEC61008-1 |
| Сертификация | CE CB CCC |DEKRA Certified |
Operating time (for residual current devices)
| In (A) | IΔn (A) | Breaking time when the residual current equals the following values(s) | ||||
| IΔn | 2IΔn | 5IΔn | 5A、10A、20A、50A、100A、200A | IΔt | ||
| 10~100A | 0.03、0.01、0.1、0.3 | 0.3 | 0.15 | 0.04 | 0.04 | 0.04 |
Mechanical endurance&Electrical endurance
| In (A) | Number of operating cycles | Operating frequency (cycles per hour) | |
| Number of on-load operating cycles | Number of no-load operating cycles | ||
| 10~25A | 2000 | 2000 | 240 |
| 32A~100A | 2000 | 1000 | 120 |
Type designation

Dimensions(mm)