PXB6DC-63M DC Miniature Circuit Breaker

Product Features

■ Breaking capacity up to 10 kA for reliable short-circuit protection.

■ Rated current range from 0.5 A to 63 A.

■ Available in 1P, 2P, 3P and 4P configurations.

■ Mechanical endurance over 10,000 operations.

Ordering Specification

Please specify the following when ordering:

1.Product Model: PXB6DC-63M

2.Number of Poles: 1P, 2P, 3P, 4P

3.Rated Current & Tripping Curve: [e.g., 16A]

  • Rated Current (In): 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6,8, 10, 13, 16, 20, 25, 32, 40, 50, 63A

5.Quantity: [e.g., 100 pcs]

Ordering Example:

PXB6DC-63M 2P 16A 100 pcs

Technical Specifications

Parameter
Rated Voltage(V) 1P DC 125V
2P DC 250V
3P DC 375V
4P DC 500V
Rated Current(A) 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A
Rated Insulation Voltage(Ui) 500V
Ultimate Breaking Capacity(Icu)(kA) 10
Service Breaking Capacity(Ics)(kA) 7.5
Number of Poles 1P, 2P, 3P, 4P
Mechanical Endurance ≥10000
Electrical Endurance ≥1500
Termination Capacity ≤25mm²
Tightening Torque(N·m) 2.5
Protection Class IP20
Standard GB/T14048.2、IEC60947-2
Zertifizierung CE·CB·CCC |DEKRA Certified

Tripping Characteristics(Reference Temperature: 30°C)

Item Test Current (A) Initial Status Time limit for tripping or non-tripping Expected result Remarks
a 1.05In Cold t≤1h Non-tripping Current smoothly rises to specified value within 5s
b 1.3In Following item a test t<1h Tripping  
c 2.55In Cold 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
Tripping  
d 4In、8In、12In
80%
Cold t≥0.2s Non-tripping Circuit switched on by closing an auxiliary switch. Verifies rapid breaking capability.
e 4In、8In、12In
120%
Cold t<0.2s Tripping

Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.

Type designation

Tripping curves

Dimensions(mm)