PXB6DC-63M DC Miniature Circuit Breaker
ميزات المنتج
■ Breaking capacity up to 10 kA for reliable short-circuit protection.
■ Rated current range from 0.5 A to 63 A.
■ Available in 1P, 2P, 3P and 4P configurations.
■ Mechanical endurance over 10,000 operations.
مواصفات الطلب
عند الطلب، يرجى تحديد ما يلي:
1.Product Model: PXB6DC-63M
2. عدد الأقطاب: 1P, 2P, 3P, 4P
3.Rated Current & Tripping Curve: [e.g., 16A]
- Rated Current (In): 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6,8, 10, 13, 16, 20, 25, 32, 40, 50, 63A
5.Quantity: [e.g., 100 pcs]
مثال الطلب:
PXB6DC-63M 2P 16A 100 pcs
المواصفات الفنية
| معامل | |
| Rated Voltage(V) | 1P DC 125V 2P DC 250V 3P DC 375V 4P DC 500V |
| Rated Current(A) | 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A |
| Rated Insulation Voltage(Ui) | 500V |
| Ultimate Breaking Capacity(Icu)(kA) | 10 |
| Service Breaking Capacity(Ics)(kA) | 7.5 |
| Number of Poles | 1P، 2P، 3P، 4P |
| التحمل الميكانيكي | ≥10000 |
| Electrical Endurance | ≥1500 |
| Termination Capacity | ≤25mm² |
| Tightening Torque(N·m) | 2.5 |
| Protection Class | IP20 |
| قياسي | GB/T14048.2、IEC60947-2 |
| شهادة | CE·CB·CCC |DEKRA Certified |
Tripping Characteristics(Reference Temperature: 30°C)
| البند | Test Current (A) | الوضع الأولي | مدة الحد الزمني للتفعيل أو عدم التفعيل | النتيجة المتوقعة | التعليقات |
| a | 1.05In | بارد | t≤1h | عدم حدوث الانزلاق | ارتفاع مستمر إلى القيمة المحددة في غضون 5 ثوانٍ |
| b | 1.3In | بعد الاختبار في البند (أ) | t<1h | الزحف | |
| c | 2.55في | بارد | 1s<t<60s(In≤32A) 1s<t<120s(In>32A) |
الزحف | |
| d | 4In、8In、12In 80% |
بارد | t≥0.2s | عدم حدوث الانزلاق | Circuit switched on by closing an auxiliary switch. Verifies rapid breaking capability. |
| e | 4In、8In、12In 120% |
بارد | t<0.2s | الزحف |
Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.
تعيين النوع

الزوايا المتقطعة

الأبعاد (مم)