PXB6DC-63M DC Miniature Circuit Breaker

Product Features

■ Breaking capacity up to 10 kA for reliable short-circuit protection.

■ Rated current range from 0.5 A to 63 A.

■ Available in 1P, 2P, 3P and 4P configurations.

■ Mechanical endurance over 10,000 operations.

Ordering Specification

Please specify the following when ordering:

1.Product Model: PXB6DC-63M

2.Number of Poles: 1P, 2P, 3P, 4P

3.Rated Current & Tripping Curve: [e.g., 16A]

  • Rated Current (In): 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6,8, 10, 13, 16, 20, 25, 32, 40, 50, 63A

5.Quantity: [e.g., 100 pcs]

Ordering Example:

PXB6DC-63M 2P 16A 100 pcs

Caractéristiques techniques

Paramètre
Rated Voltage(V) 1P DC 125V
2P DC 250V
3P DC 375V
4P DC 500V
Rated Current(A) 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A
Rated Insulation Voltage(Ui) 500V
Ultimate Breaking Capacity(Icu)(kA) 10
Service Breaking Capacity(Ics)(kA) 7.5
Number of Poles 1P, 2P, 3P, 4P
Mechanical Endurance ≥10000
Electrical Endurance ≥1500
Termination Capacity ≤25mm²
Tightening Torque(N·m) 2.5
Protection Class IP20
Standard GB/T14048.2、IEC60947-2
Certification CE·CB·CCC |DEKRA Certified

Tripping Characteristics(Reference Temperature: 30°C)

Article Test Current (A) État initial Temps de déclenchement ou non-déclenchement Résultat attendu Commentaires
a 1.05In Froid t≤1h Non-chocant La tension actuelle augmente régulièrement jusqu'à atteindre la valeur spécifiée en 5 secondes.
b 1.3In Suite à l'essai a) t<1h Desperance  
c 2,55 en Froid 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
Desperance  
d 4In、8In、12In
80%
Froid t≥0.2s Non-chocant Circuit switched on by closing an auxiliary switch. Verifies rapid breaking capability.
e 4In、8In、12In
120%
Froid t<0.2s Desperance

Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.

Designation de type

Des courbes en virage

Dimensions(mm)