Kalkulator kW ke Ampere

Konversikan kW ke ampere untuk beban tiga fase, satu fase, atau DC. Masukkan tegangan dan faktor daya, atau alihkan ke kVA untuk daya semu.

Contoh aplikasi · Masukan ilustratif

Checking a commercial feeder before breaker selection

For a commercial distribution panel, take a balanced 18.5 kW electrical load at 400 V and power factor 0.92. Entering these values gives 29.02 A per line conductor. That current provides a starting point for reviewing CHAC PXB6-63 MCB or CQM6 MCCB data, but it does not decide the breaker model. The cable capacity, fault level and trip characteristics still need to match the circuit. If the 18.5 kW describes motor shaft output instead of electrical input, use the motor-current calculator and include efficiency.

Data produk: PXB6-63 Pemutus Sirkuit Miniatur · CQM6 Standard Molded Case Circuit Breaker (MCCB) Produsen OEM