Kontaktor AC Berdaya Tinggi Seri CQC1 dan Aksesorisnya
Itu Kontaktor AC Berdaya Tinggi Seri CQC1 dan Aksesorisnya CHAC AC contactor ini digunakan untuk pengalihan dan kontrol motor jarak jauh. Halaman ini menyertakan tabel teknis spesifik model dan gambar produk asli agar pembeli dapat memverifikasi voltase, arus, konfigurasi, pemasangan, dan standar yang berlaku sebelum melakukan pemesanan. Kesesuaian akhir tergantung pada rangkaian lengkap, metode pemasangan, dan aturan pasar tujuan.
Gambaran Produk
CQC1 Series High-Duty AC Contactor and Accessories is a AC contactor intended for remote switching and motor control. The current product record identifies it for motor starters, HVAC and automation panels. Use the exact model variant and preserved technical source as the basis for procurement rather than assuming that every family member has the same rating.
Verified source summary: Model and Meaning Note 1: 09A~95A is in the form of auxiliary contact, and 115A~800Aisconventional without auxiliary10 indicates three normally open main contacts and one normally open auxiliary contact (32A and below)01 represents three normally open main contacts and one normally closed auxiliary contact (32A and below)11 represents three normally open main contacts, one normally open and one normally closed auxili
Fitur Utama
Aplikasi Biasa
Typical use can include motor starters, HVAC and automation panels when the project confirms system voltage, current, fault or surge exposure, conductor and enclosure requirements, and the selected variant’s installation instructions. This page does not replace the project design or the authority having jurisdiction.
Permohonan dan Panduan Pemilihan
Use the following decision points with the preserved model data. Product-family descriptions explain intent, but the exact technical table controls the ordered variant.
| Titik pemilihan | Kontaktor AC Berdaya Tinggi Seri CQC1 dan Aksesorisnya | Hal yang harus dipastikan oleh proyek tersebut |
|---|---|---|
| Aplikasi | AC Contactor projects | Confirm the actual system and environment |
| Selection basis | pemrograman dan kontrol motor jarak jauh | Use the exact model and technical table |
| Pemasangan | Follow the model instructions | Check mounting, clearances and termination |
| Kepatuhan | Use the listed standard where applicable | Verify edition, scope and destination rules |
| Adjacent product | Evaluate the related CHAC family where function differs | Do not substitute without engineering review |
Function
pemrograman dan kontrol motor jarak jauh
Match the protection or switching function to the system.
Konfigurasi
Model-specific options
Confirm current, voltage, poles, terminals or accessories from the table.
Pemasangan
Mechanical and electrical fit
Check enclosure, mounting, wiring space and maintenance access.
Project evidence
Documents and test records
Retain the approved drawing, technical sheet and commissioning record.
Panduan Pemesanan
- State the exact model and variant.
- Provide the system voltage, current, frequency and load or protection function.
- Confirm mounting, terminals, accessories, enclosure and environmental conditions.
- Share quantity, destination market and required technical documents.
Pengujian Instalasi dan Koordinasi
- Verify the model’s ratings and connection arrangement against the project drawings.
- Check conductor, busbar, enclosure, clearances and tightening requirements using the product documentation.
- Coordinate upstream and downstream protection or control devices where applicable.
- Use qualified personnel for installation, testing, isolation and maintenance.
Model and Meaning

Note 1: 09A~95A is in the form of auxiliary contact, and 115A~800Aisconventional without auxiliary10 indicates three normally open main contacts and one normally open auxiliary contact (32A and below)01 represents three normally open main contacts and one normally closed auxiliary contact (32A and below)11 represents three normally open main contacts, one normally open and one normally closed auxiliary contact (40~95A).
Appearance and installation dimensions
CQC1-09 12、18、25、32

| Contactor model | Amax | Bmax | Cmax | a | C1 | C2 |
| CQC1-09、12 | 47 | 76 | 82 | 35±0.50 | 113 | 133 |
| CQC1-18 | 87 | 118 | 138 | |||
| CQC1-25 | 57 | 86 | 95 | 40±0.50 | 126 | 146 |
| CQC1-32 | 100 | 131 | 151 |
Note: C1:CQC1+F4 C2:CQC1+S4
CQC1-40、50、65、80、95

| Contactor model | Amax | Cmax | C1 | C2 |
| CQC1-4011-6511 | 77 | 116 | 145 | 165 |
| CQC1-8011~9511 | 87 | 127 | 175 | 195 |
Note:C1:CQC1+F4 C2:CQC1+S4
C0C1-115~330 overall dimensions and installation dimensions [tolerance: ± 1mm]

| CQC1 | a | P | Q | Q1 | S | Φ | f | b | b1 | M | N | c | L | G | H | Φ1 | G1 | Z | Y | X1 | |
| ≤500V | >500V | ||||||||||||||||||||
| 115 | 163.5 | 37 | 29.5 | 60 | 20 | M6 | 131 | 162 | 137 | 147 | 124 | 171 | 107 | 80 | 120-106 | 6.5 | 106 | 13.5 | 44 | 10 | 15 |
| 150 | 163.5 | 40 | 26 | 57.5 | 20 | M8 | 131 | 170 | 137 | 150 | 124 | 171 | 107 | 80 | 120-106 | 6.5 | 106 | 13.5 | 44 | 10 | 15 |
| 185 | 168.5 | 40 | 29 | 59.5 | 20 | M8 | 130 | 174 | 137 | 154 | 127 | 181 | 113.5 | 80 | 120-106 | 6.5 | 111 | 13.5 | 44 | 10 | 15 |
| 225 | 168.5 | 48 | 21 | 51.5 | 25 | M10 | 130 | 197 | 137 | 172 | 127 | 181 | 113.5 | 80 | 120-106 | 6.5 | 111 | 13.5 | 44 | 10 | 15 |
| 265 | 205 | 48 | 39 | 66.5 | 25 | M10 | 147 | 203 | 145 | 180 | 147 | 213 | 141 | 96 | 120-106 | 6.5 | 140 | 20.5 | 38 | 10 | 15 |
| 330 | 213 | 48 | 43 | 74 | 25 | M10 | 147 | 209 | 145 | 184 | 158 | 219 | 145 | 96 | 120-106 | 6.5 | 154.5 | 20.5 | 38 | 10 | 15 |
Note: f is the space required for coil replacement
X1 is the minimum electrical clearance [Flying Fox distance)the same as below
CQC1-400-500 overall dimensions and installation dimensions(tolerance: ± 1mm)

| CQC1 | a | P | Q | Q1 | S | Φ | f | b | b1 | M | N | c | L | G | G1 | Φ1 | H | Y | X1 | |
| ≤500V | >500V | |||||||||||||||||||
| 400 | 213 | 48 | 43 | 74 | 25 | M10 | 151 | 206 | 209 | 181 | 158 | 219 | 145 | 80(66-102) | 170(156-192) | 8.5 | 180 | 19.5 | 15 | 20 |
| 500 | 233 | 46 | 46 | 77 | 30 | M10 | 169 | 238 | 209 | 208 | 172 | 232 | 146 | 80(66-102) | 170(156-210) | 8.5 | 180 | 39.5 | 15 | 20 |
CQC1-630-800 overall dimensions and installation dimensions(tolerance: ± 1mm)

| CQC1 | a | P | Q | Q1 | S | Φ | f | b | b1 | M | N | c | L | G | H | Φ1 | Z | Y | X1 | |
| ≤500V | >500V | |||||||||||||||||||
| 630/800 | 309 | 80 | 60 | 89 | 40 | M12 | 201 | 304 | 280 | 264 | 202 | 255 | 155 | 180(100-195) | 180 | 10.5 | 60.5 | 68.5 | 20 | 30 |
CQC1 Series Accessories
Quick selection table/specification

Specification of auxiliary contact [air delay type]
| model | Delay range | Number of delayed contacts | Delay mode | Hook mode |
| S4-20 | 0.1s~3s | 1NO+1NC | Power on delay | Top hanging |
| S4-22 | 0.1s~30s | |||
| S4-24 | 10s~180s | |||
| S5-20 | 0.1s~3s | Power off delay | ||
| S5-22 | 0.1s~30s | |||
| S5-24 | 10s~180s |

Auxiliary contact specification
| model | Number of contacts | Hook mode | |
| Normally open [NO] | Normally Closed [NC] | ||
| F4-40 | 4 | 0 | C0C1-09~95 series contactors are top mounted CQC1-115-800 series contactors are side mounted |
| F4-31 | 3 | 1 | |
| F4-22 | 2 | 2 | |
| F4-13 | 1 | 3 | |
| F4-04 | 0 | 4 | |
| F4-20 | 2 | 0 | |
| F4-11 | 1 | 1 | |
| F4-02 | 0 | 2 | |
Technical parameters
09~95A performance index
| CQC1-09 | COC1-12 | COC1-18 | COC1-25 | COC1-32 | COC1-40 | COC1-50 | COC1-65 | CQC1-80 | CQC1-95 | |||
| Rated working current le,A(AC-3) | 400V | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 | |
| 690V | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | ||
| Agreed free air heating current lth (A) | 25 | 25 | 25 | 40 | 40 | 65 | 80 | 80 | 125 | 125 | ||
| Rated working voltage Ue (V) | 380/400、660/690 | |||||||||||
| Rated insulation voltage Ui (V) | 690V | |||||||||||
| AC-3(6le、le) | Electrical life (times) | 200×104 | 200×104 | 200×104 | 200×104 | 200×104 | 200×104 | 200×104 | 200×104 | 200×104 | 200×104 | |
| Frequent operation(h) | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 | ||
| AC-4(6le、6le ) | Electrical life (times) | 20×10 | ||||||||||
| Frequent operation(h) | 300 | |||||||||||
| Rated working current le(A) | 380/400V | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | |
| 660/690V | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||
| Mechanical life (times) | 1000×104 | 800×104 | 600×104 | |||||||||
| Auxiliary contact | Agreed free air heating current lth(A) | 10 | ||||||||||
| Electrical life (times) | AC-15(360VA) | 100×104 | 80×104 | 60×1043 | ||||||||
| DC-13(33W) | ||||||||||||
| Minimum load that can be connected | 24V 10mA | |||||||||||
| Coil | Rated control supply voltage Us (V) | AC(50Hz/60Hz)24、36、110、220、380;DC:24、48、110、220 | ||||||||||
| pull-in voltage | 85%~110%Us | |||||||||||
| Release voltage | 20%~75% US(AC)10%~75% Us(DC) | |||||||||||
| 50Hz AC coil power (VA) | start | 65 | 65 | 65 | 100 | 100 | 200 | 200 | 200 | 200 | 200 | |
| Sorption | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||
| DC coil power (w) | start | 11 | 11 | 11 | 13 | 13 | 22 | 22 | 22 | 22 | 22 | |
| Sorption | ||||||||||||
| Wiring capacity of termina mm²(min/max) | Non prefabricated end cord | 1 piece | 1/4 | 1.5/6 | 1.5/10 | 2.5/10 | 2.5/25 | 4/50 | ||||
| 2 pieces | 1/4 | 1.5/6 | 1.5/6 | 2.5/10 | 2.5/16 | 4/25 | ||||||
| Flexible wire with prefabricated end | 1 piece | 1/4 | 1/6 | 1/6 | 1/9 | 2.5/25 | 4/50 | |||||
| 2 pieces | 1/2.5 | 1/4 | 1/4 | 1.5/6 | 2.5/10 | 4/16 | ||||||
| Non prefabricated end hard wire | 1 piece | 1/4 | 1.5/6 | 1.5/6 | 1.5/10 | 2.5/25 | 4/50 | |||||
| 2 pieces | 1/4 | 1.5/6 | 1.5/6 | 1.5/10 | 2.5/16 | 4/25 | ||||||
| Tightening torque of main circuit wiring | N·M | 1.7 | 2.5 | 5 | 9 | |||||||
115A-800A performance index
| technical parameter | CQC1-115 | CQC1-150 | CQC1-185 | CQC1-225 | CQC1-265 | CQC1-330 | CQC1-400 | CQC1-500 | CQC1-630 | CQC1-800 | ||
| Rated working current le(A) | AC-3 | 400V | 115 | 150 | 185 | 225 | 265 | 330 | 400 | 500 | 630 | 800 |
| 690V | 86 | 107 | 118 | 135 | 172 | 225 | 305 | 355 | 460 | 485 | ||
| AC-4 | 400V | 52 | 60 | 79 | 85 | 105 | 117 | 138 | 147 | 188 | 242 | |
| 690V | 49 | 57 | 69 | 82 | 98 | 107 | 135 | 145 | 170 | 215 | ||
| Maximum rated power of controllable three-phase squirrel cage motor Pe (k) | AC-3 | 400V | 55 | 75 | 90 | 110 | 132 | 160 | 200 | 250 | 335 | 450 |
| 690V | 80 | 100 | 110 | 129 | 160 | 220 | 280 | 335 | 450 | 475 | ||
| AC-4 | 400V | 25 | 30 | 40 | 45 | 55 | 63 | 75 | 80 | 100 | 129 | |
| 690V | 45 | 51 | 63 | 75 | 90 | 100 | 129 | 140 | 160 | 200 | ||
| Agreed free air heating current lth (A) | 200 | 200 | 280 | 280 | 360 | 360 | 580 | 580 | 850 | 850 | ||
| Rated working voltage Ue (V) | 400、690 | |||||||||||
| Rated insulation voltage Ui (V) | 690 | |||||||||||
| AC-3 | Electrical life (times) | 60×104 | 50×104 | 30×104 | 20×104 | 15×104 | ||||||
| Frequent operation (h) | 600 | 300 | 150 | |||||||||
| AC-4 | Electrical life (times) | 15×104 | 8×104 | 5×104 | 3×104 | |||||||
| Frequent operation (h) | 150 | |||||||||||
| Mechanical life (times) | 300×104 | 100×104 | 60×104 | |||||||||
| Auxiliary contact | Agreed free air heating current lth (A) | 10 | ||||||||||
| Electrical life (times) | AC-15(360VA) | 60×104 | 50×104 | 30×104 | 15×104 | |||||||
| DC-13(33W) | ||||||||||||
| Coil parameters | Rated control supply voltage Us (V) | AC50HZ:24、48 110 230(220)240 (double coil energy-saving type(380) | AC50HZ:48、110 230(220)240 (double coil energy-saving type(380) | |||||||||
| pull-in voltage | 85%~110%Us | |||||||||||
| Release voltage | 20%~75%Us | |||||||||||
| coil power (VA) | start | 560 | 800 | 750 | 1000 | 1100 | 1600 | |||||
| Sorption | 45 | 55 | 8 | 12 | 16 | 20 | ||||||
| Pickup time (ms) | 23~35 | 20~35 | 30~65 | 40~75 | 40~80 | 50~100 | ||||||
| Release time (ms) | 5~15 | 7~15 | 100~170 | 100~170 | 100~200 | 130~230 | ||||||
| Main circuit connection capacity | Copper conductor | Number of roots | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | – | |
| Conductor section mm | 120 | 150 | 185 | 240 | 240 | 150 | 240 | – | ||||
| Copper bar | Number of roots | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Dimension mm | 20×3 | 25×3 | 25×3 | 32×4 | 32×4 | 30×5 | 30×5 | 50×5 | 60×5 | 60×5 | ||
| Auxiliary circuit contrd circuit | Flexible cord mm² |
1 | 2.5 | |||||||||
| 2 | ||||||||||||
| Hard wire mm² | 1 | 4 | ||||||||||
| 2 | ||||||||||||
Mengapa Memilih CHAC
Dengan pengalaman manufaktur lebih dari 30 tahun, 1100+ karyawan, dan 100M+ tiang
kapasitas tahunan dan produksi otomatis 90% unit, CHAC memberikan kapasitas produksi yang stabil dan ketat
Pengendalian kualitas untuk pelanggan OEM/ODM global. Sistem manufaktur internal kami mendukung jangka panjang
Kerjasama untuk merek-merek listrik, importir dan distributor.
30+
BERKALI-KALI BERKEMBANG
Mengkhususkan diri dalam manufaktur listrik tegangan rendah
1100+
KARYAWAN
Tim profesional memastikan kualitas dan pengiriman yang stabil
100 juta+
Kapasitas Bulanan POKER
Kapasitas produksi berskala besar untuk memenuhi permintaan global
90%
PENGELOLAAN PRODUKSI AUTOMATIS
Otomasi canggih untuk efisiensi dan konsistensi yang tinggi

Barisan Perakitan Otomatis

Laboratorium Pengujian

Injeksi & Stamping

Pemeriksaan Kualitas





Sistem kontrol kualitas yang ketat memastikan setiap produk memenuhi standar global.
Apa yang Dapat Kami Sesuaikan?
CHAC supports customization of coil voltage, auxiliary contact configuration,
electrical parameters, product branding,packaging design and engineering development according to customers’ equipment and market requirements.
Voltan Coil
Pilihan tegangan kumparan AC dan DC yang disesuaikan dengan kebutuhan aplikasi.

Kontak Tambahan
Kombinasi kontak bantu yang fleksibel untuk berbagai fungsi kontrol.

Parameter Listrik
Rating saat ini, rentang perlindungan, dan parameter fungsional dapat disesuaikan.

Branding Produk
Dukungan untuk logo label pribadi, papan nama, dan identifikasi produk.

Desain Kemasan
Peralatan karton, label, manual, dan solusi kemasan khusus.

Pembangunan Teknik
Bantuan mulai dari optimasi desain hingga pengembangan produk dan pencocokan aplikasi.

CQC1 Product FAQ
What loads can the CQC1 contactor switch?
Use the published utilization category, operational current and voltage for the selected variant. Resistive, motor and capacitive loads require different checks.
How do I select an AC contactor size?
Start with load current, utilization category, starts per hour, coil voltage, poles and short-circuit coordination. Current alone is not enough.
Can a thermal relay be paired with it?
Where the product record supports the combination, a thermal relay can form a motor starter. Confirm mechanical fit, current range and control wiring.
Which coil voltage should I specify?
Match the control supply shown on the project drawing with the coil option for the exact model. Never assume the coil voltage from the main circuit.
What accessories are available?
Auxiliary contacts, timers, interlocks or other accessories depend on the series and variant. Confirm the compatible accessory list before ordering.
How should a contactor be commissioned?
Verify terminal torque, coil voltage, contact sequence, insulation and operating current, then record the test results.
Confirm the Right CQC1 Configuration
Send the exact model, operating conditions, quantity, destination market and required documents. CHAC will review the request against the published product data.