PXB6DC-125M Saklar Sirkuit Miniatur DC
Itu PXB6DC-125M Direkomendasikan untuk perlindungan overload DC dan arus pendek. Pilihannya berdasarkan tegangan, arus, kutub, dan data perlindungan yang tercantum, kemudian konfirmasi koordinasi kabel, kondisi kerusakan, persyaratan penutup, dan aturan pemasangan lokal.
Gambaran Produk
PXB6DC-125M is a DC circuit breaker 125A for 1P DC 24–125V; 2P DC 24–250V applications. It is intended for PV, telecom, energy-storage or control circuits when the DC fault study supports the rating; this describes an evaluation context, not a universal approval. Confirm the complete circuit design before specifying the product.
DC overload and short-circuit protection is distinct from adjacent protection functions. Do not infer AC/DC suitability, residual-current protection, automatic control or isolation performance from the product family name alone.
Fitur Utama
Aplikasi Biasa
PV, telecom, energy-storage or control circuits when the DC fault study supports the rating. Verify system voltage, expected fault current or leakage, wiring arrangement, environment, coordination and applicable rules for the ordered configuration.
Permohonan dan Panduan Pemilihan
Use the verified PXB6DC-125M records below to create a shortlist. Product labels do not replace the project calculation, coordination review or exact installation instructions.
| Titik pemilihan | PXB6DC-125M reference | Hal yang harus dipastikan oleh proyek tersebut |
|---|---|---|
| Rated current | 63–125A | Design current, conductor capacity, ambient and grouping |
| Voltage and frequency | 1P DC 24–125V; 2P DC 24–250V | Supply system and equipment rating |
| Tiang | 1P / 2P | Conductors to be switched, protected or isolated |
| Protection / control | Proteksi overload dan arus pendek DC | Required function and adjacent-device coordination |
| Fault / residual data | 10kA Icu; 7.5kA Ics | Prospective short-circuit or leakage conditions |
AC vs DC Interruption
DC interruption duty is not interchangeable with AC. Confirm the model’s DC voltage, pole arrangement, Icu/Ics and wiring instructions.
DC Fault Duty
Review Circuit Protection →
Model-Specific Ratings
Use the exact technical table for rated voltage, current, poles, terminals, life and environmental limits.
Verified Data
View Technical Support →
Installation and Coordination
Check the complete circuit, conductor sizing, fault or leakage conditions, enclosure and local rules before energising.
Engineering Check
Discuss a Configuration →
Ordering Information
State model, rating, poles, system, quantity, destination market and document requirements so the configuration can be reviewed.
Project Inputs
Send Project Details →
Panduan Pemesanan
- State the exact model: PXB6DC-125M.
- Provide rated current and voltage from the published technical table.
- Confirm poles and the required protection, isolation or control function.
- Provide application, expected fault/leakage conditions, destination market and quantity.
- List accessory, terminal, documentation and approved marking or packaging requirements.
Ordering Specification
Please specify the following when ordering:
- Product Model: PXB6DC-125M
- Number of Poles: 1P, 2P
- Rated Current & Tripping Curve: e.g., 125A
- Rated Current (In): 63, 80, 100, 125A
- Quantity: e.g., 100 pcs
- PXB6DC-125M 2P 125A 100 pcs
The quantity shown is an ordering example, not a minimum order quantity.
Pengujian Instalasi dan Koordinasi
- Use the exact model drawing and instructions; do not infer wiring or accessory compatibility from another product.
- Verify conductor size, terminal torque, enclosure conditions, temperature, grouping and clearances.
- Coordinate upstream and downstream devices and confirm the required fault, leakage or voltage response.
- Installation, testing and maintenance must be completed by qualified personnel under applicable rules.
Penamaan tipe

Tripping curves

Dimensi (mm)

Spesifikasi Teknis
| Parameter | Spesifikasi |
|---|---|
| Rated Voltage (V) | 1P DC24V/48V/80V/110V/125V |
| 2P DC24V/48V/80V/110V/125V/160V/220V/250V | |
| Rated Current (A) | 63, 80, 100, 125 |
| Rated Insulation Voltage (Ui) | 500V |
| Number of Poles | 1P, 2P |
| Rated impulse withstand voltage Uimp(kV) | 4 |
| Ultimate Breaking Capacity (Icu)(kA) | 10 |
| Service Breaking Capacity (Ics)(kA) | 7.5 |
| Mechanical Endurance | ≥10000 |
| Electrical Endurance | ≥1500 |
| Pollution Degree | 3 |
| Standard | GB/T14048.2、IEC60947-2 |
| Sertifikasi | CE·CB·CCC|TÜV Rheinland |
Tripping Characteristics (Reference Temperature: 30℃)
| Item | Test Current (A) | Initial Status | Time limit for tripping or non-tripping | Expected result | Remarks |
|---|---|---|---|---|---|
| a | 1.05In | Cold | t≤2h(In>63A) | Non-tripping | Current smoothly rises to specified value within 5s |
| t≤1h(In≤63A) | |||||
| b | 1.3In | Following item a test | t<2h(In>63A) | Tripping | |
| t<1h(In≤63A) | |||||
| c | 2In | Cold | 1s<t<600s | Tripping | |
| d | 4In、8In、12In (±20%) |
Cold | t≤0.2s | Tripping | Circuit switched on by closing an auxiliary switch. Verifies rapid breaking capability. |
Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test
Mengapa Memilih CHAC
Dengan pengalaman manufaktur lebih dari 30 tahun, 1100+ karyawan, dan 100M+ tiang
kapasitas tahunan dan produksi otomatis 90% unit, CHAC memberikan kapasitas produksi yang stabil dan ketat
Pengendalian kualitas untuk pelanggan OEM/ODM global. Sistem manufaktur internal kami mendukung jangka panjang
Kerjasama untuk merek-merek listrik, importir dan distributor.
30+
BERKALI-KALI BERKEMBANG
Mengkhususkan diri dalam manufaktur listrik tegangan rendah
1100+
KARYAWAN
Tim profesional memastikan kualitas dan pengiriman yang stabil
100 juta+
Kapasitas Bulanan POKER
Kapasitas produksi berskala besar untuk memenuhi permintaan global
90%
PENGELOLAAN PRODUKSI AUTOMATIS
Otomasi canggih untuk efisiensi dan konsistensi yang tinggi

Barisan Perakitan Otomatis

Laboratorium Pengujian

Injeksi & Stamping

Pemeriksaan Kualitas





Sistem kontrol kualitas yang ketat memastikan setiap produk memenuhi standar global.
Apa yang Dapat Kami Sesuaikan?
For PXB6DC-125M projects, CHAC can review private-label marking, packaging, approved appearance options and the published electrical configurations. Requests outside the published range require engineering evaluation, testing and feasibility review.
Logo & Branding
Penerbitan logo khusus, pencetakan laser dan solusi stiker nama.

Kemasan
Kustomisasi
Kotak warna, karton, label, dan manual yang disesuaikan.

Elektrik
Kustomisasi
Current, voltage, breaking capacity, trip curve and other
special functions.

Produk
Penampilan
Kustomisasi warna perumahan, warna pegangan, dan tampilan.

Sertifikasi
Dukungan
Products comply with international standards and market
requirements.

Teknologi
Pembangunan
Pengerjaan evaluasi, pengujian prototipe, dan produksi massal.

Unduh
PXB6 Series Miniature Circuit Breaker
Complete product overview for low-voltage electrical components and product selection reference.
Butuh Dokumen Teknis?
Hubungi kami untuk mendapatkan data spesifikasi, sertifikat, gambar, panduan pemilihan, atau dukungan proyek OEM/ODM.
PXB6DC-125M Product FAQ
What is the PXB6DC-125M used for?
The PXB6DC-125M is specified for DC overload and short-circuit protection in 1P DC 24–125V; 2P DC 24–250V applications, within the ratings and configurations listed in its technical table. Final suitability depends on the complete circuit design.
How does the PXB6DC-125M work?
Its operating principle follows the documented function: DC overload and short-circuit protection. Use the exact model documentation for thresholds, timing, trip behaviour, terminals and test procedures.
How do I choose the PXB6DC-125M rating and poles?
Start with the design current and system arrangement, then choose only a published option. The page lists pole options as 1P / 2P; confirm neutral, polarity, conductors and isolation requirements.
What safety limitation applies to the PXB6DC-125M?
Do not treat the PXB6DC-125M as a universal substitute for another device. Confirm 10kA Icu; 7.5kA Ics, the system voltage, fault or leakage conditions and any separate upstream protection before selection.
Can the PXB6DC-125M be used in another circuit type?
Only when the exact ordered configuration is rated for that circuit. AC and DC duties, residual-current devices, isolators, smart controls and voltage protectors are not interchangeable by appearance or current rating.
How should the PXB6DC-125M be installed and tested?
Use the exact product drawing, terminal identification and instructions. A qualified person should verify isolation, conductors, torque, settings, coordination and functional tests before energising the circuit.
Confirm the Right PXB6DC-125M Configuration
Send the model, rating, poles, system voltage, application, quantity and document requirements. CHAC will review the request against the published data.








