Steker DC Tegangan Tinggi Seri STE1 (Segel Keramik Persegi)Steker DC Tegangan Tinggi Seri STE1 (Segel Keramik Persegi)
Itu Steker DC Tegangan Tinggi Seri STE1 (Segel Keramik Persegi)Steker DC Tegangan Tinggi Seri STE1 (Segel Keramik Persegi) CHAC CHAC High-Voltage DC Contactor untuk switching dan isolasi DC yang terkontrol. Halaman ini menyertakan tabel teknis spesifik model serta gambar produk asli agar pembeli dapat memverifikasi tegangan, arus, konfigurasi, pemasangan, dan standar yang berlaku sebelum melakukan pemesanan. Kesesuaian akhir tergantung pada rangkaian lengkap, metode pemasangan, dan aturan pasar tujuan.
Gambaran Produk
STE1 Series High-voltage DC contactor (Square Ceramic Sealing)STE1 Series High-voltage DC contactor (Square Ceramic Sealing) is a high-voltage DC contactor intended for controlled DC switching and isolation. The current product record identifies it for battery, charging and high-voltage DC systems. Use the exact model variant and preserved technical source as the basis for procurement rather than assuming that every family member has the same rating.
Verified source summary: Type designation Product model Working voltage Working current Load polarity Coil polarity Auxiliary contact STE1-40 1500 40 Non-polarity Non-polarity / STE1-60 1000 60 Non-polarity Non-polarity / STE1-100 1000 100 Having polarity Non-polarity / STE1-150 750 150 Non-polarity Non-polarity / STE1-200 750 200 Having polarity Non-polarity / STE1-L200 1000 200 Non-polarity Non-polarity 1NO STE1-L300 1000 300 Non-polarity
Fitur Utama
Aplikasi Biasa
Typical use can include battery, charging and high-voltage DC systems when the project confirms system voltage, current, fault or surge exposure, conductor and enclosure requirements, and the selected variant’s installation instructions. This page does not replace the project design or the authority having jurisdiction.
Permohonan dan Panduan Pemilihan
Use the following decision points with the preserved model data. Product-family descriptions explain intent, but the exact technical table controls the ordered variant.
| Titik pemilihan | Steker DC Tegangan Tinggi Seri STE1 (Segel Keramik Persegi)Steker DC Tegangan Tinggi Seri STE1 (Segel Keramik Persegi) | Hal yang harus dipastikan oleh proyek tersebut |
|---|---|---|
| Aplikasi | High-Voltage DC Contactor projects | Confirm the actual system and environment |
| Selection basis | pemilihan switching DC dan isolasi yang terkontrol | Use the exact model and technical table |
| Pemasangan | Follow the model instructions | Check mounting, clearances and termination |
| Kepatuhan | Use the listed standard where applicable | Verify edition, scope and destination rules |
| Adjacent product | Evaluate the related CHAC family where function differs | Do not substitute without engineering review |
Function
pemilihan switching DC dan isolasi yang terkontrol
Match the protection or switching function to the system.
Konfigurasi
Model-specific options
Confirm current, voltage, poles, terminals or accessories from the table.
Pemasangan
Mechanical and electrical fit
Check enclosure, mounting, wiring space and maintenance access.
Project evidence
Documents and test records
Retain the approved drawing, technical sheet and commissioning record.
Panduan Pemesanan
- State the exact model and variant.
- Provide the system voltage, current, frequency and load or protection function.
- Confirm mounting, terminals, accessories, enclosure and environmental conditions.
- Share quantity, destination market and required technical documents.
Pengujian Instalasi dan Koordinasi
- Verify the model’s ratings and connection arrangement against the project drawings.
- Check conductor, busbar, enclosure, clearances and tightening requirements using the product documentation.
- Coordinate upstream and downstream protection or control devices where applicable.
- Use qualified personnel for installation, testing, isolation and maintenance.
Penamaan tipe

| Product model | Working voltage | Working current | Load polarity | Coil polarity | Auxiliary contact |
| STE1-40 | 1500 | 40 | Non-polarity | Non-polarity | / |
| STE1-60 | 1000 | 60 | Non-polarity | Non-polarity | / |
| STE1-100 | 1000 | 100 | Having polarity | Non-polarity | / |
| STE1-150 | 750 | 150 | Non-polarity | Non-polarity | / |
| STE1-200 | 750 | 200 | Having polarity | Non-polarity | / |
| STE1-L200 | 1000 | 200 | Non-polarity | Non-polarity | 1NO |
| STE1-L300 | 1000 | 300 | Non-polarity | Non-polarity | 1NO |
| STE1-X300 | 1000 | 300 | Non-polarity | Non-polarity | / |
| STE1-300 | 1000 | 300 | Having polarity | Having polarity | / |
| STE1-300D | 1500 | 300 | Non-polarity | Non-polarity | 1NO |
| STE1-350 | 1500 | 350 | Non-polarity | Having polarity | 1NO |
| STE1-400 | 1500 | 400 | Non-polarity | Non-polarity | 1NO |
| STE1-600 | 1000 | 600 | Having polarity | Having polarity | / |
Spesifikasi Teknis
| Product model | STE140 | STE160 | |
| Contact form | 1H | 1H | |
| Auxiliary contact | / | / | |
| Contact polarity | Non-polanity | Non-polanity | |
| Contact resistance | ≤5mΩ(at 40A) | ≤5mΩ(at 60A) | |
| Operating voltage | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 40A | 60A | |
| Electrical endurance | 10~1500V | 10~1000V | |
| Maximum breaking current | 400A(300VDC) | 600A(300VDC) | |
| Electrical endurance | ≥300 times(40AV1500VDC) | ≥1×10⁴times(60A/750VDC) ≥5×10³times(60A/1000VDC)“ |
|
| Current carrying | 40A:Continuous for 60A:60min 160A:10s | 60A:Continuous for 80A:20min 160A:40s | |
| Dielectric withstand voltage | Between open contacts | 3000VAC | 3000VAC |
| Between contact coils | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×105times | 2×105times | |
| Voltan Coil | 12V,24V | 12V,24V | |
| Coil power consumption | 3W | 3W | |
| Load extraction method | Internal thread | Internal thread | |
| Coil lead out method | Connector | Connector | |
| Weight | About 180g | About 180g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions/mm | 79.2×36.7×48 | 79.2×36.7×48 | |
Note:
1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:54s.
| Product model | STE1-100 | STE1-150 | STE1-200 | |
| Contact form | 1H | 1H | 1H | |
| Auxiliary contact | / | / | / | |
| Contact polarity | Having polarity | Non-polarity | Having polarity | |
| Contact resistance | ≤1mΩ(at 100A) | ≤5mΩ(at 150A) | ≤0.5mΩ(at 200A) | |
| Operating voltage | ≤75%Un | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 100A | 150A | 200A | |
| Electrical endurance | 10~1000V | 10~750V | 10~750V | |
| Maximum breaking current | 1000A(300VDC) | 1500A(300VDC) | 2000A(300VDC) | |
| Electrical endurance | ≥6×10³ times(100A/750VDC) ≥5×10³ times(100A/1000VDC) |
≥1.5×10³ times(150A/450VDC) ≥500 times(150A/750VDC) |
≥1×10³ times(200A/450VDC) ≥500 times(200A/750VDC) |
|
| Current carrying | 100A:Continuous for 120A:2h 200A:10min |
150A:Continuous for 180A:2h 225A:15min |
200A:Continuous for 250A:15min 320A:5min |
|
| Dielectric withstand voltage | Between open contacts | 3000VAC | 3000VAC | 3000VAC |
| Between contact coils | 4000VAC | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | 2×10⁵ times | |
| Voltan Coil | 12V,24V | 12V,24V | 12V,24V | |
| Coil power consumption | 4.5W | 4.5W | 6W | |
| Load extraction method | Copper bar connection | Copper bar connection | Internal thread | |
| Coil lead out method | Connector | Connector | Connector | |
| Weight | About 400g | About 400g | About 350g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 81.5×40×78.3 | 81.5×40×78.3 | 81×39×70 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Product model | STE1-L200 | STE1-L300 | |
| Contact form | 1H | 1H | |
| Auxiliary contact | 1NO | 1NO | |
| Contact polarity | Non-polarity | Non-polarity | |
| Contact resistance | ≤0.5mΩ(at 200A) | ≤0.3mΩ(at 300A) | |
| Operating voltage | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 200A | 300A | |
| Electrical endurance | 10~1000V | 10~1000V | |
| Maximum breaking current | 1000A(300VDC) | 2000A(300VDC) | |
| Electrical endurance | ≥5×10³ times(200A/450VDC) ≥1×10³ times(200A/750VDC) ≥300 times(200A/1000VDC) |
≥2×10³ times(300A/450VDC) ≥700 times(300A/750VDC) ≥300 times(300A/1000VDC) |
|
| Current carrying | 200A:Continuous for 300A:30min 400A:5min |
300A:Continuous for 450A:5min 600A:1min |
|
| Dielectric withstand voltage | Between open contacts | 4000VAC | 4000VAC |
| Between contact coils | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | |
| Voltan Coil | 12V,24V | 12V,24V | |
| Coil power consumption | 3W | 4.5W | |
| Load extraction method | Internal thread | Internal thread | |
| Coil lead out method | lead wire | lead wire | |
| Weight | About 185g | About 320g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 71.8×36×51 | 83.4×48×63.5 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Product model | STE1-X300 | STE1-300 | STE1-300D | |
| Contact form | 1H | 1H | 1H | |
| Auxiliary contact | / | / | 1NO | |
| Contact polarity | Non-polarity | Having polarity | Non-polarity | |
| Contact resistance | ≤0.5mΩ(at 300A) | ≤0.2mΩ(at 300A) | ≤0.3mΩ(at 300A) | |
| Operating voltage | ≤75%Un | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 300A | 300A | 300A | |
| Electrical endurance | 10~1000V | 10~1000V | 10~1500V | |
| Maximum breaking current | 2000A(300VDC) | 2500A(300VDC) | 2000A(300VDC) | |
| Electrical endurance | ≥1×10³ times(300A/450VDC) ≥500 times(300A/750VDC) ≥100 times(300A/1000VDC) |
≥6×10³ times(300A/750VDC) ≥3×10³ times(300A/1000VDC) |
≥1.4×10³ times(250A/800VDC) ≥1×10³ times(400A/1000VDC) ≥500 times(400A/1500VDC) |
|
| Current carrying | 300A:Continuous for 450A:5min 600A:2min |
300A:Continuous for 600A:1min 900A:10s |
400A:Continuous for 600A:1h 800A:10min |
|
| Dielectric withstand voltage | Between open contacts | 3000VAC | 3000VAC | 4000VAC |
| Between contact coils | 3000VAC | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | 2×10⁵ times | |
| Voltan Coil | 12V,24V | 12V,24V | 12V,24V | |
| Coil power consumption | 6W | Connect 46W and maintain 4.5W | 10W | |
| Load extraction method | Internal thread | Copper bar connection | Internal thread | |
| Coil lead out method | Connector | Connector | Connector | |
| Weight | About 370g | About 850g | About 700g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 88.3×42.5×74.5 | 112.6×64.7×83.9 | 98.4×45×91.5 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Product model | STE1-350 | STE1-400 | STE1-600 | |
| Contact form | 1H | 1H | 1H | |
| Auxiliary contact | 1NO | 1NO | / | |
| Contact polarity | The coil has polarity while the contacts have no polarity |
Non-polarity | Having polarity | |
| Contact resistance | ≤0.3mΩ(at 350A) | ≤0.2mΩ(at 400A) | ≤0.2mΩ(at 600A) | |
| Operating voltage | ≤75%Un | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 400A | 400A | 600A | |
| Electrical endurance | 10~1500V | 10~1800V | 10~1500V | |
| Maximum breaking current | 2000A(300VDC) | 2500A(300VDC) | 2500A(300VDC) | |
| Electrical endurance | ≥100 times(150A/1800VDC) ≥1×10³ times(400A/1000VDC) ≥500 times(400A/1500VDC) |
≥100 times(150A/1800VDC) ≥1×10³ times(400A/1000VDC) ≥500 times(400A/1500VDC) |
≥1×10³ times(600A/750VDC) ≥500 times(600A/1000VDC) ≥100 times(600A/1500VDC) |
|
| Current carrying | 400A:Continuous for 450A:60min 600A:2min |
400A:Continuous for 450A:10min 600A:90s |
600A:Continuous for 800A:20min 1000A:5min |
|
| Dielectric withstand voltage | Between open contacts | 4000VAC | 4000VAC | 3000VAC |
| Between contact coils | 4000VAC | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | 2×10⁵ times | |
| Voltan Coil | 12V,24V | 12V,24V | 12V,24V | |
| Coil power consumption | Connect 46W and maintain 4.5W | 10W | Connect 50W and maintain 10W | |
| Load extraction method | Internal thread | Internal thread | Internal thread | |
| Coil lead out method | Connector | Connector | lead wire | |
| Weight | About 730g | About 850g | About 1020g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 104×65×97.4 | 108×67×101.6 | 194.4×66.8×121.5 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
Mengapa Memilih CHAC
Dengan pengalaman manufaktur lebih dari 30 tahun, 1100+ karyawan, dan 100M+ tiang
kapasitas tahunan dan produksi otomatis 90% unit, CHAC memberikan kapasitas produksi yang stabil dan ketat
Pengendalian kualitas untuk pelanggan OEM/ODM global. Sistem manufaktur internal kami mendukung jangka panjang
Kerjasama untuk merek-merek listrik, importir dan distributor.
30+
BERKALI-KALI BERKEMBANG
Mengkhususkan diri dalam manufaktur listrik tegangan rendah
1100+
KARYAWAN
Tim profesional memastikan kualitas dan pengiriman yang stabil
100 juta+
Kapasitas Bulanan POKER
Kapasitas produksi berskala besar untuk memenuhi permintaan global
90%
PENGELOLAAN PRODUKSI AUTOMATIS
Otomasi canggih untuk efisiensi dan konsistensi yang tinggi

Barisan Perakitan Otomatis

Laboratorium Pengujian

Injeksi & Stamping

Pemeriksaan Kualitas





Sistem kontrol kualitas yang ketat memastikan setiap produk memenuhi standar global.
Apa yang Dapat Kami Sesuaikan?
CHAC supports customization of coil voltage, auxiliary contact configuration,
electrical parameters, product branding,packaging design and engineering development according to customers’ equipment and market requirements.
Voltan Coil
Pilihan tegangan kumparan AC dan DC yang disesuaikan dengan kebutuhan aplikasi.

Kontak Tambahan
Kombinasi kontak bantu yang fleksibel untuk berbagai fungsi kontrol.

Parameter Listrik
Rating saat ini, rentang perlindungan, dan parameter fungsional dapat disesuaikan.

Branding Produk
Dukungan untuk logo label pribadi, papan nama, dan identifikasi produk.

Desain Kemasan
Peralatan karton, label, manual, dan solusi kemasan khusus.

Pembangunan Teknik
Bantuan mulai dari optimasi desain hingga pengembangan produk dan pencocokan aplikasi.

Unduh
Kontaktor DC Tegangan Tinggi Seri STE
Complete product overview for low-voltage electrical components and product selection reference.
Butuh Dokumen Teknis?
Hubungi kami untuk mendapatkan data spesifikasi, sertifikat, gambar, panduan pemilihan, atau dukungan proyek OEM/ODM.
STE1 Product FAQ
What is the STE1 used for?
It is a high-voltage DC switching device for the system and variant shown in the technical table. Confirm the working voltage, current, polarity and load category.
Why does DC contactor polarity matter?
Some variants specify load or coil polarity because DC arc management and magnetic blowout depend on the internal design. Follow the marked polarity.
How do I select the voltage and current?
Use the actual steady, inrush and breaking current, system voltage, duty cycle and fault-clearing strategy. The family range is not a blanket rating for every variant.
What does ceramic or epoxy sealing change?
The sealing construction is part of the product design and environmental suitability. Compare the exact datasheet for temperature, insulation and endurance.
Can it switch a battery or charger circuit?
It may be suitable when the variant's DC voltage, current, breaking duty and insulation data match the application. Confirm the complete design.
What should be tested before energizing?
Check coil operation, contact resistance, insulation, polarity, pre-charge or discharge sequence and the emergency isolation procedure.
Confirm the Right STE1 Configuration