CQM5HU Series Molded Case Circuit Breaker

Product Features

■ Up to AC1140V Suitable for high-voltage AC distribution applications up to AC1140V.

■ Wide Current Range Rated current range from 63A to 630A with 320A and 630A frame sizes.

■Overload & Short-Circuit Protection Provides reliable protection against overload and short-circuit faults.

Isolation Function Designed with an isolation function for circuit safety and maintenance.

■Flexible Operation Supports direct handle operation and optional manual operating mechanism.

Type designation

No. Code Description
① CQ Company Code
② M Molded Case Circuit Breaker
③ 5 Design Code
④ HU Derivative Code
⑤ 320 / 630 Frame Size
⑥ M / — Breaking Capacity Code: M = Standard Type; “—” for 630
⑦ 3 Number of Poles: 3P
⑧ 2/3 Release Code: 2 = Magnetic Only; 3 = Thermal-Magnetic
⑨ □ Internal Accessory Code: See Accessory Code Reference
⑩ □ Operating Mode: Direct Handle / CS1-A Manual Operating Mechanism / CD2 Motor Operating Mechanism
⑪ □ Rated Current
⑫ □ Rated Voltage: AC800V / AC1140V
⑬ □ Accessory Voltage / Specification

Operating Conditions

Item Specificazione
Operating Altitude ≤ 2500 m
Ambient Temperature −35℃ to +70℃
Derating Required above +40℃
Storage Temperature −40℃ to +75℃
Relative Humidity ≤ 50% at +40℃; up to 90% at +20℃
Pollution Degree 3
Protection Degree IP20
Installation Vertical or horizontal
Vertical Installation Inclination ≤ 5°

Technical Specifications

Parameter CQM5HU-320 CQM5HU-630
Frame Size (A) 320 630
Rated Current In (A) 63, 80, 100, 125, 140, 160, 180, 200, 225, 250, 280, 315, 320 250, 315, 350, 400, 500, 630
Number of Poles 3P 3P
Rated Operational Voltage Ue (V) AC800 / AC1140 AC800 / AC1140
Rated Insulation Voltage Ui (V) 1250 1250
Rated Impulse Withstand Voltage Uimp (kV) 12 12
Breaking Capacity Class M —
Ics = 100% Icu @ AC800V (kA) 50 65
Ics = 100% Icu @ AC1140V (kA) 15 20
Electrical Operations @ AC800V 1500 1000
Electrical Operations @ AC1140V 1000 800
Mechanical Operations 15000 15000
Ambient Temperature -35℃ to +70℃* -3℃ to +70℃*
Normal Operating Altitude ≤ 2500 m ≤ 2500 m
Relative Humidity ≤50% at +40℃; up to 90% at +20℃ ≤50% at +40℃; up to 90% at +20℃
Pollution Degree 3 3
Installation Category III (Main Circuit) / II (Other) III
Degree of Protection IP20 IP20
Terminal Screw M8 M10
Terminal Tightening Torque 12 N·m 35 N·m
Mounting Screw M4 M4 / M3
Mounting Tightening Torque 1.5 N·m 1.5 / 0.8 N·m
Dimensions (L × W × H) mm 264 × 120 × 103 275 × 110 × 170
Standards IEC 60947-2, GB/T 14048.2 IEC 60947-2, GB/T 14048.2
Certificazione CCC、CE、TÜV、CB CCC

Recommended Conductor Cross-Section

Rated Current In (A) 63 80 100 125 140/160 180/200/225 250 315 320/350 400 500 630
Conductor Cross-Section (mm²) 16 25 35 50 70 95 120 185 185 240 2×240 2×240

Accessory List

Time-current characteristic curve

Overall and mounting dimensions

CQM5HU-320

CQM5HU-630