CQM5HU Series Molded Case Circuit Breaker

The CHAC CQM5HU molded case circuit breaker offers magnetic-only and thermal-magnetic configurations for 800V and 1140V AC distribution circuits. Select a thermal-magnetic version when both overload and short-circuit protection are required. Its 320A and 630A frames offer different current ranges and breaking capacities, so selection should match the system voltage, frame and trip unit.

Models:
CQM5HU-320 / CQM5HU-630
Poles:
3P
Rated Current:
63–320A (320 frame); 250–630A (630 frame)
Rated Voltage:
800V / 1140V AC
Breaking Capacity:
Icu = Ics: 50/65kA at 800V AC; 15/20kA at 1140V AC (320/630 frames)
Trip Unit:
Magnetic-only or thermal-magnetic, according to release code
Standard:
IEC 60947-2 / GB/T 14048.2
Customization:
One-Stop OEM/ODM Service

Product Overview

The CHAC CQM5HU molded case circuit breaker is designed for 800V and 1140V AC circuits. Its 320A and 630A frames have different current ranges and breaking capacities. Select the operating voltage and trip-unit function before choosing the frame.

For importers, distributors and equipment manufacturers, CHAC can review the requested configuration against the circuit requirements and destination-market documents. Agree the exact model, drawings and marking requirements before sample approval or a repeat order.

Key Selection Points

  • Frame and current: 320 frame: 63–320A; 630 frame: 250–630A in listed steps. Check the actual available current and mechanism combination.
  • Capacity at 800V AC: 320 frame: 50kA; 630 frame: 65kA; Ics = Icu. Use the capacity for the operating voltage.
  • Capacity at 1140V AC: 320 frame: 15kA; 630 frame: 20kA; Ics = Icu. Do not carry the higher 800V values into an 1140V design.
  • Release options: Magnetic only or thermal-magnetic. Choose thermal-magnetic when integral overload and short-circuit protection are both needed.

Typical Applications

Evaluate CQM5HU for AC distribution equipment within its documented voltage, fault-current and installation limits. A magnetic-only version needs a separately coordinated overload solution where overload protection is required.

Applications and Selection Guide

Selection item CQM5HU configuration What to verify
Frame and current 320 frame: 63–320A; 630 frame: 250–630A in listed steps Check the actual available current and mechanism combination.
Capacity at 800V AC 320 frame: 50kA; 630 frame: 65kA; Ics = Icu Use the capacity for the operating voltage.
Capacity at 1140V AC 320 frame: 15kA; 630 frame: 20kA; Ics = Icu Do not carry the higher 800V values into an 1140V design.
Release options Magnetic only or thermal-magnetic Choose thermal-magnetic when integral overload and short-circuit protection are both needed.

Use these checks to compare the protection function, configuration and related CHAC products before specifying CQM5HU. Related products are selection alternatives or system components, not automatic replacements.

Compare CQM5NEZ for the required function

The CHAC CQM5NEZ DC molded case circuit breaker is available with magnetic-only or thermal-magnetic trip units for 1500V DC circuits. Select a thermal-magnetic version when both overload and short-circuit protection are required. The 350A and 630A frames cover rated currents from 63A to 630A, with breaking capacity determined by frame and M/H version.

Related ProductSystem DesignVerify Compatibility

Compare PXD6-125 for the required function

The CHAC PXD6-125 isolator provides electrical isolation and ON/OFF indication for terminal distribution assemblies. Choose the pole arrangement and rated current for the supply system, with AC-22A utilization and ratings up to 125A.

Related ProductSystem DesignVerify Compatibility

Need Help Specifying CQM5HU?

Send the circuit requirements, selected configuration, destination market and quantity for a model-specific review.

Request a Quote

Select breaking capacity at the actual AC voltage

CQM5HU has different short-circuit ratings at 800V and 1140V. State the network voltage and calculated fault current together in the inquiry. Frame size alone cannot determine whether the breaker meets the installation fault level.

Confirm temperature conditions and the trip function

The operating data calls for derating above 40°C. Provide the actual enclosure temperature and installation conditions for review, and identify whether a magnetic-only or thermal-magnetic release is required. Neither a larger frame nor a larger trip setting substitutes for a coordination study.

How to Specify a CQM5HU Order

Use the configuration details below in the purchase specification. Keep the approved drawing revision and product identification with the order so repeat deliveries can be checked consistently.

Order detail Information to include
Frame and current 320 frame: 63–320A; 630 frame: 250–630A in listed steps — Check the actual available current and mechanism combination.
Capacity at 800V AC 320 frame: 50kA; 630 frame: 65kA; Ics = Icu — Use the capacity for the operating voltage.
Capacity at 1140V AC 320 frame: 15kA; 630 frame: 20kA; Ics = Icu — Do not carry the higher 800V values into an 1140V design.
Release options Magnetic only or thermal-magnetic — Choose thermal-magnetic when integral overload and short-circuit protection are both needed.
Project and documents Supply the application, installation conditions and destination-market document requirements.
Quantity and identification State the quantity, sample requirement, packaging language and any proposed branding; confirm feasibility before approval.

Check Installation Fit Before Approval

  • Use the CQM5HU dimension drawing to verify mounting, terminal access, operating clearance and conductor bending space.
  • Confirm conductor preparation, terminal compatibility and tightening instructions for the exact configuration. A conductor reference table does not replace project cable sizing.
  • Review temperature, enclosure conditions and the protective arrangement with the equipment designer. Do not infer compatibility from a similar model name.
  • Have qualified personnel install and verify the equipment using the model instructions and applicable isolation and testing procedures.

Type designation

No. Code Description
① CQ Company Code
② M Molded Case Circuit Breaker
③ 5 Design Code
④ HU Derivative Code
⑤ 320 / 630 Frame Size
⑥ M / — Breaking Capacity Code: M = Standard Type; “—” for 630
⑦ 3 Number of Poles: 3P
⑧ 2/3 Release Code: 2 = Magnetic Only; 3 = Thermal-Magnetic
⑨ □ Internal Accessory Code: See Accessory Code Reference
⑩ □ Operating Mode: Direct Handle / CS1-A Manual Operating Mechanism / CD2 Motor Operating Mechanism
⑪ □ Rated Current
⑫ □ Rated Voltage: AC800V / AC1140V
⑬ □ Accessory Voltage / Specification

Operating Conditions

Item Specification
Operating Altitude ≤ 2500 m
Ambient Temperature −35℃ to +70℃
Derating Required above +40℃
Storage Temperature −40℃ to +75℃
Relative Humidity ≤ 50% at +40℃; up to 90% at +20℃
Pollution Degree 3
Protection Degree IP20
Installation Vertical or horizontal
Vertical Installation Inclination ≤ 5°

Technical Specifications

Parameter CQM5HU-320 CQM5HU-630
Frame Size (A) 320 630
Rated Current In (A) 63, 80, 100, 125, 140, 160, 180, 200, 225, 250, 280, 315, 320 250, 315, 350, 400, 500, 630
Number of Poles 3P 3P
Rated Operational Voltage Ue (V) AC800 / AC1140 AC800 / AC1140
Rated Insulation Voltage Ui (V) 1250 1250
Rated Impulse Withstand Voltage Uimp (kV) 12 12
Breaking Capacity Class M —
Ics = 100% Icu @ AC800V (kA) 50 65
Ics = 100% Icu @ AC1140V (kA) 15 20
Electrical Operations @ AC800V 1500 1000
Electrical Operations @ AC1140V 1000 800
Mechanical Operations 15000 15000
Ambient Temperature -35℃ to +70℃* -3℃ to +70℃*
Normal Operating Altitude ≤ 2500 m ≤ 2500 m
Relative Humidity ≤50% at +40℃; up to 90% at +20℃ ≤50% at +40℃; up to 90% at +20℃
Pollution Degree 3 3
Installation Category III (Main Circuit) / II (Other) III
Degree of Protection IP20 IP20
Terminal Screw M8 M10
Terminal Tightening Torque 12 N·m 35 N·m
Mounting Screw M4 M4 / M3
Mounting Tightening Torque 1.5 N·m 1.5 / 0.8 N·m
Dimensions (L × W × H) mm 264 × 120 × 103 275 × 110 × 170
Standards IEC 60947-2, GB/T 14048.2 IEC 60947-2, GB/T 14048.2
Certification CCC、CE、TÜV、CB CCC

Recommended Conductor Cross-Section

Rated Current In (A) 63 80 100 125 140/160 180/200/225 250 315 320/350 400 500 630
Conductor Cross-Section (mm²) 16 25 35 50 70 95 120 185 185 240 2×240 2×240

Accessory List

Time-current characteristic curve

Overall and mounting dimensions

CQM5HU-320

CQM5HU-630

Why Choose CHAC

CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQM5HU, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.

01

CONFIRM THE SPECIFICATION

Agree the CQM5HU configuration, circuit duty and installation requirements.

02

REVIEW THE DOCUMENTS

Confirm model-specific drawings and destination-market requirements.

03

APPROVE THE SAMPLE

Record the accepted configuration and marking requirements.

04

DEFINE ORDER CHECKS

Agree packaging, identification and delivery requirements in the quotation.

CHAC Automated Assembly Line

Automated Assembly Line

CHAC Testing Laboratory

Testing Laboratory

CHAC Injection & Stamping

Injection & Stamping

CHAC Quality Inspection

Quality Inspection

What Can We Customize?

Discuss CQM5HU product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.

Logo & Branding

Submit logo artwork and marking requirements for review against the available print area and mandatory product markings.

CHAC CQM5HU product view

Packaging & Manuals

Define carton labels, packaging language, product identification and instruction requirements for the destination market.

CHAC CQM5HU product view

Configuration Selection

Specify CQM5HU with the required frame and current, operating conditions and protection duty. Confirm the complete order combination.

CHAC CQM5HU product view

Assembly Requirements

Provide the mounting and connection requirements for review. Changes to the housing, terminals or operating arrangement require engineering approval.

CHAC CQM5HU product view

Market Documentation

Request documents covering the exact CQM5HU model and destination market. A standard reference alone is not evidence of certification.

CHAC CQM5HU product view

Sample Approval

Agree the sample specification, drawing revision and acceptance criteria before confirming a production order.

CHAC CQM5HU product view

Technical Documents and Support

DOC

CQM5HU Technical Documents

Request the CQM5HU datasheet, configuration drawing, installation instructions and available model-specific market documents.Request Datasheet

SUP

Need Technical Documents?

Send the application, electrical requirements, assembly layout and destination market for configuration and document review.Contact Us

CQM5HU Product FAQ

What do Icu and Ics mean on an MCCB?

Icu is the rated ultimate short-circuit breaking capacity and Ics is the rated service breaking capacity under the specified test conditions. Compare them at the actual operating voltage. CQM5HU lists Ics equal to Icu for the published frame/voltage combinations.

Can I use the 800V breaking capacity at 1140V?

No. CQM5HU-320 lists 50kA at 800V but 15kA at 1140V; CQM5HU-630 lists 65kA and 20kA respectively. Check the value for the actual system voltage.

Does a magnetic-only MCCB protect against overload?

A magnetic-only release does not provide the thermal overload function. Select the thermal-magnetic CQM5HU option when both protections must be integral, or provide an appropriately coordinated external overload solution.

How do I choose the CQM5HU current rating?

Start with load current and conductor capacity, then check trip function, enclosure temperature and protection coordination. Use an available current step within the chosen frame; frame size alone is not the circuit protection setting.

Can I copy a cable size from the CQM5HU table?

Treat the conductor table as a product reference. Final sizing also depends on installation method, conductor material, temperature, grouping, voltage drop, short-circuit duty and local rules. Check terminal compatibility and the model-specific torque.

What should a distributor specify when ordering CQM5HU?

State frame, rated current, operating voltage, breaking-capacity version, trip function and accessory voltages. Include drawings, destination-market documents, quantity and marking requirements; approve the exact configuration before a repeat order.

Specify the Right CQM5HU Configuration

Send CHAC your required configuration, application, destination market and estimated quantity. We will review the requested specification and provide the relevant technical documents and commercial proposal.