PXB6DC-63M DC Miniature Circuit Breaker

Caraterísticas do Produto

■ Breaking capacity up to 10 kA for reliable short-circuit protection.

■ Rated current range from 0.5 A to 63 A.

■ Available in 1P, 2P, 3P and 4P configurations.

■ Mechanical endurance over 10,000 operations.

Especificação de Encomenda

Por favor, especifique o seguinte ao encomendar:

1.Product Model: PXB6DC-63M

2. Número de Polos: 1P, 2P, 3P, 4P

3.Rated Current & Tripping Curve: [e.g., 16A]

  • Rated Current (In): 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6,8, 10, 13, 16, 20, 25, 32, 40, 50, 63A

5.Quantity: [e.g., 100 pcs]

Exemplo de Pedido:

PXB6DC-63M 2P 16A 100 pcs

Especificações Técnicas

Parâmetro
Rated Voltage(V) 1P DC 125V
2P DC 250V
3P DC 375V
4P DC 500V
Rated Current(A) 0.5, 1, 1.6, 2, 2.5, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A
Rated Insulation Voltage(Ui) 500V
Ultimate Breaking Capacity(Icu)(kA) 10
Service Breaking Capacity(Ics)(kA) 7.5
Número de Polos 1P, 2P, 3P, 4P
Resistência Mecânica ≥10000
Resistência Elétrica ≥1500
Termination Capacity ≤25mm²
Tightening Torque(N·m) 2.5
Protection Class IP20
Padrão GB/T14048.2、IEC60947-2
Certificação CE·CB·CCC |DEKRA Certified

Tripping Characteristics(Reference Temperature: 30°C)

Artigo Test Current (A) Estado Inicial Prazo para tropeçar ou não tropeçar Resultado esperado Observações
a 1.05In Frio t≤1h Não disparável A corrente aumenta suavemente até atingir o valor especificado em 5 segundos
b 1.3In Seguindo o item a t<1h Viagem  
c 2,55 pol Frio 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
Viagem  
d 4In、8In、12In
80%
Frio t≥0.2s Não disparável Circuit switched on by closing an auxiliary switch. Verifies rapid breaking capability.
e 4In、8In、12In
120%
Frio t<0.2s Viagem

Nota: O termo “a frio” significa que o ensaio é efetuado a uma temperatura de calibração de referência, sem carga, antes do ensaio.

Designação do tipo

Curvas de disparo

Dimensões (mm)