Disjuntor Miniatura CQB2-63
O CQB2-63 miniature circuit breaker is designed for overload and short-circuit protection in 230/400V AC final-distribution systems. It covers 6A to 63A, B, C and D tripping curves, and 1P, 1P+N, 2P, 3P, 3P+N and 4P configurations. Its rated short-circuit breaking capacity is 6kA, with Icn equal to Ics. The series is specified to IEC 60898-1 and the model page lists CCC certification. It gives distributors, panel builders and OEM buyers a clearly defined platform for residential, commercial and light-industrial distribution projects.
Visão Geral do Produto
The CQB2-63 is a 6kA miniature circuit breaker for final-distribution circuits that require overload and short-circuit protection. It is rated for 230/400V AC at 50 or 60Hz and is available from 6A to 63A. Buyers can specify B, C or D tripping characteristics and choose 1P, 1P+N, 2P, 3P, 3P+N or 4P configurations to suit the circuit and local installation rules.
For buyers comparing a 6kA MCB, the CQB2-63 circuit breaker provides B, C and D choices within its published MCB trip curve options.
For distributors, panel builders and electrical OEMs, the series combines a consistent 6kA breaking-capacity platform with a broad configuration range. Selection should still be based on conductor ampacity, load behavior, prospective short-circuit current, ambient conditions and the destination market. The CQB2-63 is specified to IEC 60898-1, and CCC is the certification confirmed for this model on the current product page.
Principais Características
Aplicações Típicas
The CQB2-63 is intended for final circuits in residential, commercial and light-industrial distribution systems. Typical uses include lighting, socket-outlet, small HVAC, pump and other branch circuits when the selected rating and trip curve match the conductor, load and fault-current study. An MCB primarily protects the circuit conductors, so selection must account for cable size, installation method, ambient temperature, grouping and upstream coordination rather than the appliance name alone.
Guia de Candidaturas e Seleção
| Selection item | How to evaluate it | CQB2-63 options |
|---|---|---|
| Corrente nominal | Confirm design current, conductor ampacity, installation method, ambient temperature and grouping. Do not increase the breaker rating to solve repeated tripping without diagnosing the cause. | 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Tripping curve | Compare normal operating current, starting or inrush current and the fault-current level needed for timely magnetic operation. | B, C or D |
| Número de polos | Match the supply system and determine which live conductors—and, where required, the neutral—must be disconnected together. | 1P, 1P+N, 2P, 3P, 3P+N, 4P |
| Capacidade de corte | Verify that the prospective short-circuit current at the installation point does not exceed the device rating. Use another protective solution if the study requires a higher value. | 6kA, Icn = Ics |
| Standard and market documents | Check the product standard, destination-market rules and the exact documents required by the customer or approval body. | IEC 60898-1; CCC confirmed on this page |
Compare breaking capacity, tripping curves, pole configurations and protection functions before selecting the right miniature circuit breaker for your application.
6kA vs 10kA MCB
Select breaking capacity according to the prospective short-circuit current at the installation point, not only the rated current of the circuit.
B Curve vs C Curve vs D Curve
Select the tripping curve according to load inrush characteristics, not by current rating alone.
1P+N vs 2P MCB
Both options can be used in single-phase circuits, but their switching and protection arrangements are different.
Disjuntor (MCB) vs Disjuntor Diferencial (RCBO)
An MCB protects against overload and short circuit, while an RCBO also provides residual-current protection.
Need Help Selecting an MCB Configuration?
Share your pole configuration, rated current, tripping curve and quantity. Our team will help confirm a suitable CQB2-63 option for your application.
Guia de Encomenda
Professional MCB product pages commonly identify operating and storage conditions, mounting format, conductor capacity, tightening torque, dimensions and weight. These values vary by product family, rated current and pole configuration, so figures from another brand or series should not be applied to the CQB2-63. Confirm the following items on the approved CQB2-63 datasheet, installation instructions or project quotation before final selection:
For a project-specific confirmation, send CHAC the rated current, trip curve, pole configuration, destination market, expected quantity and panel or conductor constraints.
How to choose between B, C and D curves
The curve identifies the instantaneous magnetic-trip range, not a general quality grade. The CQB2-63 tripping table gives 3–5 × In for B curve, 5–10 × In for C curve and 10–20 × In for D curve. B curve is commonly considered for low-inrush circuits, C curve for moderate inrush, and D curve for higher-inrush equipment. The final choice must still provide adequate fault protection; selecting a slower curve only to avoid nuisance trips can delay operation when fault current is limited.
How to choose the pole configuration
Select the pole arrangement from the actual supply and isolation requirements rather than from panel space alone. A 1P device switches one conductor, while multi-pole versions provide mechanically linked operation for the specified conductors. Neutral switching and isolation rules vary by system and market, so 1P+N, 3P+N and 4P options should be confirmed against the project drawings and local requirements.
When 6kA is not enough
A 6kA marking means the breaker is rated to interrupt a prospective short-circuit current of up to 6,000A under the applicable test conditions; it is not the normal load-current rating. If the calculated or measured prospective fault current at the installation point exceeds 6kA, use equipment with a suitable rating or a verified coordinated solution rather than assuming every MCB is interchangeable.
Designação do tipo

Curvas de disparo

Dimensions(unit:mm)

Especificações Técnicas
| Parâmetro | |
| Rated insulation voltage | 500 V |
| Tensão estipulada de resistência a impulsos (Uimp) | 4000 V |
| Corrente nominal | 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Frequência nominal | 50 Hz / 60 Hz |
| Número de polos | 1P, 1P+N, 2P, 3P, 3P+N, 4P |
| Poder de corte nominal (Icn = Ics) | 6000 A |
| Vida mecânica | ≥ 10,000 operations |
| Vida elétrica | ≥ 6,000 operations |
| Tripping characteristics | B, C, D |
| Terminal center distance | 45 mm |
| Grau de proteção | IP20 |
| Normas | IEC 60898-1, GB/T 10963.1 |
| Certificação | CCC |
Table 1 Tripping characteristics (Reference temperature 30°C)
| Artigo | Curva de disparo | Corrente de teste In(A) | Estado Inicial | Prazo para tropeçar ou não tropeçar | Resultado esperado | Observações |
| a | B, C, D | 1,13ln | Frio | t≤1h | Não disparável | Current smoothly rises to specified value within 5s |
| b | B, C, D | 1.45ln | Following item a test | t<1h | Viagem | |
| c | B, C, D | 2.55ln | Frio | 1s<t<60s(ln≤32A) 1s<t<120s(ln>32A) |
Viagem | |
| d | B | 3In | Frio | t≤0,1s | Não disparável | Ligue a fonte de alimentação fechando o interruptor auxiliar |
| C | 5In | |||||
| D | 10ln | |||||
| e | B | 5In | Frio | t<0,1s | Viagem | Ligue a fonte de alimentação fechando o interruptor auxiliar |
| C | 10ln | |||||
| D | 20ln |
Nota: O termo “a frio” significa que o ensaio é efetuado a uma temperatura de calibração de referência, sem carga, antes do ensaio.
Requisitos e secção transversal do condutor
| Secção transversal de cobre (mm²) | Corrente nominal In(A) |
| 1 | Em ≤ 6 |
| 1.5 | 6 In≤13 |
| 2.5 | 13 In≤20 |
| 4 | 20 In≤25 |
| 6 | 25 In≤32 |
| 10 | 32 In≤50 |
| 16 | 50 In≤63 |
Porquê escolher a CHAC
Com mais de 30 anos de experiência em fabrico, mais de 1100 funcionários, mais de 100 milhões de postes
Com uma capacidade anual e um processo de produção automatizado 90%, a CHAC garante uma capacidade de produção estável e rigorosos
Controlo de qualidade para clientes OEM/ODM globais. O nosso sistema de fabrico interno suporta a longo prazo
cooperação para marcas elétricas, importadores e distribuidores.
30+
ANOS DE EXPERIÊNCIA
Especializado em fabrico de baixa tensão elétrica
1100+
FUNCIONÁRIOS
Equipa profissional garante qualidade e entrega estáveis
100M+
CAPACIDADE ANUAL DE POSTOS
Capacidade de produção em larga escala para satisfazer a procura global
90%
PRODUÇÃO AUTOMATIZADA
Automação avançada para alta eficiência e consistência

Linha de Montagem Automatizada

Laboratório de Ensaios

Injeção e Estampagem

Inspeção de Qualidade





Um rigoroso sistema de controlo de qualidade garante que cada produto cumpre as normas globais.
O que podemos personalizar?
CQB2-63 OEM/ODM options are reviewed per project rather than assumed to be available for every configuration. The published 6–63A ratings, B/C/D curves and listed pole arrangements are the starting platform. Marking, packaging, labels, manuals, appearance requests, engineering work and certification support depend on technical feasibility, order quantity, tooling requirements and the destination market. Changes to internal construction, breaking capacity, terminals, dimensions or certified ratings require separate engineering and compliance confirmation.
Logótipo e Identidade Visual
Logo and marking requests are reviewed against the available print area, required regulatory markings and approved artwork.

Embalagem
Personalização
Color boxes, cartons, labels and manuals can be reviewed by language, destination market and order quantity.

Elétrico
Personalização
Available rated-current, pole and B/C/D curve combinations are reviewed within the validated CQB2-63 platform.

Produto
Aparência
Housing or handle color requests require technical, material, tooling and compliance review before sampling.

Certificação
Apoio
Destination-market documents and certification requirements are reviewed for the exact model and configuration before sample approval.

Engenharia
Desenvolvimento
Drawing, prototype and validation support is scoped per project; internal construction or rating changes are not assumed.

Transferir
Disjuntor Miniature Série CQB2
Visão geral completa de componentes elétricos de baixa tensão e referência para seleção de produtos.
Precisa de Documentos Técnicos?
Contacte-nos para folhas de dados, certificados, desenhos, orientação de seleção ou suporte a projetos OEM/ODM.
CQB2-63 Miniature Circuit Breaker FAQ
How to choose the correct MCB?
Start with the conductor ampacity and circuit design current, then check the supply voltage, pole configuration, load inrush, ambient conditions and prospective short-circuit current. For the CQB2-63, select within 6–63A, match the B/C/D curve to the load and fault conditions, and verify that the installation point does not exceed the 6kA breaking-capacity rating.
What are the different types of poles in an MCB?
MCBs may switch one or several conductors together. The CQB2-63 is offered in 1P, 1P+N, 2P, 3P, 3P+N and 4P configurations; the correct option depends on the single- or three-phase system and whether the neutral must be switched or isolated under the applicable rules.
What does kA mean on circuit breakers?
kA indicates short-circuit breaking capacity, not continuous load current. The CQB2-63 has a 6kA rating, meaning it is designed to interrupt up to 6,000A of prospective short-circuit current under the stated IEC 60898-1 test conditions; the installation must be checked to confirm that this rating is sufficient.
What is the difference between a 1-pole MCB and a 2-pole MCB?
A 1-pole MCB operates one conductor, while a 2-pole MCB provides linked operation across two conductors. The choice depends on the supply arrangement and disconnection rules; two unrelated single-pole breakers should not be assumed to provide the same common operation as a purpose-designed 2P device.
What is the C curve and D curve in an MCB?
For the CQB2-63, the published instantaneous magnetic-trip ranges are 5–10 × In for C curve and 10–20 × In for D curve. D curve tolerates more starting current, but it should only be used when the load profile and available fault current allow the protective device to operate within the required disconnection time.
When should a B-curve MCB be used?
B curve is generally considered for circuits with relatively low starting or inrush current. The CQB2-63 data gives a B-curve magnetic-trip range of 3–5 × In; engineers should still confirm conductor protection, normal transients and fault-loop conditions rather than choosing the curve from the load label alone.
Build the Right CQB2-63 Configuration for Your Market
Send us your required current rating, B/C/D curve, pole configuration, destination market and estimated quantity. CHAC will review the specification and provide the relevant technical documents and commercial proposal.