CQM7 Thermal-Magnetic MCCB Manufacturer with OEM Branding Options
ال قاطع الدائرة الحراري المغناطيسي من سلسلة CQM7 provides overload and short-circuit protection for low-voltage AC distribution systems, with a 16–800A range and AC 400/415V ratings. Panel builders and equipment manufacturers can select the frame, breaking capacity and accessories to suit their assemblies. For distributor orders or project procurement, share your required configuration and quantity with CHAC for review.
مواصفات المنتج
The CQM7 Series Thermal-Magnetic Molded Case Circuit Breaker covers a rated current range of 16A-800A. Its compact design combines overload and short-circuit protection with accessory options for low-voltage switchboards and equipment assemblies. For OEM projects and distribution orders, the CQM7 catalogue gives purchasing and engineering teams a common reference for confirming ratings, dimensions and accessories before ordering.
الطلبات
Typical applications include industrial power distribution, commercial buildings, infrastructure, switchboards and motor protection. Panel builders and electrical contractors should match the selected CQM7 configuration to the circuit design, enclosure space and protection requirements. Importers and distributors can use the frame and current options to define a product range for their market, with local requirements checked for each configuration.
المواصفات الرئيسية
التيار المقدر: 16A-800A
الجهد التشغيلي المحدد: AC 400/415V
طاقة العزل المقدرة: 800 فولت
مقاومة الجهد الزائد: 8 كيلو فولت
قدرة كسر الدائرة القصيرة: تصل إلى 50kA عند الجهد 400/415 فولت، حسب نوع الإطار وتحديد قدرة الكسر
نوع الرحلة: حرارية مغناطيسية
Choose the Right CQM7 Frame for Your Project
Start with the circuit current and fault level, then compare the available CQM7 frames. The frame number identifies the frame rating; it does not mean that every breaker in that frame has the same rated current.
| CQM7 frame | Available rated currents (A) | Icu / Ics at AC 400/415 V (kA) |
|---|---|---|
| CQM7-125 | 16, 20, 32, 40, 50, 63, 80, 100, 125 | C: 25 / 15; S: 30 / 20 |
| CQM7-250 | 125, 140, 160, 180, 200, 225, 250 | C: 35 / 25; S: 40 / 30 |
| CQM7-400 | 250, 315, 350, 400 | S: 35 / 25; M: 50 / 35 |
| CQM7-630 | 250, 315, 350, 400, 500, 630 | S: 35 / 25; M: 50 / 35 |
| CQM7-800 | 500, 630, 700, 800 | S: 35 / 25; M: 50 / 35 |
The ratings above are for the published 3-pole models. C, S and M identify the listed breaking-capacity options. Match the selected option to the installation fault level and required service performance. Where current ratings overlap between frames, also compare mounting dimensions, conductor connections and accessory requirements.
دليل الاختيار
![]()
| رمز المنتج | قاعدة التوسيع | درجة إطار الشل | قوة الكسر | طريقة التشغيل | عدد الأقطاب | ||||
| CQM7 | G | 125 | C | P | 4 | ||||
| قاطع الدائرة في الصندوق المطلي | — : لا يمكن ضبط الحماية الحرارية والمغناطيسية. G: إنذار الزائد دون وظيفة الإيقاف |
C | S | M | H | P: التشغيل عن طريق المحرك Z: مقبض التعديل W: التشغيل المباشر |
125A:3P 250A:3P 400A:3P 630A:3P 800A:3P |
||
| 125 | 125 | 25/15 | 30/20 | / | / | ||||
| 250 | 250 | 35/25 | 40/30 | / | / | ||||
| 400 | 400 | / | 35/25 | 50/35 | / | ||||
| 630 | 630 | / | 35/25 | 50/35 | / | ||||
| 800 | 800 | / | 35/25 | 50/35 | / | ||||
| وحدة الرحلة ومعداتها | التيار المقدر A | الوظيفة | رمز الخيار 4P | رمز خاص | |
| 300 | 125 أمبير | 2 | A | I | |
| تحدد الرقمة الأولى نوع المقبض. 2: تثبيت فوري فقط 3: مقبض مكرر ملاحظة: الأرقام الأخيرة هي رمز الملحق (انظر جدول الملحقات). |
125 | 16,20,32,40,50,63,80,100,125 | 1: لتوزيع الطاقة 2: لحماية المحرك |
أ: النقطة N غير محمية ولا يمكن الجمع بينها. B:N-pole غير مأمون ويمكن الجمع بينهما C:N-pole مأمون ويمكن الجمع بينهما D:N-pole مأمون ولا يمكن الجمع بينهما |
I: وظيفة إنذار الزائد غير المتوقف |
| 250 | 125,140,160,180,200,225,250 | ||||
| 400 | 250,315,350,400 | ||||
| 630 | 250,315,350,400,500,630 | ||||
| 800 | 500,630,700,800 | ||||
| جهد الملحقات | الجهد التشغيلي للمحرك | التثبيت | خيارات التوصيل الطرفي | |||
| سؤال 1 | D1 | Q | 2 | |||
| نقص الجهد القبض سؤال 1: AC220V Q2: AC240V Q3: AC380V Q4: AC415V |
شنت الإفراج F1: AC220V F2: AC380V F3: DC110V F4: DC24V |
مساعد إنذار J1: AC125V J2: AC250V J3: DC125V J4: DC24V |
CD1 التشغيل الكهربائي D1: AC220V D2:AC230V D3: AC380V D4:AC400V |
CD2 التشغيل الكهربائي D5: AC230V D6: AC110V D7: DC220V D8:DC110 D9: AC110-240V D10: DC100-220V |
س: الجزء الأمامي من اللوحة H: الجزء الخلفي من اللوحة C:تم إدخاله |
1: التثبيت 2: التثبيت |
| ملاحظة: عند تحديد تشغيل المحرك، يرجى الرجوع إلى الملحقات الخارجية لمعرفة الجهدين المطبقين على تشغيل المحرك. | ||||||
المواصفات الفنية الرئيسية
| رقم النموذج | CQM7-125 | CQM7-250 | ||||
| توليد التيار الكهربائي في الإطار (Inm) (أ) | 125 | 250 | ||||
| عدد الأقطاب | 3 | 3 | ||||
| التيار المقدر (A) عند 40 درجة مئوية، و50 درجة مئوية، و55 درجة مئوية | 16, 20, 32, 40, 50, 63, 80, 100, 125 | 125, 140, 160, 180, 200, 225, 250 | ||||
| الجهد التشغيلي المقدر Ue (V)، تيار كهربائي 50/60 هرتز | 400/415 | 400/415 | ||||
| جهد العزل المقدر Ui (V) | 800 | 800 | ||||
| الجهد المقاوم للتأثير الكهربي Uimp (كيلو فولت) | 8 | 8 | ||||
| تصنيف قدرة التكسير | C | S | C | S | ||
| قدرة كسر الدائرة القصيرة Icu/Ics (kA) | تيار مستمر 400/415 فولت | 25/15 | 30/20 | 35/25 | 40/30 | |
| فئة الانتقائية | A | A | A | A | ||
| عدد دورات التشغيل (الدورة) | أفتح | 1000 | 1000 | |||
| إيقاف التشغيل | 10000 | 10000 | ||||
| آليات الرحلات وأنواع الحماية | رحلة مغناطيسية | حماية توزيع الطاقة | ● | ● | ● | ● |
| حماية المحرك | ● | ● | ● | ● | ||
| رحلة الحرارية المغناطيسية | حماية توزيع الطاقة | ● | ● | ● | ● | |
| حماية المحرك | ● | ● | ● | ● | ||
| الملحقات | الاتصالات الإضافية | ● | ● | ● | ● | |
| الاتصالات في حالة الطوارئ | ● | ● | ● | ● | ||
| قطع الشق | ● | ● | ● | ● | ||
| مستشعر انخفاض الجهد | ● | ● | ● | ● | ||
| آلية التشغيل اليدوية | ● | ● | ● | ● | ||
| آلية تشغيل ميكانيكية | ● | ● | ● | ● | ||
| توصيلات الخلفية | ● | ● | ● | ● | ||
| تم إدخاله | ● | ● | ● | ● | ||
| غطاء التوصيل | ● | ● | ● | ● | ||
| التقسيم بين المراحل | ● | ● | ● | ● | ||
| المنتجات المشتقة | مخصصة للمقاييس الكهربائية المدفوعة مقدماً | ● | ● | ● | ● | |
| إنذار الزائد دون حدوث انقطاع | – | – | ● | ● | ||
| الأبعاد الكلية (مم) (أ-ب-ج-كأ) | ![]() |
3 P | 77×131×65×82 | 105×165×68×95 | ||
ملاحظة:● بالنسبة للأدوات الاختيارية؛ “-” يعني عدم وجود أدوات اختيارية.
| رقم النموذج | CQM7-400 | CQM7-630 | CQM7-800 | |||||
| التيار المقدر على مستوى الإطار Inm(A) | 400 | 630 | 800 | |||||
| عدد الأقطاب | 3 | 3 | 3 | |||||
| التيار المقدر (A)، عند 40 درجة مئوية، و50 درجة مئوية، و55 درجة مئوية | 250, 315, 350, 400 | 250, 315, 350, 400, 500, 630 | 500, 630, 700, 800 | |||||
| الجهد التشغيلي المقدر Ue (V)، التيار المتردد 50/60 هرتز | 400/415 | 400/415 | 400/415 | |||||
| جهد العزل المقدر Ui (V) | 800 | 800 | 800 | |||||
| الجهد المقاوم للتأثير الكهربائي Uimp (KV) | 8 | 8 | 8 | |||||
| تصنيف قدرة التكسير | S | M | S | M | S | M | ||
| قدرة كسر المقاومة عند القصور في التيار Icu/Ics (kA) | AC400/415V | 35/25 | 50/35 | 35/25 | 50/35 | 35/25 | 50/35 | |
| فئة الانتقائية | A | A | A | A | A | A | ||
| عدد دورات التشغيل (الدورة) | أفتح | 1000 | 1000 | 500 | ||||
| إيقاف التشغيل | 4000 | 4000 | 2500 | |||||
| آليات الرحلات أنواع الحماية |
رحلة مغناطيسية | حماية توزيع الطاقة | ● | ● | ● | ● | ● | ● |
| حماية المحرك | ● | ● | ● | ● | ● | ● | ||
| رحلة الحرارية المغناطيسية | حماية توزيع الطاقة | ● | ● | ● | ● | ● | ● | |
| حماية المحرك | ● | ● | ● | ● | ● | ● | ||
| مستلزمات | الاتصالات الإضافية | ● | ● | ● | ● | ● | ● | |
| الاتصالات في حالة الطوارئ | ● | ● | ● | ● | ● | ● | ||
| قطع الشق | ● | ● | ● | ● | ● | ● | ||
| مستشعر انخفاض الجهد | ● | ● | ● | ● | ● | ● | ||
| آلية التشغيل اليدوية | ● | ● | ● | ● | ● | ● | ||
| آلية تشغيل ميكانيكية | ● | ● | ● | ● | ● | ● | ||
| توصيلات الخلفية | ● | ● | ● | ● | ● | ● | ||
| تم إدخاله | ● | ● | ● | ● | ● | ● | ||
| غطاء التوصيل | ● | ● | ● | ● | ● | ● | ||
| التقسيم بين المراحل | ● | ● | ● | ● | ● | ● | ||
| المنتجات المشتقة | مخصصة للمقاييس الكهربائية المدفوعة مقدماً | ● | ● | ● | ● | ● | ● | |
| إنذار الزائد دون حدوث انقطاع | ● | ● | ● | ● | ● | ● | ||
| الأبعاد الكلية (مم) (أ-ب-ج-ج) |
![]() |
3 P | 139×257×108×154 | 139×257×108×154 | 180×270×114×158 | |||
ملاحظة:● بالنسبة للأدوات الاختيارية؛ “-” يعني عدم وجود أدوات اختيارية.
خصائص التشغيل
1. يتم توضيح خصائص التشغيل العكسي لدّودات توزيع الطاقة عند تشغيل جميع المقاطع في وقت واحد عند درجة حرارة جوية مسببة +40 درجة مئوية (بدون تعويض للرطوبة) في الجدول التالي:
| اختبار التصنيف الحالي | إعداد متعددة الحالات الحالية | الوقت التقليدي | الوضع الأولي |
| في ≤63 <In | |||
| الحالة التقليدية بدون انقطاع التيار | 1.05 | ≥1 ساعة ≥2 ساعة | دولة رائعة |
| الحالة التقليدية لتسريع التيار الكهربائي | 1.30 | <1ساعة <2ساعة | الوضع الساخن |
2. تُظهر خصائص عمل مفاتيح الفصل الكهربائي في الحماية من المحركات دون تعويض الرطوبة عند تشغيل جميع المقاطع في وقت واحد عند درجة حرارة جوية مسببة +40 درجة مئوية في الجدول التالي:
| اختبار التصنيف الحالي | إعداد متعددة الحالات الحالية | الوقت التقليدي | الوضع الأولي |
| في ≤800 | |||
| الحالة التقليدية بدون انقطاع التيار | 1.0 | ≥2 ساعة | دولة رائعة |
| الحالة التقليدية لتسريع التيار الكهربائي | 1.2 | <2 ساعة | الوضع الساخن |
3. خصائص العمل في حالة العرقلة: قيمة إعداد التيار العرقلة في المحول الفوري للمفتاح الكهربائي لتوزيع الطاقة هي 10 إن.
يبلغ إعداد تيار المقاومة القصيرة في مقياس التذبذب الفوري للمفتاح الكهربائي لحماية المحركات 12 إن.
تكون دقة قيمة إعداد تيار العزل في المحول الفوري 20% من قيمة إعداد تيار العزل.
قائمة الملحقات



1. يمكن لشركتنا توفير ثلاثة منتجات جديدة يمكن للعملاء الاختيار من بينها، وهي مفتاح التوجيه الجانبي الأيمن، وأجهزة التوقف الاختباري الجانبي الأيسر، وأجهزة التخفيف من الجهد الأيسر.
2. بالنسبة لمواصفات 220 و320 و240 و340 و270 و370، يمكن لمفتاح التبديل الإضافي توفير زوجين من المفاتيح. يرجى تحديد ذلك عند تقديم طلبك.
3. بالنسبة للمواصفات 250 و350، لا يمكن تركيب جهاز السيطرة التنازلي وإطلاق التيار المنخفض لنماذج 400 وما فوق إلا على مفاتيح الحماية ثلاثية المقاطع.
CQM7-125 منحنى الخصائص التشغيلية

CQM7-250 منحنى الخصائص التشغيلية

CQM7-400 / 630 منحنى الخصائص التشغيلية

CQM7-800 منحنى الخصائص التشغيلية

مقدمة و أبعاد التركيب (مم)

| الحالة المطليّة قاطع الدائرة |
الابعاد الكلية | التثبيت الأبعاد |
بولت | |||||||||||||||||||||
| A | A1 | A2 | A3 | B | B1 | B2 | B3 | B5 | B6 | H | H1 | H2 | H3 | H4 | H5 | H6 | A4 | B4 | ||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |||||||||||||||||
| CQM7-125 | 77 | – | 50 | – | – | – | – | – | 131 | 116 | 90.2 | 45 | – | – | 82 | 68.3 | 3 | 65.3 | 56.5 | 25 | 25 | – | – | M6 |
| CQM7-250 | 105 | – | 70 | – | – | – | – | – | 165 | 144 | 101.2 | 60.8 | – | – | 95 | 73.1 | 6 | 68.1 | 61.4 | 22.3 | 23.1 | – | – | M8 |
| CQM7-400 | 139 | – | 88 | – | – | – | – | – | 257 | 224.5 | 150 | 97 | – | – | 154.2 | 110.5 | 4.5 | 108 | 99.5 | 35.2 | 36.5 | – | – | M10 |
| CQM7-630 | 136 | – | 88 | – | – | – | – | – | 257 | 224.5 | 150 | 97 | – | – | 154.2 | 110.5 | 4.5 | 108 | 99.5 | 35.2 | 36.5 | – | – | M10 |
| CQM7-800 | 180 | – | 116 | – | – | – | – | – | 270 | 235 | 150 | 96 | – | – | 158.2 | 116 | 5 | 114 | 103 | 43.5 | 44.8 | – | – | M12 |
لماذا تختار CHAC
مع خبرة تصنيع تزيد عن 30 عامًا، وأكثر من 1100 موظف، وأكثر من 100 مليون عمود
بفضل طاقتها الإنتاجية السنوية ونظام الإنتاج الآلي 90%، توفر شركة CHAC طاقة إنتاجية مستقرة ومعايير صارمة
مراقبة الجودة لعملاء OEM/ODM العالميين. يدعم نظام التصنيع الداخلي الخاص بنا على المدى الطويل
تعاون مع العلامات التجارية الكهربائية والمستوردين والموزعين.
30+
سنوات الخبرة
متخصص في تصنيع المعدات الكهربائية منخفضة الجهد
1100+
الموظفين
فريق محترف يضمن جودة ثابتة والتسليم
١٠٠ مليون+
السعة السنوية للأعمدة
قدرة إنتاجية واسعة النطاق لتلبية الطلب العالمي
90%
الإنتاج الآلي
الأتمتة المتقدمة لتحقيق كفاءة واتساق عاليين

خط التجميع الآلي

مختبر اختبار

حقن وختم

فحص الجودة





طلب الوثائق التقنية والمتعلقة بالتوافقية الخاصة بـ CQM7 المطلوبة لمشروعك. المعلومات على مستوى الشركة والعلامات المعروضة لا تعني الموافقة على كل تكوين لـ CQM7 في كل سوق.
ما الذي يمكننا تخصيصه؟
For electrical brands, equipment manufacturers and distributors sourcing CQM7 MCCBs, start with the frame, rated current within the published 16–800 A range, protection duty and catalogue-listed accessories. CHAC can review private-label marking, packaging and technical-document requirements for the agreed configuration. Include your destination market and order quantity in the enquiry; housing, internal or electrical changes require engineering confirmation.
حَظِيرة
تصميم
تحقق من أبعاد الإطار وتركيب الإطار والمسافات المسموح بها لبطاقة الطاقة الخاصة بك. تتطلب تغييرات الهيكل موافقة هندسية.

داخلي
إعدادات
حدد تكوين الرحلة المطلوب ومجموعات الملحقات المذكورة في الكتالوج المناسبة للإطار CQM7 الذي تم طلبه.

العلامة التجارية و
شعار
For private-label orders, review logo, nameplate and label artwork while retaining the required CQM7 identification and electrical markings.

تعبئة وتغليف
تصميم
Discuss unit cartons, shipping cartons, labels and manuals for your distribution channel, with packaging requirements agreed before the order is confirmed.

كهربائي
إعدادات
تأكد من القيمة المقدرة للحالة الحالية، والجهد الكهربائي 400/415 فولت، ووظيفة كابينة العزل. قم بتحديد الجهدات المساعدة للتحكم بشكل منفصل.

شهادة
دعم
طلب الوثائق التقنية اللازمة لتكوين CQM7 المحدد والسوق المستهدف. التحقق من الموافقات حسب النموذج والنطاق.

What to Confirm Before Ordering CQM7 MCCBs
A clear specification helps panel builders, OEM purchasing teams and distributors compare quotations for the same product. Use these four checks to define the technical and commercial scope of your enquiry.
Define the electrical configuration
List the CQM7 frame, rated current, AC system voltage, required Icu/Ics, poles and distribution or motor-protection duty. Include the selected trip type and accessories.
Attach the relevant specification or bill of materials so the quotation identifies the intended configuration.
Break down the quantity by model
For project or distributor orders, state the quantity for each configuration. Separate any sample request from the main order and provide your requested delivery schedule.
Ask CHAC to confirm availability and lead time for the agreed configuration and quantity.
Agree the branding and packaging scope
For OEM branding, provide logo artwork, proposed nameplate details and label requirements. Specify unit and shipping cartons, manuals and any distributor packaging needs.
Review the proposed artwork and packaging specification before approving the order.
Identify the documents your market requires
State the destination market and request the applicable datasheet, dimensional drawing, installation instructions and conformity documents for the exact model.
Check document scope against the ordered configuration; company-level certificates do not establish every product approval.
تنزيل
قائمة منتجات CQM7
كتالوج قواطع التيار المباشر المكون من 7 أقطاب من CQM7 مع دليل اختيار يتراوح من 16 إلى 800 أمبير، وتقييمات تقنية، وخيارات لوازم، وعوارض تشغيل، ومقاسات التركيب.
هل تحتاج إلى وثائق فنية؟
اتصل بنا للحصول على أوراق البيانات، والشهادات، والرسومات، وإرشادات الاختيار، أو دعم مشاريع OEM/ODM.
أسئلة متكررة حول منتج CQM7
لماذا تُستخدم مفاتيح الحماية المدمجة CQM7؟
توفّر وحدة CQM7 حماية من الحمل الزائد والتوتر الكهربائي للمحولات ذات الجهد المنخفض. وتتضمن تطبيقاتها المعتمدة توزيع الطاقة في الصناعة والمباني التجارية والبنية التحتية وصمامات التبديل وحماية المحركات. اختر بين إصدارات وحدة التوزيع أو حماية المحركات لتناسب الدائرة ومتطلبات التنسيق الخاصة بها.
ما هو الجهد التشغيلي المحدد لـ CQM7؟
تحدد الجداول الفنية لـ CQM7 التيار المستمر عند 400/415 فولت بمعدل 50/60 هرتز. وتحدد تصنيف العزل 800 فولت ومقاومة الصدمات 8 كيلوفولت خصائص مختلفة؛ ولا يرفع أي من هذين التصنيفين من الجهد التشغيلي المسموح به. استخدم تصنيفات الجهد التشغيلي ومقاومة الصدمات الخاصة بالنموذج المحدد الذي تُريد شرائه.
كيف يمكنني اختيار حجم الإطار ودرجة الجهد المقدرة لـ CQM7؟
تغطي السلسلة نطاقات التيار من 16 إلى 800 أمبير عبر الإطارات CQM7-125 و-250 و-400 و-630 و-800. لا يعادل تصنيف الإطار التيار المقدر للمفصل المجهز. ابدأ من الحمل التصميمي واحتياجات حماية الكابلات، ثم اختر تصنيف تيار متاح في الإطار المناسب. قبل طلب المنتج، تأكد من درجات الحرارة المحيطة وأوضاع الغرفة وتنسيق الحماية.
ما هو الفرق بين وحدة التحكم في العطل (ICU) ووحدة التحكم في العطل (ICCS) في مقبس MCCB CQM7؟
Icu هي القدرة القصوى المقدرة على كسر الدائرة القصيرة؛ وIcs هي القدرة القصوى المقدرة على كسر الدائرة القصيرة أثناء التشغيل. عند جهد 400/415 فولت، تظهر جداول CQM7 أزواج Icu/Ics بنسب 25/15 أو 30/20 kA للدوائر 125، و35/25 أو 40/30 kA للدوائر 250، و35/25 أو 50/35 kA للدوائر 400 و630 و800. تحقق من تحديد القدرة القصوى الدقيقة وفقًا لمستوى الأعطال ومتطلبات الخدمة الخاصة بالمعدات. لا ينطبق الحد الأقصى لـ Icu البالغ 50 kA على جميع الطرازات.
ما هي تكوينات قضبان CQM7 الموضحة في الجداول الفنية؟
تُعرض الجداول الفنية الرئيسية المصورة والرسومات الأبعادية المعروضة في هذا المقال نماذج ثلاثية القطب لتركيبات CQM7-125 و-250 و-400 و-630 و-800. على الرغم من أن دليل الترتيب يحتوي أيضًا على رموز خيارات القطبين، فلا يُفترض أن كل تركيبة متوفرة في نسخة ذات ثلاثة قطبين. يُرجى طلب التكوين المحدد والرسومات المعنية قبل تحديد القطبين غير النشطين.
ما الذي يجب التحقق منه قبل تثبيت وتفعيل نظام CQM7؟
يجب على الفنيين المؤهلين التحقق من الطراز المحدد، والجهد المقدر، وقدرة الكسر، وأبعاد التركيب، واتصالات الموصلات، وعزم الدوران للموصلات، والمسافات المطلوبة وفقًا لإرشادات التركيب. تأكد من تحديد الجهد القياسي للعتاد، وأتمّ عمليات الفحص الوظيفي المحددة قبل تشغيل الجهاز. استخدم الرسم الخاص بالصندوق المحدد بدلاً من استخدام حجم آخر من CQM7.
كيف يتوقف مقبس MCCB الحراري المغناطيسي؟
في الموصلات الحرارية المغناطيسية، يستجيب عنصر الحرارة إلى الحمل الزائد المستمر، بينما يستجيب عنصر المغناطيس إلى التيار الزائد العالي. يميز كتالوج CQM7 بين التكوينات الحرارية المغناطيسية والتركيزات الميكانيكية فقط، بالإضافة إلى مهام توفير الحماية والتوزيع. قم بتحديد نوع الحماية المطلوب؛ فلا يوفر إصدار ميكانيكي فقط نفس مستوى الحماية من الحمل الزائد مثل الإصدار الحراري المغناطيسي.
هل يمكن ضبط إعدادات الرحلات الحرارية والمغناطيسية في جهاز CQM7؟
تُصنف التكوين الحراري المغناطيسي القياسي في دليل الترتيب CQM7 على أنه يحتوي على حماية حرارية ومغناطيسية غير قابلة للتعديل. لا يُفترض أن جميع المكونات الميكروويفية الحرارية والمغناطيسية لها إعدادات قابلة للتعديل. إذا كان المشروع يحتاج إلى حماية قابلة للتعديل، فقم بتقديم نطاقات الإعدادات والدراسة التنسيقية المطلوبة حتى يتمكن من تقييم التكوين أو المنتج المناسب.
متى يجب أن أختار مكاب بدلاً من مكب؟
يجب تقييم مكاب عند الحاجة في الدائرة إلى نطاق تيار، أو قدرة كسر، أو ترتيب توصيل، أو ملحق تحكم لا يوفرها مكاب المقترح. تتجاوز عائلة CQM7 نطاق 800 أمبير وتوفر خيارات ملحقية محددة للفرامل. في حال تداخل التصنيفات، يُرجى مقارنة الأجهزة الدقيقة وتنسيقها، والأبعاد ومتطلبات التركيب، بدلاً من اختيارها وفقاً لفئة المنتج وحدها.
هل يوفر قاطع MCCB CQM7 أيضًا حماية من تسرب الأرض؟
تتضمن المعيارية CQM7 الموضحة هنا حماية من الحمل الزائد والتدخل الكهربائي. ولا توفر هذه الوظائف حماية من التيار المتبقي أو تسرب الأرض. وفي حال كان المشروع يتطلب حماية من تسرب التيار، يُرجى تحديد هذه الوظيفة بشكل منفصل وتأكيد الجهاز المناسب أو التجمع المنسق. ولا يكفي وجود فتحة شحن فقط للكشف عن تسرب التيار.
هل يمكن استخدام محول الطاقة العالي الكفاءة CQM7 في دائرة تيار مستمر أو دائرة طاقة شمسية؟
لا تستخدمي الفئة AC 400/415 فولت في دائرة تيار متردد. تتطلب انقطاع التيار المتردد جهدًا تياريًا مُعلنًا، وتوزيعًا للقطب، واتجاهًا للتيار، ومواصفات قطع التيار المناسبة لنوع النموذج المحدد. لا تحدد جداول AC CQM7 الواردة في هذه الصفحة هذه الفئات. بالنسبة للدوائر الكهروضوئية أو البطاريات، اختر منتجًا يتم توفيره تصنيفات موثقة للتطبيق التيار المتردد المقصود.
ما هو الفرق بين رحلة الشنت وإطلاق التيار الكهربائي عند انخفاض الجهد؟
عند تلقي الإشارة الخارجية المحددة، يفتح جهاز الشحن الكهربائي المفتاح. يتفاعل جهاز التخلص من الحمل الزائد عند انخفاض إمداد التحكم إلى أقل من ظروف التشغيل المحددة، وقد يمنع إغلاق الجهاز دون إمداد كاف. يورد كتالوج CQM7 قائمة بكل من الأنواع الإضافية. تأكد من نوع الإطار والتركيب الإضافي وارتفاع الجهد في المقبس الكهربائي أو المقبس الدائري، وشكل الأسلاك قبل طلب الجهاز؛ لا يمكن استبدال هاتين الوظيفتين.
تأكيد التكوين الصحيح لـ CQM7
Planning a panel-building project, distributor order or OEM supply enquiry? Send the CQM7 frame, rated current, AC system voltage, fault level, protection duty, accessories and quantity. Include the destination market and any branding or packaging requirements so CHAC can review the configuration and quotation scope.