Resistance of 12 AWG Wire: Ohms per Foot and Voltage Drop

A technician estimates the voltage drop on a 100-foot cable run and gets a reassuring result. The installed two-wire circuit shows roughly twice the resistive drop predicted because the calculation counted the outgoing conductor but omitted the return. This illustrative error is common when route length and conductor length are treated as the same quantity.

ملخص: The nominal resistance of 12 AWG wire made from copper is approximately 1.588 Ω per 1,000 feet at 20°C, or 5.20864 Ω/km. State the material and temperature, count the complete current path, and distinguish conductor resistance from connections and AC impedance.

What is the resistance of 12 AWG copper wire at 20°C?

Resistance depends on resistivity, length and metallic cross-sectional area: R = ρL/A. The familiar AWG resistance value assumes a particular conductor material and reference temperature. A gauge designation alone does not establish resistance when material or construction is different.

PowerStream’s wire-size table gives approximately 1.588 Ω per 1,000 feet for 12 AWG copper. Dividing by 1,000 gives 0.001588 Ω per foot. Converting the same reference gives approximately 0.00520864 Ω per meter. These are nominal reference values, not a guaranteed maximum for every finished cable.

12 AWG copper reference at 20°C Approximate resistance التفسير
1 foot of one conductor 0.001588 Ω 1.588 milliohms
100 feet of one conductor 0.1588 Ω Does not include a return conductor
1,000 feet of one conductor 1.588 Ω Common reference-table basis
1 meter of one conductor 0.00520864 Ω 5.20864 milliohms
1 kilometer of one conductor 5.20864 Ω Same reference expressed metrically

The area and resistance columns in an AWG chart answer different questions. Area helps describe conductor size; resistance supports a voltage-drop or loss calculation. Neither alone establishes allowable current in an installed circuit.

For purchasing, use the cable manufacturer’s stated maximum DC conductor resistance where available. A nominal engineering-table value is useful for an estimate, but a contractual acceptance limit should identify the product standard, test temperature, length basis and construction.

Use a stated material and temperature — Resistance of 12 AWG Wire

Calculate voltage drop using both outgoing and return conductor lengths

For a simple two-wire DC circuit, current travels to the load and returns through another conductor. If the route is 100 feet and both conductors have the same size and length, the resistive path is 200 feet. Its nominal resistance at 20°C is 200 × 0.001588 = 0.3176 Ω.

At a hypothetical 20 A load, Vdrop = I × R = 20 × 0.3176 = 6.352 V. Relative to 120 V, that is approximately 5.29%; relative to 240 V, it is approximately 2.65%. These percentages compare the same resistive drop with two different supply voltages; they do not approve a particular circuit design.

The example is exact for its stated resistive DC model and is a useful approximation for an AC circuit where reactance and power-factor effects are negligible. Other AC arrangements need the appropriate impedance and phase relationships. In particular, do not apply the simple two-wire multiplier indiscriminately to a balanced three-phase calculation.

Illustrative two-wire circuit 20°C reference 75°C estimate
طول المسار باتجاه واحد 100 ft 100 ft
Total outgoing and return length 200 ft 200 ft
Resistance per 1,000 ft 1.588 Ω About 1.931 Ω
Loop resistance 0.3176 Ω About 0.3862 Ω
Current used for the calculation 20 أ 20 أ
انخفاض الجهد المقاومي 6.352 V About 7.725 V

The 20 A value is chosen only to demonstrate arithmetic. Permissible loading depends on conductor material, insulation, installation conditions, terminals and applicable rules. A successful voltage-drop calculation cannot replace the separate ampacity and protection checks.

Use the complete outgoing and return path — Resistance of 12 AWG Wire

How conductor temperature changes 12 AWG copper resistance

Conductor temperature matters because copper resistance rises as temperature increases. A practical linear approximation around the reference range is RT = R20[1 + α(T − 20)], using a copper coefficient of approximately 0.00393 per °C at 20°C.

At 75°C, the factor is 1 + 0.00393 × 55 = 1.21615. Multiplying 1.588 Ω per 1,000 feet by that factor gives approximately 1.931 Ω per 1,000 feet. The corresponding 200-foot loop is approximately 0.3862 Ω, producing about 7.725 V drop at the illustrative 20 A.

This is a temperature-correction example, not a prediction that the conductor will operate at 75°C. Actual operating temperature depends on load, ambient conditions, heat dissipation and installation. An insulation temperature marking is a limit under specified conditions, not an automatic estimate of running temperature.

Keep the reference conditions with the result. Comparing a manufacturer’s resistance at 20°C with an operating measurement on a warm conductor can suggest a defect where none exists. Equally, unexplained excess resistance should not be dismissed as temperature without checking the actual conditions.

How material, stranding and connections affect total circuit resistance

Aluminum has higher resistivity than copper. Using illustrative material values of 2.65 × 10−8 Ωm for aluminum and 1.724 × 10−8 Ωm for copper gives a ratio of about 1.54 for equal length and area at the stated reference conditions. Actual alloys and product specifications must be checked.

That ratio is a material comparison, not permission to substitute aluminum wire in a copper-only terminal. Conductor approval, connection method and installation rules remain separate. Do not infer compatibility from gauge size or a resistance calculation.

Stranded and solid conductors of the same nominal gauge have similar intended metallic area, but exact resistance can differ with strand geometry, lay length and manufacturing limits. For long runs or acceptance testing, use the exact product’s resistance data rather than assuming every construction matches a single table value.

Connections add resistance to the circuit. A poor termination can create a localized hot spot that is not represented by the uniform conductor model. Longer cable resistance and defective connection resistance may produce similar total voltage loss while requiring very different corrective action.

At low resistance values, measurement method matters. Test-lead and contact resistance can be significant compared with the sample. Suitable four-wire measurement can separate lead effects for an appropriate de-energized test, while temperature and sample length must still be recorded.

Check circuit conditions before using resistance to calculate voltage drop

For AC circuits, resistance is only part of impedance. Frequency, conductor arrangement and load power factor can affect the calculated drop. Use the relevant method for the circuit, and check whether a calculator expects one-way route length or total conductor length before entering the number.

ال voltage-drop calculator can support an initial check when its assumptions match the installation. Keep the material, temperature basis, load current, voltage and length definition with the output so another reviewer can reproduce the result.

When selecting a CHAC قاطع دارة مصغر PXB6-63, confirm conductor and terminal requirements independently of voltage drop. The resistance values in this article do not establish an approved conductor type, current setting or protective arrangement for a particular model.

A useful purchase or design record includes the exact wire construction, manufacturer’s maximum resistance, expected operating conditions and permitted voltage drop. This makes a proposed cable substitution reviewable. It also prevents a nominally equal gauge from being accepted without checking material and installation differences.

Common questions about 12 AWG resistance and voltage drop

What is the resistance of 12 AWG copper wire per foot at 20°C?

The nominal reference is approximately 0.001588 Ω per foot, or 1.588 milliohms per foot. It applies to one conductor length. Use the manufacturer’s specified value for product acceptance.

What is the resistance of 12 AWG copper wire per meter?

It is approximately 0.00520864 Ω per meter at 20°C using the stated reference. That is about 5.209 milliohms per meter. Material and temperature must remain part of the description.

What is the resistance of a 100-foot length of 12 AWG copper wire?

One 100-foot conductor is approximately 0.1588 Ω at 20°C. A 100-foot two-wire route with an equal return conductor has approximately 0.3176 Ω of conductor-loop resistance. Connections add separately.

How does temperature change the resistance of 12 AWG wire?

Copper resistance increases with temperature. Using a coefficient of 0.00393 per °C gives approximately 21.6% higher resistance at 75°C than at 20°C. The actual conductor temperature must be assessed separately.

Does stranded 12 AWG wire have the same resistance as solid wire?

The values are generally comparable for the same material and nominal size, but are not necessarily identical. Strand lay and manufacturing specifications affect the result. Use the exact product’s maximum DC resistance where accuracy matters.

How does 12 AWG aluminum wire resistance compare with copper?

Aluminum has higher resistance for the same area and length. The illustrative resistivity values used here give about 1.54 times the copper value. This comparison does not establish interchangeability or terminal approval.

How do you calculate voltage drop using the round-trip resistance of 12 AWG wire?

For the simple two-wire resistive case, multiply resistance per unit length by the outgoing plus return length, then multiply by current. A 200-foot loop at 20°C is about 0.3176 Ω, giving 6.352 V drop at 20 A. Use the appropriate AC method where reactance or phase relationships matter.

المراجع

A resistance value becomes useful when its material, temperature and length are clear. Discuss your breaker application with CHAC using the conductor specification and completed circuit calculation.