CQM5E Series Electronic Molded Case Circuit Breaker

The CQM5E series electronic molded case circuit breaker is designed by CHAC Electric for use in AC 50Hz/60Hz systems with a rated voltage of up to AC 690V and a rated current of up to 800A.Additionally, it provides ground fault protection, further enhancing the safety and reliability of electrical systems.

Polacos
3P / 4P

Corriente nominal:
10A–800A

Voltaje nominal
380/400/415/660/690V AC

Capacidad nominal de interrupción de cortocircuito:
20/70/85/100kA

Capacidad nominal de interrupción de cortocircuito de servicio:
10/50/65/75kA

Estándar
IEC 60947-1, IEC 60947-2
Personalización
Servicio OEM/ODM integral

Características del producto

■ Compact and modular design for quick installation and maintenance.

■ High breaking capacity (M-type: higher breaking, H-type: high brreaking)

■ Provides overload, short-circuit, and ground fault protection, with optional undervoltage protection.

■ Supports communication module integration for remote monitoring and control (remote trip, adjustment, testing, and signaling).

■ Suitable for both distribution network and motor protectionapplications.

■ Complies with IEC 60947-1, IEC 60947-2, and GB/T 14048 standards

Condiciones de Operación y Ambientales

■ Designed for vertical mounting (±5° tilt allowed unless specified)。

■ Suitable for infrequent circuit switching and motor starting operations

■ Pollution degree: 3

■ Communication module can be added for smart functionality.

Lista de accesorios

Dimensiones (mm)

CQM5E-125 (M, H Types)

Front Terminal Connection Dimensions

(X-X, Y-Y denote center points for 3P breakers)

CQM5E-250 (M, H Types)

Front Terminal Connection Dimensions

(X-X,Y-Y denote center points for 3P breakers)

CQM5E-400 (M, H Types)

Front Terminal Connection Dimensions

(X-X, Y-Y denote center points for 3P breakers)

CQM5E-630 (M, H Types)、CQM5E-800 (M, H Types)

Front Terminal Connection Dimensions

(X-X, Y-Y denote center points for 3P breakers)

Designación del tipo

Code Position Code Symbol Meaning & Explanation
CQ Enterprise Code: Zhejiang Chuangqi Electric Co., LTD.
M Interruptor automático moldeado
5 Design Serial Number
E Special Protection Function Residual Current Protection (Options: L=RC Protection)
125 Rated Frame Current (A): Options: 125, 250, 400, 630, 800
M Short-Circuit Breaking Capacity:
• M: Higher Fault Capacity
• H: High Fault Capacity
Operation Mechanism [blank]: Manual | Z: Rotary Handle | P: Motorized
Intelligence Function
• [blank]: Basic Protection
• G: Ground Fault Protection
• T: Communication Capable
• GT: Ground+Communication
4 Number of Poles:• 3 – Three Poles    • 4 – Four Poles
300 Trip Unit & Accessories Code:• 3 – Electronic Trip (Compound Trip)
• 00 – No Accessories (Refer to accessory table for specific codes)
□: Application Profile   [blank]: Distribution | 2: Motor Protection
B N-Pole Type (For 4P products only):
• Type A: N-pole is always connected, without overcurrent release.
• Type B: N-pole breaks with other poles, without overcurrent release.
• Type C: N-pole breaks with other poles, with overcurrent release.
• Type D: N-pole is always connected, with overcurrent release.
Special Function   I: Overload Alarm (non-trip)
Rated Current (A)   Options: 32 | 63 | 125 | 250 | 400 | 630 | 800
Terminal & Connection Type:
• (No Code) – Front Terminal Connection
• B – Rear Terminal Connection
• C – Plug-in Type

Especificaciones técnicas

Número de modelo CQM5E-125 CQM5E-250
Rated current In(A), 40℃ 32 63 125 250
Setting Current Ir (A), 40℃ 16/20/25/32 32/40/50/63 63/80/100/125 100, 125, 140, 160, 180, 200,225, 250
Rated operating voltage Ue(V) AC380/400/415V AC380/400/415V
AC660/690V AC660/690V
Rated insulation voltage Ui (V) 1000 1000
Rated impulse withstand voltage Uimp(KV) 8 8
Mechanical life 20000 20000
Electrical life(AC415V) 8000 8000
Trip mechanisms and protection types Electronic Electronic
Selectivity category A A
Número de polos 3P 4P 3P 4P
Breaking capacity designation M H / M H /
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 70 85 70 70 85 70
AC660/690V 20 / 20 20 / 20
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 50 65 50 50 65 50
AC660/690V 10 / 10 10 / 10
Phase spacing (mm) 30 35
Arc distance (mm) ≤50 ≤100
Operating ambient temp -35 ℃ to +70℃ -35 ℃ to +70℃
Rated short-time withstand current (Icw) 1kA/1s 2.5kA/1s
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Short-circuit protection types Short-time delay protection (S) Isd= (2-12) Ir Isd= (2-12) Ir
Instantaneous protection (I) Ii= (4-14) Ir Ii= (4-14) Ir
Overall dimensions
(mm) (L-W-H)
3 P 155-90-90 165-105-103
4 P 155-120-90 165-140-103

Note: ● for optional accessories;”-” for no optional accessories.

Número de modelo CQM5E-400 CQM5E-630
Rated current In(A), 40℃ 400 630
Setting Current Ir (A), 40℃ 200, 225, 250, 280, 315, 350, 400 400, 420, 440, 460, 480, 500, 530, 560, 600, 630
Rated operating voltage Ue(V) AC380/400/415V AC380/400/415V
AC660/690V AC660/690V
Rated insulation voltage Ui (V) 1000 1000
Tensión nominal de choque soportada Uimp (kV) 8 8
Mechanical life 10000 10000
Electrical life(AC415V) 7000 7000
Trip mechanisms and protection types Electronic Electronic
Selectivity category B B
Número de polos 3P 4P 3P 4P
Breaking capacity designation M H / M H /
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 70 100 70 70 100 70
AC660/690V 20 / 20 20 / 20
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 50 75 50 50 75 50
AC660/690V 10 / 10 10 / 10
Phase spacing (mm) 48 70
Arc distance (mm) ≤100 ≤100
Operating ambient temp -35℃ to +70℃ -35℃ to +70℃
Rated short-time withstand current (Icw) 5kA/1s 10kA/1s
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Short-circuit protection types Short-time delay protection (S) Isd= (2-12) Ir Isd= (2-12) Ir
Instantaneous protection (I) Ii= (4-14) Ir Ii= (4-14) Ir
Overall dimensions
(mm) (L-W-H)
3 P 257-150-140.5 280-210-112
4 P 257-198-140.5 280-280-112

Note: ● for optional accessories;”-” for no optional accessories.

Número de modelo CQM5E-800
Rated current In(A), 40℃ 800
Setting Current Ir (A), 40℃ 630,640,660,680,700,720,740,760,780,800
Rated operating voltage Ue(V) AC380/400/415V
AC660/690V
Rated insulation voltage Ui (V) 1000
Tensión nominal de choque soportada Uimp (kV) 8
Mechanical life 10000
Electrical life(AC415V) 7000
Trip mechanisms and protection types Electronic
Selectivity category B
Número de polos 3P 4P
Breaking capacity designation M H /
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 70 100 70
AC660/690V 20 / 20
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 50 75 50
AC660/690V 10 / 10
Phase spacing (mm) 70
Arc distance (mm) ≤100
Operating ambient temp -35℃ to +70℃
Rated short-time withstand current (Icw) 10kA/1s
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Short-circuit protection types Short-time delay protection (S) Isd= (2-12) Ir
Instantaneous protection (I) Ii= (4-14) Ir
Overall dimensions
(mm) (L-W-H)
3 P 280-210-112
4 P 280-280-112

Note: ● for optional accessories;”-” for no optional accessories.

Internal Accessories

1.1 AX Auxiliary Contact

Function

Remote status indicator for breaker ON/OFF or trip-free operation, integrated into the auxiliary circuit.

Indicating Circuit Breaker ON/OFF Status

When the circuit breaker is in the “OFF” and “TRIPPED”position Dual auxiliary contact
Single auxiliary contact.
When the circuit
breaker is in the “ON”
position
Dual auxiliary contact
Single auxiliary contact

Electrical Characteristics

Classification Frame Rating Conventional Thermal Current (A) Rated Operational Current (A)
Auxiliary Contact 63,100,125,250 3 AC400V DC220V
400,630,800 3 0.4 0.15

1.2 AL Alarm Contact

Wiring Diagram

Function

Primarily used to provide a signal when a fault such as overloadd,short circuit,or undervoltage occurs on the circuit breaker’s loaad side,orwhenitentersafree-trip state.

Reasons for the alarm contact to issue a fault indication signal:

Overload or Short Circuit Trip

Undervoltage Trip

Residual Current Operation Trip

Manual Free-Trip

Indicating Circuit Breaker ON/OFF Status

When the circuit breaker is in the “OFF” and “ON” position
When the circuit breaker is in the “TRIPPED” position.

Electrical Characteristics

Classification Frame Rating Conventional Thermal Current (A) Rated Operational Current (A)
Alarm Contact 63,100,125,250 3 AC400V DC220V
400,630,800 3 0.4 0.15

1.3 SHT Shunt Release

Wiring Diagram

 

Function

The shunt release is activated by an electrical signal, enabling remote and automatic control of the circuit breaker. The shunt release shall reliably cause the circuit breaker to operate when the supply voltage is any value between 70% and 110% of the rated control supply voltage.

Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W)
DC24V DC220V AC230V AC380V DC24V DC220V AC230V AC380V
1 CQM5-63/100 5.7 0.62 0.64 0.38 136.8 136.4 147.2 152
2 CQM5-125 4 0.24 0.25 0.43 97.6 52.6 57.5 173.9
3 CQM5-250 4 0.24 0.25 0.43 97.6 52.6 57.5 173.9
4 CQM5-400/630 6.8 0.48 0.76 0.28 164.5 105 176.3 112
5 CQM5-800 6.8 0.48 0.76 0.28 164.5 105 176.3 112
Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W)
DC24V DC220V AC230V AC380V DC24V DC220V AC230V AC380V
1 CQM5L-125 4 0.24 0.25 0.43 97.6 52.6 57.5 173.9
2 CQM5L-250 4 0.24 0.25 0.43 97.6 52.6 57.5 173.9
3 CQM5L-400 6.8 0.48 0.76 0.28 164.5 105 176.3 112
4 CQM5L-630 6.8 0.48 0.76 0.28 164.5 105 176.3 112
Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W)
DC24V DC220V AC230V AC380V DC24V DC220V AC230V AC380V
1 CQM5E-125 4 0.24 0.25 0.43 97.6 52.6 57.5 173.9
2 CQM5E-250 4 0.24 0.25 0.43 97.6 52.6 57.5 173.9
3 CQM5E-400 6.8 0.48 0.76 0.28 164.5 105 176.3 112
4 CQM5E-630 6.8 0.48 0.76 0.28 164.5 105 176.3 112
5 CQM5E-800 6.8 0.48 0.76 0.28 164.5 105 176.3 112

1.4UVR Under-Voltage Release

Wiring Diagram

Function

Protects equipment by tripping breakers during voltage dips.

Operational Thresholds

Reliable closing: ≥85% rated voltage

Mandatory tripping: 70%-35% rated voltage

Closing prevention:<35% rated voltage

Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W)
Pick-up Power (W) Hold-in Power (W)
DC24V DC220V AC230V AC380V AC230V AC380V
1 CQM5E-125 0.2 0.3 / / 0.5 0.5
2 CQM5E-250 0.006 0.01 / / 0.3 0.3
3 CQM5E-400 0.006 0.01 / / 0.8 0.9
4 CQM5E-630 0.8 0.5 190 223 0.8 0.9
5 CQM5E-800 0.8 0.5 190 223 0.8 0.9
Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W)
Pick-up Power (W) Hold-in Power (W)
DC24V DC220V AC230V AC380V AC230V AC380V
1 CQM5L-125 0.006 0.01 / / 0.3 0.3
2 CQM5L-250 0.006 0.01 / / 0.3 0.3
3 CQM5L-400 0.8 0.5 190 223 0.8 0.9
4 CQM5L-630 0.8 0.5 190 223 0.8 0.9
Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W)
Pick-up Power (W) Hold-in Power (W)
DC24V DC220V AC230V AC380V AC230V AC380V
1 CQM5E-125 0.006 0.01 / / 0.3 0.3
2 CQM5E-250 0.006 0.01 / / 0.3 0.3
3 CQM5E-400 0.8 0.5 190 223 0.8 0.9
4 CQM5E-630 0.8 0.5 190 223 0.8 0.9
5 CQM5E-800 0.8 0.5 190 223 0.8 0.9

External Accessories

2.1 Motor Operating Mechanism

Schematic Diagram

Function

Suitable for remotely closing, tripping (resetting) the circuit breaker,and for automated applications.

Position indication for O (OFF), I (ON), and TRIPPED.

Enables free trip operation of the circuit breaker.

Allows manual or automatic closing and opening of the circuit breaker.

Automatic closing or tripping can be achieved using momentary pulse signals or maintained signal control.

Reliable closing and tripping of the circuit breaker is ensured only when the control voltage is **≥85% and ≤ 110%** of the rated control

voltage (Un).

Dimensiones (mm)

Schematic & Symbol Legend:

SB1, SB2: Operation buttons(To be provided by customer)

X: Terminal block

P1、P2:External power supply

Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W) Operating Mechanism
Height
DC24V AC/DC110V AC/DC220V AC380V
1 CQM5-63/100 80 ≤180 ≤180 ≤350 20000 94
2 CQM5-125 80 ≤180 ≤180 ≤350 20000 97
3 CQM5-250 80 ≤180 ≤180 ≤350 20000 101
4 CQM5-400/630 160 ≤250 ≤350 ≤600 10000 149
5 CQM5-800 160 ≤250 ≤350 ≤600 10000 152
Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W) Operating Mechanism
Height
DC24V AC/DC110V AC/DC220V AC380V
1 CQM5L-125 80 ≤180 ≤180 ≤350 20000 97
2 CQM5L-250 80 ≤180 ≤180 ≤350 20000 101
3 CQM5L-400/630 160 ≤250 ≤350 ≤600 10000 149
4 CQM5L-800 160 ≤250 ≤350 ≤600 10000 152
Code Número de modelo Instantaneous Tripping Current (A) Power Consumption (W) Operating Mechanism
Height
DC24V AC/DC110V AC/DC220V AC380V
1 CQM5E-125 80 ≤180 ≤180 ≤350 20000 97
2 CQM5E-250 80 ≤180 ≤180 ≤350 20000 101
3 CQM5E-400 160 ≤250 ≤350 ≤600 10000 149
4 CQM5E-630 160 ≤250 ≤350 ≤600 10000 152
5 CQM5E-800 160 ≤250 ≤350 ≤600 10000 152

Note: General tolerance grade shall be in accordance withGB/T 1804-c.

2.2 Manual Handle Assembly

Function

Employs a unique design and transmission mechanism to perform circuit breaker Closing, Tripping (Reset), and Opening operations via handle rotation.

Features isolated position indication.

Clear position indications: O (OFF), I (ON), and TRIPPED

The breaker in the OFF position accepts 1-3 padlocks (Φ5-8mm), preverhting inadvertent closure and locking compartment access.

In the ON (closed) position, handle rotation mechanically prevents compartment door opening.(For emergency door access, use the handle’smanual override release).

Standard shaft length: 150mm.

Dimensiones (mm)

Code Número de modelo A B C D H
1 CQM5-63/100 25 111 55 8 40
2 CQM5-125 30 132 66 8 44
3 CQM5-250 35 126 63 8 44
4 CQM5-400/630 138 195 97.5 10 70
5 CQM5-800 198 243 121.5 10 76
Code Número de modelo A B C D H
1 CQM5L-125 30 132 66 8 44
2 CQM5L-250 35 126 63 8 44
3 CQM5L-400 138 195 97.5 10 70
4 CQM5L-630 198 243 121.5 10 76
Code Número de modelo A B C D H
1 CQM5E-125 30 132 66 8 44
2 CQM5E-250 35 126 63 8 44
3 CQM5E-400 138 195 97.5 10 70
4 CQM5E-630 198 243 121.5 10 76
5 CQM5E-800 198 243 121.5 10 76

Note: General tolerance grade shall be in accordance with GB/T1804-c.

The figure below shows the rotating handle and installation dimernsions of the manual operating mechanism.

Handle Length Dimensions in the Figure:

For models CQM5-125/250: 65 mm or 95 mm (optional), with 65 mm as the default.

For models CQM5-400/630/800: 95 mm.

For models CQM5E-125/250:65 mm or 95 mm (optional), with 65mm as the default.

For models CQM5E-400/630/800:95 mm.

For models CQM5L-125/250: 65 mm or 95 mm (optional), with 65 mm as the default.

For models CQM5L-400/630/800: 95 mm.

2.3 Fixed Type Rear-Mounting Kit

Dimensiones (mm)

CQM5 / CQM5E / CQM5L – 125/250

CQM5 / CQM5E / CQM5L – 400/630/800

Code Número de modelo A H H1 H2 D
1 CQM5-63/100 111 / 60.5 102.5 M8
2 CQM5-125 135 / 58 98 M8
3 CQM5-250 144 / 65 104 M8
4 CQM5-400/630 224 102 42 82 M12
5 CQM5-800 243 118 33 98 M16
Code Número de modelo A H H1 H2 D
1 CQM5L-125 135 / 58 98 M8
2 CQM5L-250 144 / 65 104 M8
3 CQM5L-400 224 102 42 82 M12
4 CQM5L-630 243 118 33 98 M16
Code Número de modelo A H H1 H2 D
1 CQM5E-125 135 / 58 98 M8
2 CQM5E-250 144 / 65 104 M8
3 CQM5E-400 224 102 42 82 M12
4 CQM5E-630 243 118 33 98 M16
5 CQM5E-800 243 118 33 98 M16

Note: General tolerance grade shall be in accordance with GB/T 1804-c.

2.4 Plug-in Type, Front-of-Panel

Dimensiones (mm)

CQM5 / CQM5E/CQM5L-125/250

CQM5 / CQM5E/CQM5L-400

Code Número de modelo A B L1 L2 D E H
1 CQM5-125 112 30 30 200 5.5 6.5 56
2 CQM5-250 150 35 35 223 5.5 8.5 73
Code Número de modelo A B L1 L2 D E H
1 CQM5E-125 112 30 30 200 5.5 6.5 56
2 CQM5E-250 150 35 35 223 5.5 8.5 73
Code Número de modelo A B L1 L2 D E H
1 CQM5L-125 112 30 30 200 5.5 6.5 56
2 CQM5L-250 150 35 35 223 5.5 8.5 73

Note: General tolerance grade shall be in accordance with GB/T 1804-c.

2.5 Plug-in Type, Rear-of-Panel

Dimensiones (mm)

CQM5 / CQM5E/CQM5L-125/250

CQM5 / CQM5E/CQM5L-400

CQM5 / CQM5E / CQM5L-630/800

Code Número de modelo A B L L1 L2 d C D E H1 H2
1 CQM5-125 67 60 90 51 94 6.5 162 90 30 20 56
2 CQM5-250 74 70 100 55 110 6.5 179 105 35 27 73
Code Número de modelo A B L L1 L2 d C D E H1 H2
1 CQM5E-125 67 60 90 51 94 6.5 162 90 30 20 56
2 CQM5E-250 74 70 100 55 110 6.5 179 105 35 27 73
Code Número de modelo A B L L1 L2 d C D E H1 H2
1 CQM5L-125 67 60 90 51 94 6.5 162 90 30 20 56
2 CQM5L-250 74 70 100 55 110 6.5 179 105 35 27 73

Note: General tolerance grade shall be in accordance with GB/T 1804-c.

2.6 Mechanical Interlock

Parámetro CQM5-125 CQM5-250 CQM5-400 CQM5-630/800
A (3P) 90 105 150 210
B (3P) 120 130 180 243
C(3P) 45 50 57 58
D (3P) 14 16.5 10 20
L (3P) 134 140.5 190 240
H (3P) 22 22 30 20
A (4P) 120 140 198 280
B (4P) 150 170 230 310
C (4P) 45 50 57 58
D (4P) 14 16.5 10 20
L (4P) 164 233 240 320
H (4P) 22 22 30 30
Parámetro CQM5E-125 CQM5E-250 CQM5E-400 CQM5E-630/800
A (3P) 90 105 150 210
B (3P) 120 130 180 243
C(3P) 45 50 57 58
D (3P) 14 16.5 10 20
L (3P) 134 140.5 190 240
H (3P) 22 22 30 20
A (4P) 120 140 198 280
B (4P) 150 170 230 310
C (4P) 45 50 57 58
D (4P) 14 16.5 10 20
L (4P) 164 233 240 320
H (4P) 22 22 30 30
Parámetro CQM5L-125 CQM5L-250 CQM5L-400 CQM5L-630/800
A (3P) 90 105 150 210
B (3P) 120 130 180 243
C(3P) 45 50 57 58
D (3P) 14 16.5 10 20
L (3P) 134 140.5 190 240
H (3P) 22 22 30 20
A (4P) 120 140 198 280
B (4P) 150 170 230 310
C (4P) 45 50 57 58
D (4P) 14 16.5 10 20
L (4P) 164 233 240 320
H (4P) 22 22 30 30

Notes: a. Units: mm  b. Undefined tolerances comply with GB/T 1804-2000 medium grade (m)

¿Por qué elegir CHAC?

Con más de 30 años de experiencia en fabricación, más de 1100 empleados, más de 100 millones de postes
Con una capacidad anual y un proceso de producción automatizado 90%, CHAC ofrece una capacidad de producción estable y un estricto
control de calidad para clientes OEM/ODM globales. Nuestro sistema de fabricación interno respalda a largo plazo
Cooperación para marcas eléctricas, importadores y distribuidores.


30+

AÑOS DE EXPERIENCIA

Especializado en fabricación eléctrica de bajo voltaje


1100+

EMPLEADOS

Equipo profesional garantiza calidad y entrega estables


100M+

CAPACIDAD ANUAL DE LOS POLOS

Capacidad de producción a gran escala para satisfacer la demanda mundial


90%

PRODUCCIÓN AUTOMATIZADA

Automatización avanzada para alta eficiencia y consistencia

Línea de ensamblaje automatizada

Línea de ensamblaje automatizada

Laboratorio de pruebas

Laboratorio de pruebas

Inyección y Estampado

Inyección y Estampado

Inspección de calidad

Inspección de calidad

Certificación IEC
Certificación CE
Certificación CB
Certificación RoHS
Certificación ISO 14001

Un estricto sistema de control de calidad garantiza que cada producto cumpla con los estándares mundiales.

¿Qué podemos personalizar?

Flexible customization services are available for enclosure dimensions, component configuration,
branding and project requirements.

Diseño de cerramiento

Recinto
Diseño

Tamaños, estructuras y detalles de instalación de recintos personalizados.

Diseño de cerramiento
Configuración interna

Interno
Configuración

Opciones flexibles de diseño interno y disposición de componentes.

Configuración interna
Marca y Logotipo

Marca e
Logo

Logotipos de marca propia, placas de identificación e identificación de marca.

Marca y Logotipo
Diseño de empaque

Empaquetado
Diseño

Soluciones de embalaje, cajas personalizadas, etiquetas y manuales.

Diseño de empaque
Configuración eléctrica

Eléctrico
Configuración

Instalación eléctrica adaptada a los requisitos de la aplicación.

Configuración eléctrica
Soporte de Certificación

Certificación
Apoyo

Soporte para estándares del mercado objetivo y requisitos de cumplimiento.

Soporte de Certificación

Descargar

PDF

Interruptor Automático de Caja Moldeada Serie CQM5

Descripción general completa de componentes eléctricos de bajo voltaje y referencia para la selección de productos.

Descargar PDF

Arriba

¿Necesita documentos técnicos?

Contáctenos para obtener hojas de datos, certificados, planos, orientación de selección o soporte para proyectos OEM/ODM.

Contáctanos

Preguntas frecuentes

¿Admite la personalización de productos según nuestros requisitos de diseño?

Absolutamente. Nos especializamos en cooperación OEM y ODM en el campo de la electricidad de bajo voltaje y hemos brindado servicios personalizados a muchas empresas de renombre internacional. Ofrecemos soporte de proceso completo, que incluye diseño de I+D, ajustes de parámetros y selección de materiales especiales, asegurando que el producto cumpla completamente con sus requisitos.

P2: ¿Cuál es tu capacidad de producción y Cantidad Mínima de Pedido (MOQ)?

A2: Operamos una base de producción altamente automatizada con una producción anual de más de 100 millones de polos para interruptores automáticos en miniatura. Nuestra política de MOQ es flexible. Podemos ofrecer pedidos de prueba competitivos para lotes pequeños y planes de garantía de capacidad de producción dedicada.

P3: ¿Qué garantías hay sobre la calidad del producto y las certificaciones?

Nuestros productos principales cuentan con las certificaciones CCC, CE, CB y más, y se venden en más de 30 países y regiones en todo el mundo. La empresa ha establecido un Centro de Operaciones de Calidad dedicado que trabaja con los departamentos de negocios y producción para implementar un control de calidad de proceso completo, garantizando que los productos cumplan con los estándares internacionales.

P4: ¿Tiene la capacidad para la I+D de productos y para convertir conceptos en realidad?

A4: Contamos con un equipo completo de I+D y talleres digitales, respaldados por una amplia experiencia en personalización al servicio de numerosos clientes internacionales. Desde la propuesta conceptual y el desarrollo de muestras hasta la producción en masa, ofrecemos soporte técnico integral para ayudar a dar vida a tus ideas.