CQM5E Series Electronic Molded Case Circuit Breaker
The CQM5E series electronic molded case circuit breaker is designed by CHAC Electric for use in AC 50Hz/60Hz systems with a rated voltage of up to AC 690V and a rated current of up to 800A.Additionally, it provides ground fault protection, further enhancing the safety and reliability of electrical systems.
Características del producto
■ Compact and modular design for quick installation and maintenance.
■ High breaking capacity (M-type: higher breaking, H-type: high brreaking)
■ Provides overload, short-circuit, and ground fault protection, with optional undervoltage protection.
■ Supports communication module integration for remote monitoring and control (remote trip, adjustment, testing, and signaling).
■ Suitable for both distribution network and motor protectionapplications.
■ Complies with IEC 60947-1, IEC 60947-2, and GB/T 14048 standards
Condiciones de Operación y Ambientales
■ Designed for vertical mounting (±5° tilt allowed unless specified)。
■ Suitable for infrequent circuit switching and motor starting operations
■ Pollution degree: 3
■ Communication module can be added for smart functionality.
Lista de accesorios


Dimensiones (mm)
CQM5E-125 (M, H Types)
Front Terminal Connection Dimensions
(X-X, Y-Y denote center points for 3P breakers)

CQM5E-250 (M, H Types)
Front Terminal Connection Dimensions
(X-X,Y-Y denote center points for 3P breakers)

CQM5E-400 (M, H Types)
Front Terminal Connection Dimensions
(X-X, Y-Y denote center points for 3P breakers)

CQM5E-630 (M, H Types)、CQM5E-800 (M, H Types)
Front Terminal Connection Dimensions
(X-X, Y-Y denote center points for 3P breakers)

Designación del tipo

| Code Position | Code Symbol | Meaning & Explanation |
| ① | CQ | Enterprise Code: Zhejiang Chuangqi Electric Co., LTD. |
| ② | M | Interruptor automático moldeado |
| ③ | 5 | Design Serial Number |
| ④ | E | Special Protection Function Residual Current Protection (Options: L=RC Protection) |
| ⑤ | 125 | Rated Frame Current (A): Options: 125, 250, 400, 630, 800 |
| ⑥ | M | Short-Circuit Breaking Capacity: • M: Higher Fault Capacity • H: High Fault Capacity |
| ⑦ | □ | Operation Mechanism [blank]: Manual | Z: Rotary Handle | P: Motorized |
| ⑧ | □ | Intelligence Function • [blank]: Basic Protection • G: Ground Fault Protection • T: Communication Capable • GT: Ground+Communication |
| ⑨ | 4 | Number of Poles:• 3 – Three Poles • 4 – Four Poles |
| ⑩ | 300 | Trip Unit & Accessories Code:• 3 – Electronic Trip (Compound Trip) • 00 – No Accessories (Refer to accessory table for specific codes) |
| ⑪ | □ | □: Application Profile [blank]: Distribution | 2: Motor Protection |
| ⑫ | B | N-Pole Type (For 4P products only): • Type A: N-pole is always connected, without overcurrent release. • Type B: N-pole breaks with other poles, without overcurrent release. • Type C: N-pole breaks with other poles, with overcurrent release. • Type D: N-pole is always connected, with overcurrent release. |
| ⑬ | □ | Special Function I: Overload Alarm (non-trip) |
| ⑭ | □ | Rated Current (A) Options: 32 | 63 | 125 | 250 | 400 | 630 | 800 |
| ⑮ | □ | Terminal & Connection Type: • (No Code) – Front Terminal Connection • B – Rear Terminal Connection • C – Plug-in Type |
Especificaciones técnicas
| Número de modelo | CQM5E-125 | CQM5E-250 | ||||||
| Rated current In(A), 40℃ | 32 | 63 | 125 | 250 | ||||
| Setting Current Ir (A), 40℃ | 16/20/25/32 | 32/40/50/63 | 63/80/100/125 | 100, 125, 140, 160, 180, 200,225, 250 | ||||
| Rated operating voltage Ue(V) | AC380/400/415V | AC380/400/415V | ||||||
| AC660/690V | AC660/690V | |||||||
| Rated insulation voltage Ui (V) | 1000 | 1000 | ||||||
| Rated impulse withstand voltage Uimp(KV) | 8 | 8 | ||||||
| Mechanical life | 20000 | 20000 | ||||||
| Electrical life(AC415V) | 8000 | 8000 | ||||||
| Trip mechanisms and protection types | Electronic | Electronic | ||||||
| Selectivity category | A | A | ||||||
| Número de polos | 3P | 4P | 3P | 4P | ||||
| Breaking capacity designation | M | H | / | M | H | / | ||
| Rated ultimate short-circuit breaking capacity (Icu) (kA) | AC380/400/415V | 70 | 85 | 70 | 70 | 85 | 70 | |
| AC660/690V | 20 | / | 20 | 20 | / | 20 | ||
| Rated service short-circuit breaking capacity (Ics) (kA) | AC380/400/415V | 50 | 65 | 50 | 50 | 65 | 50 | |
| AC660/690V | 10 | / | 10 | 10 | / | 10 | ||
| Phase spacing (mm) | 30 | 35 | ||||||
| Arc distance (mm) | ≤50 | ≤100 | ||||||
| Operating ambient temp | -35 ℃ to +70℃ | -35 ℃ to +70℃ | ||||||
| Rated short-time withstand current (Icw) | 1kA/1s | 2.5kA/1s | ||||||
| Accessory | Auxiliary contacts | ● | ● | ● | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ● | ● | ● | ||
| Shunt Release | ● | ● | ● | ● | ● | ● | ||
| Under-Voltage Release | ● | ● | ● | ● | ● | ● | ||
| Motor Operating Mechanism | ● | ● | ● | ● | ● | ● | ||
| Manual Handle Assembly | ● | ● | ● | ● | ● | ● | ||
| Fixed Type Rear-Mounting Kit | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Front-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Rear-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Mechanical Interlock | ● | ● | ● | ● | ● | ● | ||
| Short-circuit protection types | Short-time delay protection (S) | Isd= (2-12) Ir | Isd= (2-12) Ir | |||||
| Instantaneous protection (I) | Ii= (4-14) Ir | Ii= (4-14) Ir | ||||||
| Overall dimensions (mm) (L-W-H) |
![]() |
3 P | 155-90-90 | 165-105-103 | ||||
| 4 P | 155-120-90 | 165-140-103 | ||||||
Note: ● for optional accessories;”-” for no optional accessories.
| Número de modelo | CQM5E-400 | CQM5E-630 | ||||||
| Rated current In(A), 40℃ | 400 | 630 | ||||||
| Setting Current Ir (A), 40℃ | 200, 225, 250, 280, 315, 350, 400 | 400, 420, 440, 460, 480, 500, 530, 560, 600, 630 | ||||||
| Rated operating voltage Ue(V) | AC380/400/415V | AC380/400/415V | ||||||
| AC660/690V | AC660/690V | |||||||
| Rated insulation voltage Ui (V) | 1000 | 1000 | ||||||
| Tensión nominal de choque soportada Uimp (kV) | 8 | 8 | ||||||
| Mechanical life | 10000 | 10000 | ||||||
| Electrical life(AC415V) | 7000 | 7000 | ||||||
| Trip mechanisms and protection types | Electronic | Electronic | ||||||
| Selectivity category | B | B | ||||||
| Número de polos | 3P | 4P | 3P | 4P | ||||
| Breaking capacity designation | M | H | / | M | H | / | ||
| Rated ultimate short-circuit breaking capacity (Icu) (kA) | AC380/400/415V | 70 | 100 | 70 | 70 | 100 | 70 | |
| AC660/690V | 20 | / | 20 | 20 | / | 20 | ||
| Rated service short-circuit breaking capacity (Ics) (kA) | AC380/400/415V | 50 | 75 | 50 | 50 | 75 | 50 | |
| AC660/690V | 10 | / | 10 | 10 | / | 10 | ||
| Phase spacing (mm) | 48 | 70 | ||||||
| Arc distance (mm) | ≤100 | ≤100 | ||||||
| Operating ambient temp | -35℃ to +70℃ | -35℃ to +70℃ | ||||||
| Rated short-time withstand current (Icw) | 5kA/1s | 10kA/1s | ||||||
| Accessory | Auxiliary contacts | ● | ● | ● | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ● | ● | ● | ||
| Shunt Release | ● | ● | ● | ● | ● | ● | ||
| Under-Voltage Release | ● | ● | ● | ● | ● | ● | ||
| Motor Operating Mechanism | ● | ● | ● | ● | ● | ● | ||
| Manual Handle Assembly | ● | ● | ● | ● | ● | ● | ||
| Fixed Type Rear-Mounting Kit | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Front-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Rear-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Mechanical Interlock | ● | ● | ● | ● | ● | ● | ||
| Short-circuit protection types | Short-time delay protection (S) | Isd= (2-12) Ir | Isd= (2-12) Ir | |||||
| Instantaneous protection (I) | Ii= (4-14) Ir | Ii= (4-14) Ir | ||||||
| Overall dimensions (mm) (L-W-H) |
![]() |
3 P | 257-150-140.5 | 280-210-112 | ||||
| 4 P | 257-198-140.5 | 280-280-112 | ||||||
Note: ● for optional accessories;”-” for no optional accessories.
| Número de modelo | CQM5E-800 | ||||
| Rated current In(A), 40℃ | 800 | ||||
| Setting Current Ir (A), 40℃ | 630,640,660,680,700,720,740,760,780,800 | ||||
| Rated operating voltage Ue(V) | AC380/400/415V | ||||
| AC660/690V | |||||
| Rated insulation voltage Ui (V) | 1000 | ||||
| Tensión nominal de choque soportada Uimp (kV) | 8 | ||||
| Mechanical life | 10000 | ||||
| Electrical life(AC415V) | 7000 | ||||
| Trip mechanisms and protection types | Electronic | ||||
| Selectivity category | B | ||||
| Número de polos | 3P | 4P | |||
| Breaking capacity designation | M | H | / | ||
| Rated ultimate short-circuit breaking capacity (Icu) (kA) | AC380/400/415V | 70 | 100 | 70 | |
| AC660/690V | 20 | / | 20 | ||
| Rated service short-circuit breaking capacity (Ics) (kA) | AC380/400/415V | 50 | 75 | 50 | |
| AC660/690V | 10 | / | 10 | ||
| Phase spacing (mm) | 70 | ||||
| Arc distance (mm) | ≤100 | ||||
| Operating ambient temp | -35℃ to +70℃ | ||||
| Rated short-time withstand current (Icw) | 10kA/1s | ||||
| Accessory | Auxiliary contacts | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ||
| Shunt Release | ● | ● | ● | ||
| Under-Voltage Release | ● | ● | ● | ||
| Motor Operating Mechanism | ● | ● | ● | ||
| Manual Handle Assembly | ● | ● | ● | ||
| Fixed Type Rear-Mounting Kit | ● | ● | ● | ||
| Plug-in Type, Front-of-Panel | ● | ● | ● | ||
| Plug-in Type, Rear-of-Panel | ● | ● | ● | ||
| Mechanical Interlock | ● | ● | ● | ||
| Short-circuit protection types | Short-time delay protection (S) | Isd= (2-12) Ir | |||
| Instantaneous protection (I) | Ii= (4-14) Ir | ||||
| Overall dimensions (mm) (L-W-H) |
![]() |
3 P | 280-210-112 | ||
| 4 P | 280-280-112 | ||||
Note: ● for optional accessories;”-” for no optional accessories.
Internal Accessories
1.1 AX Auxiliary Contact

Function
Remote status indicator for breaker ON/OFF or trip-free operation, integrated into the auxiliary circuit.
Indicating Circuit Breaker ON/OFF Status
| When the circuit breaker is in the “OFF” and “TRIPPED”position | Dual auxiliary contact | ![]() |
| Single auxiliary contact. | ![]() |
|
| When the circuit breaker is in the “ON” position |
Dual auxiliary contact | ![]() |
| Single auxiliary contact | ![]() |
Electrical Characteristics
| Classification | Frame Rating | Conventional Thermal Current (A) | Rated Operational Current (A) | |
| Auxiliary Contact | 63,100,125,250 | 3 | AC400V | DC220V |
| 400,630,800 | 3 | 0.4 | 0.15 | |
1.2 AL Alarm Contact
Wiring Diagram

Function
Primarily used to provide a signal when a fault such as overloadd,short circuit,or undervoltage occurs on the circuit breaker’s loaad side,orwhenitentersafree-trip state.
Reasons for the alarm contact to issue a fault indication signal:
Overload or Short Circuit Trip
Undervoltage Trip
Residual Current Operation Trip
Manual Free-Trip
Indicating Circuit Breaker ON/OFF Status
| When the circuit breaker is in the “OFF” and “ON” position | ![]() |
| When the circuit breaker is in the “TRIPPED” position. | ![]() |
Electrical Characteristics
| Classification | Frame Rating | Conventional Thermal Current (A) | Rated Operational Current (A) | |
| Alarm Contact | 63,100,125,250 | 3 | AC400V | DC220V |
| 400,630,800 | 3 | 0.4 | 0.15 | |
1.3 SHT Shunt Release
Wiring Diagram

Function
The shunt release is activated by an electrical signal, enabling remote and automatic control of the circuit breaker. The shunt release shall reliably cause the circuit breaker to operate when the supply voltage is any value between 70% and 110% of the rated control supply voltage.
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | DC24V | DC220V | AC230V | AC380V | ||
| 1 | CQM5-63/100 | 5.7 | 0.62 | 0.64 | 0.38 | 136.8 | 136.4 | 147.2 | 152 |
| 2 | CQM5-125 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 3 | CQM5-250 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 4 | CQM5-400/630 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 5 | CQM5-800 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | DC24V | DC220V | AC230V | AC380V | ||
| 1 | CQM5L-125 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 2 | CQM5L-250 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 3 | CQM5L-400 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 4 | CQM5L-630 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | DC24V | DC220V | AC230V | AC380V | ||
| 1 | CQM5E-125 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 2 | CQM5E-250 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 3 | CQM5E-400 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 4 | CQM5E-630 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 5 | CQM5E-800 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
1.4UVR Under-Voltage Release
Wiring Diagram

Function
Protects equipment by tripping breakers during voltage dips.
Operational Thresholds
Reliable closing: ≥85% rated voltage
Mandatory tripping: 70%-35% rated voltage
Closing prevention:<35% rated voltage
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||
| Pick-up Power (W) | Hold-in Power (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | AC230V | AC380V | ||
| 1 | CQM5E-125 | 0.2 | 0.3 | / | / | 0.5 | 0.5 |
| 2 | CQM5E-250 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 3 | CQM5E-400 | 0.006 | 0.01 | / | / | 0.8 | 0.9 |
| 4 | CQM5E-630 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 5 | CQM5E-800 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||
| Pick-up Power (W) | Hold-in Power (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | AC230V | AC380V | ||
| 1 | CQM5L-125 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 2 | CQM5L-250 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 3 | CQM5L-400 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 4 | CQM5L-630 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||
| Pick-up Power (W) | Hold-in Power (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | AC230V | AC380V | ||
| 1 | CQM5E-125 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 2 | CQM5E-250 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 3 | CQM5E-400 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 4 | CQM5E-630 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 5 | CQM5E-800 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
External Accessories
2.1 Motor Operating Mechanism
Schematic Diagram

Function
Suitable for remotely closing, tripping (resetting) the circuit breaker,and for automated applications.
Position indication for O (OFF), I (ON), and TRIPPED.
Enables free trip operation of the circuit breaker.
Allows manual or automatic closing and opening of the circuit breaker.
Automatic closing or tripping can be achieved using momentary pulse signals or maintained signal control.
Reliable closing and tripping of the circuit breaker is ensured only when the control voltage is **≥85% and ≤ 110%** of the rated control
voltage (Un).
Dimensiones (mm)

Schematic & Symbol Legend:
SB1, SB2: Operation buttons(To be provided by customer)
X: Terminal block
P1、P2:External power supply
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | Operating Mechanism Height |
|||
| DC24V | AC/DC110V | AC/DC220V | AC380V | ||||
| 1 | CQM5-63/100 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 94 |
| 2 | CQM5-125 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 97 |
| 3 | CQM5-250 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 101 |
| 4 | CQM5-400/630 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 149 |
| 5 | CQM5-800 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | Operating Mechanism Height |
|||
| DC24V | AC/DC110V | AC/DC220V | AC380V | ||||
| 1 | CQM5L-125 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 97 |
| 2 | CQM5L-250 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 101 |
| 3 | CQM5L-400/630 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 149 |
| 4 | CQM5L-800 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
| Code | Número de modelo | Instantaneous Tripping Current (A) | Power Consumption (W) | Operating Mechanism Height |
|||
| DC24V | AC/DC110V | AC/DC220V | AC380V | ||||
| 1 | CQM5E-125 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 97 |
| 2 | CQM5E-250 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 101 |
| 3 | CQM5E-400 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 149 |
| 4 | CQM5E-630 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
| 5 | CQM5E-800 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
Note: General tolerance grade shall be in accordance withGB/T 1804-c.
2.2 Manual Handle Assembly
Function
Employs a unique design and transmission mechanism to perform circuit breaker Closing, Tripping (Reset), and Opening operations via handle rotation.
Features isolated position indication.
Clear position indications: O (OFF), I (ON), and TRIPPED
The breaker in the OFF position accepts 1-3 padlocks (Φ5-8mm), preverhting inadvertent closure and locking compartment access.
In the ON (closed) position, handle rotation mechanically prevents compartment door opening.(For emergency door access, use the handle’smanual override release).
Standard shaft length: 150mm.
Dimensiones (mm)

| Code | Número de modelo | A | B | C | D | H |
| 1 | CQM5-63/100 | 25 | 111 | 55 | 8 | 40 |
| 2 | CQM5-125 | 30 | 132 | 66 | 8 | 44 |
| 3 | CQM5-250 | 35 | 126 | 63 | 8 | 44 |
| 4 | CQM5-400/630 | 138 | 195 | 97.5 | 10 | 70 |
| 5 | CQM5-800 | 198 | 243 | 121.5 | 10 | 76 |
| Code | Número de modelo | A | B | C | D | H |
| 1 | CQM5L-125 | 30 | 132 | 66 | 8 | 44 |
| 2 | CQM5L-250 | 35 | 126 | 63 | 8 | 44 |
| 3 | CQM5L-400 | 138 | 195 | 97.5 | 10 | 70 |
| 4 | CQM5L-630 | 198 | 243 | 121.5 | 10 | 76 |
| Code | Número de modelo | A | B | C | D | H |
| 1 | CQM5E-125 | 30 | 132 | 66 | 8 | 44 |
| 2 | CQM5E-250 | 35 | 126 | 63 | 8 | 44 |
| 3 | CQM5E-400 | 138 | 195 | 97.5 | 10 | 70 |
| 4 | CQM5E-630 | 198 | 243 | 121.5 | 10 | 76 |
| 5 | CQM5E-800 | 198 | 243 | 121.5 | 10 | 76 |
Note: General tolerance grade shall be in accordance with GB/T1804-c.
The figure below shows the rotating handle and installation dimernsions of the manual operating mechanism.

Handle Length Dimensions in the Figure:
For models CQM5-125/250: 65 mm or 95 mm (optional), with 65 mm as the default.
For models CQM5-400/630/800: 95 mm.
For models CQM5E-125/250:65 mm or 95 mm (optional), with 65mm as the default.
For models CQM5E-400/630/800:95 mm.
For models CQM5L-125/250: 65 mm or 95 mm (optional), with 65 mm as the default.
For models CQM5L-400/630/800: 95 mm.
2.3 Fixed Type Rear-Mounting Kit
Dimensiones (mm)
CQM5 / CQM5E / CQM5L – 125/250

CQM5 / CQM5E / CQM5L – 400/630/800

| Code | Número de modelo | A | H | H1 | H2 | D |
| 1 | CQM5-63/100 | 111 | / | 60.5 | 102.5 | M8 |
| 2 | CQM5-125 | 135 | / | 58 | 98 | M8 |
| 3 | CQM5-250 | 144 | / | 65 | 104 | M8 |
| 4 | CQM5-400/630 | 224 | 102 | 42 | 82 | M12 |
| 5 | CQM5-800 | 243 | 118 | 33 | 98 | M16 |
| Code | Número de modelo | A | H | H1 | H2 | D |
| 1 | CQM5L-125 | 135 | / | 58 | 98 | M8 |
| 2 | CQM5L-250 | 144 | / | 65 | 104 | M8 |
| 3 | CQM5L-400 | 224 | 102 | 42 | 82 | M12 |
| 4 | CQM5L-630 | 243 | 118 | 33 | 98 | M16 |
| Code | Número de modelo | A | H | H1 | H2 | D |
| 1 | CQM5E-125 | 135 | / | 58 | 98 | M8 |
| 2 | CQM5E-250 | 144 | / | 65 | 104 | M8 |
| 3 | CQM5E-400 | 224 | 102 | 42 | 82 | M12 |
| 4 | CQM5E-630 | 243 | 118 | 33 | 98 | M16 |
| 5 | CQM5E-800 | 243 | 118 | 33 | 98 | M16 |
Note: General tolerance grade shall be in accordance with GB/T 1804-c.
2.4 Plug-in Type, Front-of-Panel
Dimensiones (mm)
CQM5 / CQM5E/CQM5L-125/250

CQM5 / CQM5E/CQM5L-400

| Code | Número de modelo | A | B | L1 | L2 | D | E | H |
| 1 | CQM5-125 | 112 | 30 | 30 | 200 | 5.5 | 6.5 | 56 |
| 2 | CQM5-250 | 150 | 35 | 35 | 223 | 5.5 | 8.5 | 73 |
| Code | Número de modelo | A | B | L1 | L2 | D | E | H |
| 1 | CQM5E-125 | 112 | 30 | 30 | 200 | 5.5 | 6.5 | 56 |
| 2 | CQM5E-250 | 150 | 35 | 35 | 223 | 5.5 | 8.5 | 73 |
| Code | Número de modelo | A | B | L1 | L2 | D | E | H |
| 1 | CQM5L-125 | 112 | 30 | 30 | 200 | 5.5 | 6.5 | 56 |
| 2 | CQM5L-250 | 150 | 35 | 35 | 223 | 5.5 | 8.5 | 73 |
Note: General tolerance grade shall be in accordance with GB/T 1804-c.
2.5 Plug-in Type, Rear-of-Panel
Dimensiones (mm)
CQM5 / CQM5E/CQM5L-125/250

CQM5 / CQM5E/CQM5L-400

CQM5 / CQM5E / CQM5L-630/800

| Code | Número de modelo | A | B | L | L1 | L2 | d | C | D | E | H1 | H2 |
| 1 | CQM5-125 | 67 | 60 | 90 | 51 | 94 | 6.5 | 162 | 90 | 30 | 20 | 56 |
| 2 | CQM5-250 | 74 | 70 | 100 | 55 | 110 | 6.5 | 179 | 105 | 35 | 27 | 73 |
| Code | Número de modelo | A | B | L | L1 | L2 | d | C | D | E | H1 | H2 |
| 1 | CQM5E-125 | 67 | 60 | 90 | 51 | 94 | 6.5 | 162 | 90 | 30 | 20 | 56 |
| 2 | CQM5E-250 | 74 | 70 | 100 | 55 | 110 | 6.5 | 179 | 105 | 35 | 27 | 73 |
| Code | Número de modelo | A | B | L | L1 | L2 | d | C | D | E | H1 | H2 |
| 1 | CQM5L-125 | 67 | 60 | 90 | 51 | 94 | 6.5 | 162 | 90 | 30 | 20 | 56 |
| 2 | CQM5L-250 | 74 | 70 | 100 | 55 | 110 | 6.5 | 179 | 105 | 35 | 27 | 73 |
Note: General tolerance grade shall be in accordance with GB/T 1804-c.
2.6 Mechanical Interlock

| Parámetro | CQM5-125 | CQM5-250 | CQM5-400 | CQM5-630/800 |
| A (3P) | 90 | 105 | 150 | 210 |
| B (3P) | 120 | 130 | 180 | 243 |
| C(3P) | 45 | 50 | 57 | 58 |
| D (3P) | 14 | 16.5 | 10 | 20 |
| L (3P) | 134 | 140.5 | 190 | 240 |
| H (3P) | 22 | 22 | 30 | 20 |
| A (4P) | 120 | 140 | 198 | 280 |
| B (4P) | 150 | 170 | 230 | 310 |
| C (4P) | 45 | 50 | 57 | 58 |
| D (4P) | 14 | 16.5 | 10 | 20 |
| L (4P) | 164 | 233 | 240 | 320 |
| H (4P) | 22 | 22 | 30 | 30 |
| Parámetro | CQM5E-125 | CQM5E-250 | CQM5E-400 | CQM5E-630/800 |
| A (3P) | 90 | 105 | 150 | 210 |
| B (3P) | 120 | 130 | 180 | 243 |
| C(3P) | 45 | 50 | 57 | 58 |
| D (3P) | 14 | 16.5 | 10 | 20 |
| L (3P) | 134 | 140.5 | 190 | 240 |
| H (3P) | 22 | 22 | 30 | 20 |
| A (4P) | 120 | 140 | 198 | 280 |
| B (4P) | 150 | 170 | 230 | 310 |
| C (4P) | 45 | 50 | 57 | 58 |
| D (4P) | 14 | 16.5 | 10 | 20 |
| L (4P) | 164 | 233 | 240 | 320 |
| H (4P) | 22 | 22 | 30 | 30 |
| Parámetro | CQM5L-125 | CQM5L-250 | CQM5L-400 | CQM5L-630/800 |
| A (3P) | 90 | 105 | 150 | 210 |
| B (3P) | 120 | 130 | 180 | 243 |
| C(3P) | 45 | 50 | 57 | 58 |
| D (3P) | 14 | 16.5 | 10 | 20 |
| L (3P) | 134 | 140.5 | 190 | 240 |
| H (3P) | 22 | 22 | 30 | 20 |
| A (4P) | 120 | 140 | 198 | 280 |
| B (4P) | 150 | 170 | 230 | 310 |
| C (4P) | 45 | 50 | 57 | 58 |
| D (4P) | 14 | 16.5 | 10 | 20 |
| L (4P) | 164 | 233 | 240 | 320 |
| H (4P) | 22 | 22 | 30 | 30 |
Notes: a. Units: mm b. Undefined tolerances comply with GB/T 1804-2000 medium grade (m)
¿Por qué elegir CHAC?
Con más de 30 años de experiencia en fabricación, más de 1100 empleados, más de 100 millones de postes
Con una capacidad anual y un proceso de producción automatizado 90%, CHAC ofrece una capacidad de producción estable y un estricto
control de calidad para clientes OEM/ODM globales. Nuestro sistema de fabricación interno respalda a largo plazo
Cooperación para marcas eléctricas, importadores y distribuidores.
30+
AÑOS DE EXPERIENCIA
Especializado en fabricación eléctrica de bajo voltaje
1100+
EMPLEADOS
Equipo profesional garantiza calidad y entrega estables
100M+
CAPACIDAD ANUAL DE LOS POLOS
Capacidad de producción a gran escala para satisfacer la demanda mundial
90%
PRODUCCIÓN AUTOMATIZADA
Automatización avanzada para alta eficiencia y consistencia

Línea de ensamblaje automatizada

Laboratorio de pruebas

Inyección y Estampado

Inspección de calidad





Un estricto sistema de control de calidad garantiza que cada producto cumpla con los estándares mundiales.
¿Qué podemos personalizar?
Flexible customization services are available for enclosure dimensions, component configuration,
branding and project requirements.
Recinto
Diseño
Tamaños, estructuras y detalles de instalación de recintos personalizados.

Interno
Configuración
Opciones flexibles de diseño interno y disposición de componentes.

Marca e
Logo
Logotipos de marca propia, placas de identificación e identificación de marca.

Empaquetado
Diseño
Soluciones de embalaje, cajas personalizadas, etiquetas y manuales.

Eléctrico
Configuración
Instalación eléctrica adaptada a los requisitos de la aplicación.

Certificación
Apoyo
Soporte para estándares del mercado objetivo y requisitos de cumplimiento.

Descargar
Interruptor Automático de Caja Moldeada Serie CQM5
Descripción general completa de componentes eléctricos de bajo voltaje y referencia para la selección de productos.
¿Necesita documentos técnicos?
Contáctenos para obtener hojas de datos, certificados, planos, orientación de selección o soporte para proyectos OEM/ODM.
Preguntas frecuentes
¿Admite la personalización de productos según nuestros requisitos de diseño?
Absolutamente. Nos especializamos en cooperación OEM y ODM en el campo de la electricidad de bajo voltaje y hemos brindado servicios personalizados a muchas empresas de renombre internacional. Ofrecemos soporte de proceso completo, que incluye diseño de I+D, ajustes de parámetros y selección de materiales especiales, asegurando que el producto cumpla completamente con sus requisitos.
P2: ¿Cuál es tu capacidad de producción y Cantidad Mínima de Pedido (MOQ)?
A2: Operamos una base de producción altamente automatizada con una producción anual de más de 100 millones de polos para interruptores automáticos en miniatura. Nuestra política de MOQ es flexible. Podemos ofrecer pedidos de prueba competitivos para lotes pequeños y planes de garantía de capacidad de producción dedicada.
P3: ¿Qué garantías hay sobre la calidad del producto y las certificaciones?
Nuestros productos principales cuentan con las certificaciones CCC, CE, CB y más, y se venden en más de 30 países y regiones en todo el mundo. La empresa ha establecido un Centro de Operaciones de Calidad dedicado que trabaja con los departamentos de negocios y producción para implementar un control de calidad de proceso completo, garantizando que los productos cumplan con los estándares internacionales.
P4: ¿Tiene la capacidad para la I+D de productos y para convertir conceptos en realidad?
A4: Contamos con un equipo completo de I+D y talleres digitales, respaldados por una amplia experiencia en personalización al servicio de numerosos clientes internacionales. Desde la propuesta conceptual y el desarrollo de muestras hasta la producción en masa, ofrecemos soporte técnico integral para ayudar a dar vida a tus ideas.