CQM5E Series Electronic Molded Case Circuit Breaker
The CQM5E series electronic molded case circuit breaker is designed by CHAC Electric for use in AC 50Hz/60Hz systems with a rated voltage of up to AC 690V and a rated current of up to 800A.Additionally, it provides ground fault protection, further enhancing the safety and reliability of electrical systems.
ميزات المنتج
■ Compact and modular design for quick installation and maintenance.
■ High breaking capacity (M-type: higher breaking, H-type: high brreaking)
■ Provides overload, short-circuit, and ground fault protection, with optional undervoltage protection.
■ Supports communication module integration for remote monitoring and control (remote trip, adjustment, testing, and signaling).
■ Suitable for both distribution network and motor protectionapplications.
■ Complies with IEC 60947-1, IEC 60947-2, and GB/T 14048 standards
ظروف التشغيل والبيئة
■ Designed for vertical mounting (±5° tilt allowed unless specified)。
■ Suitable for infrequent circuit switching and motor starting operations
■ Pollution degree: 3
■ Communication module can be added for smart functionality.
Accessory List


الأبعاد (مم)
CQM5E-125 (M, H Types)
Front Terminal Connection Dimensions
(X-X, Y-Y denote center points for 3P breakers)

CQM5E-250 (M, H Types)
Front Terminal Connection Dimensions
(X-X,Y-Y denote center points for 3P breakers)

CQM5E-400 (M, H Types)
Front Terminal Connection Dimensions
(X-X, Y-Y denote center points for 3P breakers)

CQM5E-630 (M, H Types)、CQM5E-800 (M, H Types)
Front Terminal Connection Dimensions
(X-X, Y-Y denote center points for 3P breakers)

تعيين النوع

| Code Position | Code Symbol | Meaning & Explanation |
| ① | CQ | Enterprise Code: Zhejiang Chuangqi Electric Co., LTD. |
| ② | M | قاطع دائرة مصبوب |
| ③ | 5 | Design Serial Number |
| ④ | E | Special Protection Function Residual Current Protection (Options: L=RC Protection) |
| ⑤ | 125 | Rated Frame Current (A): Options: 125, 250, 400, 630, 800 |
| ⑥ | M | Short-Circuit Breaking Capacity: • M: Higher Fault Capacity • H: High Fault Capacity |
| ⑦ | □ | Operation Mechanism [blank]: Manual | Z: Rotary Handle | P: Motorized |
| ⑧ | □ | Intelligence Function • [blank]: Basic Protection • G: Ground Fault Protection • T: Communication Capable • GT: Ground+Communication |
| ⑨ | 4 | Number of Poles:• 3 – Three Poles • 4 – Four Poles |
| ⑩ | 300 | Trip Unit & Accessories Code:• 3 – Electronic Trip (Compound Trip) • 00 – No Accessories (Refer to accessory table for specific codes) |
| ⑪ | □ | □: Application Profile [blank]: Distribution | 2: Motor Protection |
| ⑫ | B | N-Pole Type (For 4P products only): • Type A: N-pole is always connected, without overcurrent release. • Type B: N-pole breaks with other poles, without overcurrent release. • Type C: N-pole breaks with other poles, with overcurrent release. • Type D: N-pole is always connected, with overcurrent release. |
| ⑬ | □ | Special Function I: Overload Alarm (non-trip) |
| ⑭ | □ | Rated Current (A) Options: 32 | 63 | 125 | 250 | 400 | 630 | 800 |
| ⑮ | □ | Terminal & Connection Type: • (No Code) – Front Terminal Connection • B – Rear Terminal Connection • C – Plug-in Type |
المواصفات الفنية
| Model number | CQM5E-125 | CQM5E-250 | ||||||
| Rated current In(A), 40℃ | 32 | 63 | 125 | 250 | ||||
| Setting Current Ir (A), 40℃ | 16/20/25/32 | 32/40/50/63 | 63/80/100/125 | 100, 125, 140, 160, 180, 200,225, 250 | ||||
| Rated operating voltage Ue(V) | AC380/400/415V | AC380/400/415V | ||||||
| AC660/690V | AC660/690V | |||||||
| Rated insulation voltage Ui (V) | 1000 | 1000 | ||||||
| Rated impulse withstand voltage Uimp(KV) | 8 | 8 | ||||||
| Mechanical life | 20000 | 20000 | ||||||
| Electrical life(AC415V) | 8000 | 8000 | ||||||
| Trip mechanisms and protection types | Electronic | Electronic | ||||||
| Selectivity category | A | A | ||||||
| Number of poles | 3P | 4P | 3P | 4P | ||||
| Breaking capacity designation | M | H | / | M | H | / | ||
| Rated ultimate short-circuit breaking capacity (Icu) (kA) | AC380/400/415V | 70 | 85 | 70 | 70 | 85 | 70 | |
| AC660/690V | 20 | / | 20 | 20 | / | 20 | ||
| Rated service short-circuit breaking capacity (Ics) (kA) | AC380/400/415V | 50 | 65 | 50 | 50 | 65 | 50 | |
| AC660/690V | 10 | / | 10 | 10 | / | 10 | ||
| Phase spacing (mm) | 30 | 35 | ||||||
| Arc distance (mm) | ≤50 | ≤100 | ||||||
| Operating ambient temp | -35 ℃ to +70℃ | -35 ℃ to +70℃ | ||||||
| Rated short-time withstand current (Icw) | 1kA/1s | 2.5kA/1s | ||||||
| Accessory | Auxiliary contacts | ● | ● | ● | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ● | ● | ● | ||
| Shunt Release | ● | ● | ● | ● | ● | ● | ||
| Under-Voltage Release | ● | ● | ● | ● | ● | ● | ||
| Motor Operating Mechanism | ● | ● | ● | ● | ● | ● | ||
| Manual Handle Assembly | ● | ● | ● | ● | ● | ● | ||
| Fixed Type Rear-Mounting Kit | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Front-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Rear-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Mechanical Interlock | ● | ● | ● | ● | ● | ● | ||
| Short-circuit protection types | Short-time delay protection (S) | Isd= (2-12) Ir | Isd= (2-12) Ir | |||||
| Instantaneous protection (I) | Ii= (4-14) Ir | Ii= (4-14) Ir | ||||||
| Overall dimensions (mm) (L-W-H) |
![]() |
3 P | 155-90-90 | 165-105-103 | ||||
| 4 P | 155-120-90 | 165-140-103 | ||||||
Note: ● for optional accessories;”-” for no optional accessories.
| Model number | CQM5E-400 | CQM5E-630 | ||||||
| Rated current In(A), 40℃ | 400 | 630 | ||||||
| Setting Current Ir (A), 40℃ | 200, 225, 250, 280, 315, 350, 400 | 400, 420, 440, 460, 480, 500, 530, 560, 600, 630 | ||||||
| Rated operating voltage Ue(V) | AC380/400/415V | AC380/400/415V | ||||||
| AC660/690V | AC660/690V | |||||||
| Rated insulation voltage Ui (V) | 1000 | 1000 | ||||||
| Rated impulse withstand voltage Uimp(kV) | 8 | 8 | ||||||
| Mechanical life | 10000 | 10000 | ||||||
| Electrical life(AC415V) | 7000 | 7000 | ||||||
| Trip mechanisms and protection types | Electronic | Electronic | ||||||
| Selectivity category | B | B | ||||||
| Number of poles | 3P | 4P | 3P | 4P | ||||
| Breaking capacity designation | M | H | / | M | H | / | ||
| Rated ultimate short-circuit breaking capacity (Icu) (kA) | AC380/400/415V | 70 | 100 | 70 | 70 | 100 | 70 | |
| AC660/690V | 20 | / | 20 | 20 | / | 20 | ||
| Rated service short-circuit breaking capacity (Ics) (kA) | AC380/400/415V | 50 | 75 | 50 | 50 | 75 | 50 | |
| AC660/690V | 10 | / | 10 | 10 | / | 10 | ||
| Phase spacing (mm) | 48 | 70 | ||||||
| Arc distance (mm) | ≤100 | ≤100 | ||||||
| Operating ambient temp | -35℃ to +70℃ | -35℃ to +70℃ | ||||||
| Rated short-time withstand current (Icw) | 5kA/1s | 10kA/1s | ||||||
| Accessory | Auxiliary contacts | ● | ● | ● | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ● | ● | ● | ||
| Shunt Release | ● | ● | ● | ● | ● | ● | ||
| Under-Voltage Release | ● | ● | ● | ● | ● | ● | ||
| Motor Operating Mechanism | ● | ● | ● | ● | ● | ● | ||
| Manual Handle Assembly | ● | ● | ● | ● | ● | ● | ||
| Fixed Type Rear-Mounting Kit | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Front-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Plug-in Type, Rear-of-Panel | ● | ● | ● | ● | ● | ● | ||
| Mechanical Interlock | ● | ● | ● | ● | ● | ● | ||
| Short-circuit protection types | Short-time delay protection (S) | Isd= (2-12) Ir | Isd= (2-12) Ir | |||||
| Instantaneous protection (I) | Ii= (4-14) Ir | Ii= (4-14) Ir | ||||||
| Overall dimensions (mm) (L-W-H) |
![]() |
3 P | 257-150-140.5 | 280-210-112 | ||||
| 4 P | 257-198-140.5 | 280-280-112 | ||||||
Note: ● for optional accessories;”-” for no optional accessories.
| Model number | CQM5E-800 | ||||
| Rated current In(A), 40℃ | 800 | ||||
| Setting Current Ir (A), 40℃ | 630,640,660,680,700,720,740,760,780,800 | ||||
| Rated operating voltage Ue(V) | AC380/400/415V | ||||
| AC660/690V | |||||
| Rated insulation voltage Ui (V) | 1000 | ||||
| Rated impulse withstand voltage Uimp(kV) | 8 | ||||
| Mechanical life | 10000 | ||||
| Electrical life(AC415V) | 7000 | ||||
| Trip mechanisms and protection types | Electronic | ||||
| Selectivity category | B | ||||
| Number of poles | 3P | 4P | |||
| Breaking capacity designation | M | H | / | ||
| Rated ultimate short-circuit breaking capacity (Icu) (kA) | AC380/400/415V | 70 | 100 | 70 | |
| AC660/690V | 20 | / | 20 | ||
| Rated service short-circuit breaking capacity (Ics) (kA) | AC380/400/415V | 50 | 75 | 50 | |
| AC660/690V | 10 | / | 10 | ||
| Phase spacing (mm) | 70 | ||||
| Arc distance (mm) | ≤100 | ||||
| Operating ambient temp | -35℃ to +70℃ | ||||
| Rated short-time withstand current (Icw) | 10kA/1s | ||||
| Accessory | Auxiliary contacts | ● | ● | ● | |
| Alarm contacts | ● | ● | ● | ||
| Shunt Release | ● | ● | ● | ||
| Under-Voltage Release | ● | ● | ● | ||
| Motor Operating Mechanism | ● | ● | ● | ||
| Manual Handle Assembly | ● | ● | ● | ||
| Fixed Type Rear-Mounting Kit | ● | ● | ● | ||
| Plug-in Type, Front-of-Panel | ● | ● | ● | ||
| Plug-in Type, Rear-of-Panel | ● | ● | ● | ||
| Mechanical Interlock | ● | ● | ● | ||
| Short-circuit protection types | Short-time delay protection (S) | Isd= (2-12) Ir | |||
| Instantaneous protection (I) | Ii= (4-14) Ir | ||||
| Overall dimensions (mm) (L-W-H) |
![]() |
3 P | 280-210-112 | ||
| 4 P | 280-280-112 | ||||
Note: ● for optional accessories;”-” for no optional accessories.
Internal Accessories
1.1 AX Auxiliary Contact

Function
Remote status indicator for breaker ON/OFF or trip-free operation, integrated into the auxiliary circuit.
Indicating Circuit Breaker ON/OFF Status
| When the circuit breaker is in the “OFF” and “TRIPPED”position | Dual auxiliary contact | ![]() |
| Single auxiliary contact. | ![]() |
|
| When the circuit breaker is in the “ON” position |
Dual auxiliary contact | ![]() |
| Single auxiliary contact | ![]() |
Electrical Characteristics
| Classification | Frame Rating | Conventional Thermal Current (A) | Rated Operational Current (A) | |
| Auxiliary Contact | 63,100,125,250 | 3 | AC400V | DC220V |
| 400,630,800 | 3 | 0.4 | 0.15 | |
1.2 AL Alarm Contact
Wiring Diagram

Function
Primarily used to provide a signal when a fault such as overloadd,short circuit,or undervoltage occurs on the circuit breaker’s loaad side,orwhenitentersafree-trip state.
Reasons for the alarm contact to issue a fault indication signal:
Overload or Short Circuit Trip
Undervoltage Trip
Residual Current Operation Trip
Manual Free-Trip
Indicating Circuit Breaker ON/OFF Status
| When the circuit breaker is in the “OFF” and “ON” position | ![]() |
| When the circuit breaker is in the “TRIPPED” position. | ![]() |
Electrical Characteristics
| Classification | Frame Rating | Conventional Thermal Current (A) | Rated Operational Current (A) | |
| Alarm Contact | 63,100,125,250 | 3 | AC400V | DC220V |
| 400,630,800 | 3 | 0.4 | 0.15 | |
1.3 SHT Shunt Release
Wiring Diagram

Function
The shunt release is activated by an electrical signal, enabling remote and automatic control of the circuit breaker. The shunt release shall reliably cause the circuit breaker to operate when the supply voltage is any value between 70% and 110% of the rated control supply voltage.
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | DC24V | DC220V | AC230V | AC380V | ||
| 1 | CQM5-63/100 | 5.7 | 0.62 | 0.64 | 0.38 | 136.8 | 136.4 | 147.2 | 152 |
| 2 | CQM5-125 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 3 | CQM5-250 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 4 | CQM5-400/630 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 5 | CQM5-800 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | DC24V | DC220V | AC230V | AC380V | ||
| 1 | CQM5L-125 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 2 | CQM5L-250 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 3 | CQM5L-400 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 4 | CQM5L-630 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | DC24V | DC220V | AC230V | AC380V | ||
| 1 | CQM5E-125 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 2 | CQM5E-250 | 4 | 0.24 | 0.25 | 0.43 | 97.6 | 52.6 | 57.5 | 173.9 |
| 3 | CQM5E-400 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 4 | CQM5E-630 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
| 5 | CQM5E-800 | 6.8 | 0.48 | 0.76 | 0.28 | 164.5 | 105 | 176.3 | 112 |
1.4UVR Under-Voltage Release
Wiring Diagram

Function
Protects equipment by tripping breakers during voltage dips.
Operational Thresholds
Reliable closing: ≥85% rated voltage
Mandatory tripping: 70%-35% rated voltage
Closing prevention:<35% rated voltage
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||
| Pick-up Power (W) | Hold-in Power (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | AC230V | AC380V | ||
| 1 | CQM5E-125 | 0.2 | 0.3 | / | / | 0.5 | 0.5 |
| 2 | CQM5E-250 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 3 | CQM5E-400 | 0.006 | 0.01 | / | / | 0.8 | 0.9 |
| 4 | CQM5E-630 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 5 | CQM5E-800 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||
| Pick-up Power (W) | Hold-in Power (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | AC230V | AC380V | ||
| 1 | CQM5L-125 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 2 | CQM5L-250 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 3 | CQM5L-400 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 4 | CQM5L-630 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | ||||
| Pick-up Power (W) | Hold-in Power (W) | ||||||
| DC24V | DC220V | AC230V | AC380V | AC230V | AC380V | ||
| 1 | CQM5E-125 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 2 | CQM5E-250 | 0.006 | 0.01 | / | / | 0.3 | 0.3 |
| 3 | CQM5E-400 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 4 | CQM5E-630 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
| 5 | CQM5E-800 | 0.8 | 0.5 | 190 | 223 | 0.8 | 0.9 |
External Accessories
2.1 Motor Operating Mechanism
Schematic Diagram

Function
Suitable for remotely closing, tripping (resetting) the circuit breaker,and for automated applications.
Position indication for O (OFF), I (ON), and TRIPPED.
Enables free trip operation of the circuit breaker.
Allows manual or automatic closing and opening of the circuit breaker.
Automatic closing or tripping can be achieved using momentary pulse signals or maintained signal control.
Reliable closing and tripping of the circuit breaker is ensured only when the control voltage is **≥85% and ≤ 110%** of the rated control
voltage (Un).
الأبعاد (مم)

Schematic & Symbol Legend:
SB1, SB2: Operation buttons(To be provided by customer)
X: Terminal block
P1、P2:External power supply
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | Operating Mechanism Height |
|||
| DC24V | AC/DC110V | AC/DC220V | AC380V | ||||
| 1 | CQM5-63/100 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 94 |
| 2 | CQM5-125 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 97 |
| 3 | CQM5-250 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 101 |
| 4 | CQM5-400/630 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 149 |
| 5 | CQM5-800 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | Operating Mechanism Height |
|||
| DC24V | AC/DC110V | AC/DC220V | AC380V | ||||
| 1 | CQM5L-125 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 97 |
| 2 | CQM5L-250 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 101 |
| 3 | CQM5L-400/630 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 149 |
| 4 | CQM5L-800 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
| Code | Model number | Instantaneous Tripping Current (A) | Power Consumption (W) | Operating Mechanism Height |
|||
| DC24V | AC/DC110V | AC/DC220V | AC380V | ||||
| 1 | CQM5E-125 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 97 |
| 2 | CQM5E-250 | 80 | ≤180 | ≤180 | ≤350 | 20000 | 101 |
| 3 | CQM5E-400 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 149 |
| 4 | CQM5E-630 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
| 5 | CQM5E-800 | 160 | ≤250 | ≤350 | ≤600 | 10000 | 152 |
Note: General tolerance grade shall be in accordance withGB/T 1804-c.
2.2 Manual Handle Assembly
Function
Employs a unique design and transmission mechanism to perform circuit breaker Closing, Tripping (Reset), and Opening operations via handle rotation.
Features isolated position indication.
Clear position indications: O (OFF), I (ON), and TRIPPED
The breaker in the OFF position accepts 1-3 padlocks (Φ5-8mm), preverhting inadvertent closure and locking compartment access.
In the ON (closed) position, handle rotation mechanically prevents compartment door opening.(For emergency door access, use the handle’smanual override release).
Standard shaft length: 150mm.
الأبعاد (مم)

| Code | Model number | A | B | C | D | H |
| 1 | CQM5-63/100 | 25 | 111 | 55 | 8 | 40 |
| 2 | CQM5-125 | 30 | 132 | 66 | 8 | 44 |
| 3 | CQM5-250 | 35 | 126 | 63 | 8 | 44 |
| 4 | CQM5-400/630 | 138 | 195 | 97.5 | 10 | 70 |
| 5 | CQM5-800 | 198 | 243 | 121.5 | 10 | 76 |
| Code | Model number | A | B | C | D | H |
| 1 | CQM5L-125 | 30 | 132 | 66 | 8 | 44 |
| 2 | CQM5L-250 | 35 | 126 | 63 | 8 | 44 |
| 3 | CQM5L-400 | 138 | 195 | 97.5 | 10 | 70 |
| 4 | CQM5L-630 | 198 | 243 | 121.5 | 10 | 76 |
| Code | Model number | A | B | C | D | H |
| 1 | CQM5E-125 | 30 | 132 | 66 | 8 | 44 |
| 2 | CQM5E-250 | 35 | 126 | 63 | 8 | 44 |
| 3 | CQM5E-400 | 138 | 195 | 97.5 | 10 | 70 |
| 4 | CQM5E-630 | 198 | 243 | 121.5 | 10 | 76 |
| 5 | CQM5E-800 | 198 | 243 | 121.5 | 10 | 76 |
Note: General tolerance grade shall be in accordance with GB/T1804-c.
The figure below shows the rotating handle and installation dimernsions of the manual operating mechanism.

Handle Length Dimensions in the Figure:
For models CQM5-125/250: 65 mm or 95 mm (optional), with 65 mm as the default.
For models CQM5-400/630/800: 95 mm.
For models CQM5E-125/250:65 mm or 95 mm (optional), with 65mm as the default.
For models CQM5E-400/630/800:95 mm.
For models CQM5L-125/250: 65 mm or 95 mm (optional), with 65 mm as the default.
For models CQM5L-400/630/800: 95 mm.
2.3 Fixed Type Rear-Mounting Kit
الأبعاد (مم)
CQM5 / CQM5E / CQM5L – 125/250

CQM5 / CQM5E / CQM5L – 400/630/800

| Code | Model number | A | H | H1 | H2 | D |
| 1 | CQM5-63/100 | 111 | / | 60.5 | 102.5 | M8 |
| 2 | CQM5-125 | 135 | / | 58 | 98 | M8 |
| 3 | CQM5-250 | 144 | / | 65 | 104 | M8 |
| 4 | CQM5-400/630 | 224 | 102 | 42 | 82 | M12 |
| 5 | CQM5-800 | 243 | 118 | 33 | 98 | M16 |
| Code | Model number | A | H | H1 | H2 | D |
| 1 | CQM5L-125 | 135 | / | 58 | 98 | M8 |
| 2 | CQM5L-250 | 144 | / | 65 | 104 | M8 |
| 3 | CQM5L-400 | 224 | 102 | 42 | 82 | M12 |
| 4 | CQM5L-630 | 243 | 118 | 33 | 98 | M16 |
| Code | Model number | A | H | H1 | H2 | D |
| 1 | CQM5E-125 | 135 | / | 58 | 98 | M8 |
| 2 | CQM5E-250 | 144 | / | 65 | 104 | M8 |
| 3 | CQM5E-400 | 224 | 102 | 42 | 82 | M12 |
| 4 | CQM5E-630 | 243 | 118 | 33 | 98 | M16 |
| 5 | CQM5E-800 | 243 | 118 | 33 | 98 | M16 |
Note: General tolerance grade shall be in accordance with GB/T 1804-c.
2.4 Plug-in Type, Front-of-Panel
الأبعاد (مم)
CQM5 / CQM5E/CQM5L-125/250

CQM5 / CQM5E/CQM5L-400

| Code | Model number | A | B | L1 | L2 | D | E | H |
| 1 | CQM5-125 | 112 | 30 | 30 | 200 | 5.5 | 6.5 | 56 |
| 2 | CQM5-250 | 150 | 35 | 35 | 223 | 5.5 | 8.5 | 73 |
| Code | Model number | A | B | L1 | L2 | D | E | H |
| 1 | CQM5E-125 | 112 | 30 | 30 | 200 | 5.5 | 6.5 | 56 |
| 2 | CQM5E-250 | 150 | 35 | 35 | 223 | 5.5 | 8.5 | 73 |
| Code | Model number | A | B | L1 | L2 | D | E | H |
| 1 | CQM5L-125 | 112 | 30 | 30 | 200 | 5.5 | 6.5 | 56 |
| 2 | CQM5L-250 | 150 | 35 | 35 | 223 | 5.5 | 8.5 | 73 |
Note: General tolerance grade shall be in accordance with GB/T 1804-c.
2.5 Plug-in Type, Rear-of-Panel
الأبعاد (مم)
CQM5 / CQM5E/CQM5L-125/250

CQM5 / CQM5E/CQM5L-400

CQM5 / CQM5E / CQM5L-630/800

| Code | Model number | A | B | L | L1 | L2 | d | C | D | E | H1 | H2 |
| 1 | CQM5-125 | 67 | 60 | 90 | 51 | 94 | 6.5 | 162 | 90 | 30 | 20 | 56 |
| 2 | CQM5-250 | 74 | 70 | 100 | 55 | 110 | 6.5 | 179 | 105 | 35 | 27 | 73 |
| Code | Model number | A | B | L | L1 | L2 | d | C | D | E | H1 | H2 |
| 1 | CQM5E-125 | 67 | 60 | 90 | 51 | 94 | 6.5 | 162 | 90 | 30 | 20 | 56 |
| 2 | CQM5E-250 | 74 | 70 | 100 | 55 | 110 | 6.5 | 179 | 105 | 35 | 27 | 73 |
| Code | Model number | A | B | L | L1 | L2 | d | C | D | E | H1 | H2 |
| 1 | CQM5L-125 | 67 | 60 | 90 | 51 | 94 | 6.5 | 162 | 90 | 30 | 20 | 56 |
| 2 | CQM5L-250 | 74 | 70 | 100 | 55 | 110 | 6.5 | 179 | 105 | 35 | 27 | 73 |
Note: General tolerance grade shall be in accordance with GB/T 1804-c.
2.6 Mechanical Interlock

| معامل | CQM5-125 | CQM5-250 | CQM5-400 | CQM5-630/800 |
| A (3P) | 90 | 105 | 150 | 210 |
| B (3P) | 120 | 130 | 180 | 243 |
| C(3P) | 45 | 50 | 57 | 58 |
| D (3P) | 14 | 16.5 | 10 | 20 |
| L (3P) | 134 | 140.5 | 190 | 240 |
| H (3P) | 22 | 22 | 30 | 20 |
| A (4P) | 120 | 140 | 198 | 280 |
| B (4P) | 150 | 170 | 230 | 310 |
| C (4P) | 45 | 50 | 57 | 58 |
| D (4P) | 14 | 16.5 | 10 | 20 |
| L (4P) | 164 | 233 | 240 | 320 |
| H (4P) | 22 | 22 | 30 | 30 |
| معامل | CQM5E-125 | CQM5E-250 | CQM5E-400 | CQM5E-630/800 |
| A (3P) | 90 | 105 | 150 | 210 |
| B (3P) | 120 | 130 | 180 | 243 |
| C(3P) | 45 | 50 | 57 | 58 |
| D (3P) | 14 | 16.5 | 10 | 20 |
| L (3P) | 134 | 140.5 | 190 | 240 |
| H (3P) | 22 | 22 | 30 | 20 |
| A (4P) | 120 | 140 | 198 | 280 |
| B (4P) | 150 | 170 | 230 | 310 |
| C (4P) | 45 | 50 | 57 | 58 |
| D (4P) | 14 | 16.5 | 10 | 20 |
| L (4P) | 164 | 233 | 240 | 320 |
| H (4P) | 22 | 22 | 30 | 30 |
| معامل | CQM5L-125 | CQM5L-250 | CQM5L-400 | CQM5L-630/800 |
| A (3P) | 90 | 105 | 150 | 210 |
| B (3P) | 120 | 130 | 180 | 243 |
| C(3P) | 45 | 50 | 57 | 58 |
| D (3P) | 14 | 16.5 | 10 | 20 |
| L (3P) | 134 | 140.5 | 190 | 240 |
| H (3P) | 22 | 22 | 30 | 20 |
| A (4P) | 120 | 140 | 198 | 280 |
| B (4P) | 150 | 170 | 230 | 310 |
| C (4P) | 45 | 50 | 57 | 58 |
| D (4P) | 14 | 16.5 | 10 | 20 |
| L (4P) | 164 | 233 | 240 | 320 |
| H (4P) | 22 | 22 | 30 | 30 |
Notes: a. Units: mm b. Undefined tolerances comply with GB/T 1804-2000 medium grade (m)
لماذا تختار CHAC
مع خبرة تصنيع تزيد عن 30 عامًا، وأكثر من 1100 موظف، وأكثر من 100 مليون عمود
بفضل طاقتها الإنتاجية السنوية ونظام الإنتاج الآلي 90%، توفر شركة CHAC طاقة إنتاجية مستقرة ومعايير صارمة
مراقبة الجودة لعملاء OEM/ODM العالميين. يدعم نظام التصنيع الداخلي الخاص بنا على المدى الطويل
تعاون مع العلامات التجارية الكهربائية والمستوردين والموزعين.
30+
سنوات الخبرة
متخصص في تصنيع المعدات الكهربائية منخفضة الجهد
1100+
الموظفين
فريق محترف يضمن جودة ثابتة والتسليم
١٠٠ مليون+
السعة السنوية للأعمدة
قدرة إنتاجية واسعة النطاق لتلبية الطلب العالمي
90%
الإنتاج الآلي
الأتمتة المتقدمة لتحقيق كفاءة واتساق عاليين

خط التجميع الآلي

مختبر اختبار

حقن وختم

فحص الجودة





نظام صارم لمراقبة الجودة يضمن أن كل منتج يلبي المعايير العالمية.
ما الذي يمكننا تخصيصه؟
Flexible customization services are available for enclosure dimensions, component configuration,
branding and project requirements.
حَظِيرة
تصميم
أحجام وحاويات مخصصة وهياكل وتفاصيل تركيب.

داخلي
إعدادات
خيارات مرنة لتخطيط داخلي وترتيب المكونات.

العلامة التجارية و
شعار
شعارات العلامة التجارية الخاصة، ولوحات الأسماء، وتحديد الهوية التجارية.

تعبئة وتغليف
تصميم
علب مخصصة، وملصقات، وأدلة، وحلول تغليف.

كهربائي
إعدادات
إعداد كهربائي مخصص بناءً على متطلبات التطبيق.

شهادة
دعم
دعم معايير السوق المستهدفة ومتطلبات الامتثال.

تنزيل
قواطع الدائرة المقولبة من سلسلة CQM5
نظرة عامة كاملة على مكونات كهربائية منخفضة الجهد ومرجع لاختيار المنتج.
هل تحتاج إلى وثائق فنية؟
اتصل بنا للحصول على أوراق البيانات، والشهادات، والرسومات، وإرشادات الاختيار، أو دعم مشاريع OEM/ODM.
أسئلة متكررة
س1. هل تدعمون تخصيص المنتجات بناءً على متطلبات التصميم الخاصة بنا؟
أ1: بالتأكيد. نحن متخصصون في التعاون في مجالات تصنيع المعدات الأصلية (OEM) وتصنيع التصميم الأصلي (ODM) في مجال الأجهزة الكهربائية منخفضة الجهد، وقد قدمنا خدمات مخصصة للعديد من الشركات العالمية الشهيرة. نقدم دعمًا لكامل العملية، بما في ذلك تصميم البحث والتطوير، وتعديل المعلمات، واختيار المواد الخاصة، مما يضمن تلبية المنتج لمتطلباتك بالكامل.
س2: ما هي طاقتك الإنتاجية والحد الأدنى لكمية الطلب؟
A2: نحن ندير قاعدة إنتاج مؤتمتة للغاية بإنتاج سنوي يزيد عن 100 مليون عمود للقواطع الكهربائية المصغرة. سياسة الحد الأدنى لكمية الطلب لدينا مرنة. يمكننا توفير طلبات تجريبية تنافسية للكميات الصغيرة وخطط ضمان مخصصة للسعة الإنتاجية.
س 3: ما هي الضمانات المقدمة لجودة المنتج والشهادات؟
ج 3: منتجاتنا الرئيسية حاصلة على شهادات CCC و CE و CB وغيرها، وتُباع في أكثر من 30 دولة ومنطقة حول العالم. وقد أنشأت الشركة «مركز عمليات الجودة» مخصصًا يعمل بالتعاون مع أقسام الأعمال والإنتاج لتطبيق مراقبة الجودة على جميع مراحل العملية، مما يضمن توافق المنتجات مع المعايير الدولية.
س4: هل لديكم القدرة على البحث والتطوير للمنتجات وتحويل الأفكار إلى واقع؟
لدينا فريق بحث وتطوير كامل وورش عمل رقمية، مدعومة بخبرة تخصيص واسعة تخدم العديد من العملاء الدوليين. من اقتراح المفهوم وتطوير العينات إلى الإنتاج الضخم، نقدم دعمًا فنيًا شاملاً لمساعدتك في تحقيق أفكارك.