PXB6Ln-40 Electronic Residual Current Operated Circuit-Breaker with Overcurrent Protection

Product Features

■ Enhanced Safety Design: Compact enclosure with a 1P+N configuration and simultaneous disconnection for improved maintenance safety.

■ Dual Electrical Protection: Integrated overload and short-circuit protection provides reliable basic protection for distribution circuits.

■ Safe Isolation: Reliable electrical isolation with a clearly indicated open position ensures complete circuit isolation for safe maintenance.

■ Wide Application Range: Suitable for circuit protection in industrial, commercial, high-rise residential, and household electrical systems.

Ordering Specification

Please specify the following when ordering:

1.Product Model: PXB6Ln-40

2.Number of Poles: 1P+N,

3.Rated Current & Tripping Curve: e.g., C/25A

  • Tripping Curve (Type): B, C
  • Rated Current (In): 6A, 10A, 16A, 20A, 25A, 32A,40A

4.Residual Current Operation:

  • Residual Current Type: AC, A
  • Rated Residual Operating Current (IΔn): 10mA, 30mA,100mA,

Quantity: e.g., 100 pcs

5.Ordering Example:

PXB6Ln-40 1P+N C/25A 30mA AC 100 pcs

Caractéristiques techniques

Paramètre
Rated Voltage 230/240V
Rated Insulation Voltage(Ui) 400V
Rated Impulse Withstand Voltage (Uimp) 4000V
Rated Current (In) 6、10、16、20、25、32、40
Rated Residual Operating Current(IΔn) 10、30、100mA
Residual Current Trip Type AC type、A type
Rated Frequency 50/60Hz
Number of Poles 1P+N
Rated Short-Circuit Breaking Capacity (Icn = Ics) 6000A
Mechanical Endurance ≥10000
Electrical Endurance ≥4000
Instantaneous Tripping Type B、C
Grid Spacing 50mm
Degree of Protection IP 20
Standards Compliance IEC61009-1, GB/T 16917.1
Certification CE CB CCC |DEKRA Certified

Tripping Characteristics (Reference Temperature: 30℃)

Article Curve de Triche Test Current (A) État initial Temps de déclenchement ou non-déclenchement Résultat attendu Commentaires
a B、C 1.13Dans Froid t≤1h Non-chocant La tension actuelle augmente régulièrement jusqu'à atteindre la valeur spécifiée en 5 secondes.
b B、C 1.45In Suite à l'essai a) t<1h Desperance
c B、C 2,55 en Froid 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
Desperance
d B 3 En Froid t≤0.1s Non-chocant Allumez l’alimentation en éteignant le commutateur auxiliaire.
C 5En
e B 5En Froid t<0.1s Desperance Allumez l’alimentation en éteignant le commutateur auxiliaire.
C 10Dans

Note: The :erm “cold” means that the test is carried out at at a reference calibration temperature without load before the test.

Règles relatives aux conducteurs et section de la conduite

Section de cuivre (mm²) Courant nominal (A)
1 En ≤6
1.5 6<In≤13
2.5 13<In≤20
4 20<In≤25
6 25<In≤32
10 32<In≤40