Calcolatore per la selezione degli avviatori di motori — Avvio diretto alla linea

Stima la corrente del motore DOL trifase e la corrente di avviamento, quindi confronta i contattori CHAC CQC6 e gli intervalli dei relè di sovraccarico CQR2 elencati.

CQC6 contactor and CQR2 overload relay reference

Current adjustment ranges and plug-in contactors from the CHAC CQR2 product table. Each listed range is shown separately; the model names and range notation retain the source wording.

Reference data. Calculate to highlight the matching row.

CQR2-25

Plug-in contactors listed by CHAC:

Scroll horizontally on small screens to read all columns.

CQR2-25 current adjustment ranges
Intervallo di regolazione corrente RC(A)Calculator reference
0.1~0.16Listed adjustment range
0.16~0.25Listed adjustment range
0.25~0.40Listed adjustment range
0.40~0.63Listed adjustment range
0.63~1Listed adjustment range
1~1.6Listed adjustment range
1.6~2.5Listed adjustment range
2.5~4Listed adjustment range
4~6Listed adjustment range
5.5-8Listed adjustment range
7~10Listed adjustment range
9~13Listed adjustment range
12~18Listed adjustment range
17-25Listed adjustment range

CQR2-38

Plug-in contactors listed by CHAC:

Scroll horizontally on small screens to read all columns.

CQR2-38 current adjustment ranges
Intervallo di regolazione corrente RC(A)Calculator reference
23-32Listed adjustment range
30~38Listed adjustment range

CQR2-95

Plug-in contactors listed by CHAC:

Scroll horizontally on small screens to read all columns.

CQR2-95 current adjustment ranges
Intervallo di regolazione corrente RC(A)Calculator reference
17~25Listed adjustment range
23~32Listed adjustment range
30~40Listed adjustment range
37~50Listed adjustment range
48~65Listed adjustment range
55~70Listed adjustment range
63~85Listed adjustment range
80~95Listed adjustment range

Reading this reference

  • Plug-in compatibility and adjustment-range coverage do not establish a tested Type 1 or Type 2 short-circuit coordinated starter.
  • The source lists CQR2-38 with CQC6(SM/KMNC1)-32. This reference does not add CQC6-38 to that pairing.
  • Use the original product page for the separately listed protection data, relay characteristics and installation requirements.

Source: CHAC CQR2 adjustment-range and plug-in table (aprirà in una nuova scheda) · CHAC CQC6 AC-3 ratings

Source checked: . This is the retrieval date, not a standard edition or product revision date.

Esempio di applicazione · Contributi illustrativi

Pairing a pump contactor with a listed overload-relay range

For a 15 kW, 400 V DOL pump example with a 28 A motor-current input, the calculator shortlists CQC6-32 and a CQR2-38 relay range of 23–32 A. These come from CHAC’s published current, motor-power and plug-in pairing tables. An assumed six-times starting multiple gives 168 A, but does not establish starting duration or a breaker trip response. The proposed 28 A overload setting must be reviewed against the actual motor and relay instructions. Complete the selection with the exact protection and coordination data rather than presenting the table pairing as a tested starter combination.

Dati del prodotto: CQC6 Serie Contatto Industriale AC, Prodotto per l'OEM · Relè di sovraccarico termico della serie CQR2