Kalkulator Pemilihan Starter Motor — DOL

Perkirakan arus motor DOL tiga fase dan arus starting, lalu bandingkan kontaktor CHAC CQC6 dengan rentang relay beban lebih CQR2 yang terdaftar.

CQC6 contactor and CQR2 overload relay reference

Current adjustment ranges and plug-in contactors from the CHAC CQR2 product table. Each listed range is shown separately; the model names and range notation retain the source wording.

Reference data. Calculate to highlight the matching row.

CQR2-25

Plug-in contactors listed by CHAC:

Scroll horizontally on small screens to read all columns.

CQR2-25 current adjustment ranges
Current adjustment range RC(A)Calculator reference
0.1~0.16Listed adjustment range
0.16~0.25Listed adjustment range
0.25~0.40Listed adjustment range
0.40~0.63Listed adjustment range
0.63~1Listed adjustment range
1~1.6Listed adjustment range
1.6~2.5Listed adjustment range
2.5~4Listed adjustment range
4~6Listed adjustment range
5.5-8Listed adjustment range
7~10Listed adjustment range
9~13Listed adjustment range
12~18Listed adjustment range
17-25Listed adjustment range

CQR2-38

Plug-in contactors listed by CHAC:

Scroll horizontally on small screens to read all columns.

CQR2-38 current adjustment ranges
Current adjustment range RC(A)Calculator reference
23-32Listed adjustment range
30~38Listed adjustment range

CQR2-95

Plug-in contactors listed by CHAC:

Scroll horizontally on small screens to read all columns.

CQR2-95 current adjustment ranges
Current adjustment range RC(A)Calculator reference
17~25Listed adjustment range
23~32Listed adjustment range
30~40Listed adjustment range
37~50Listed adjustment range
48~65Listed adjustment range
55~70Listed adjustment range
63~85Listed adjustment range
80~95Listed adjustment range

Reading this reference

  • Plug-in compatibility and adjustment-range coverage do not establish a tested Type 1 or Type 2 short-circuit coordinated starter.
  • The source lists CQR2-38 with CQC6(SM/KMNC1)-32. This reference does not add CQC6-38 to that pairing.
  • Use the original product page for the separately listed protection data, relay characteristics and installation requirements.

Source: CHAC CQR2 adjustment-range and plug-in table (buka di tab baru) · CHAC CQC6 AC-3 ratings

Source checked: . This is the retrieval date, not a standard edition or product revision date.

Contoh aplikasi · Masukan ilustratif

Pairing a pump contactor with a listed overload-relay range

For a 15 kW, 400 V DOL pump example with a 28 A motor-current input, the calculator shortlists CQC6-32 and a CQR2-38 relay range of 23–32 A. These come from CHAC’s published current, motor-power and plug-in pairing tables. An assumed six-times starting multiple gives 168 A, but does not establish starting duration or a breaker trip response. The proposed 28 A overload setting must be reviewed against the actual motor and relay instructions. Complete the selection with the exact protection and coordination data rather than presenting the table pairing as a tested starter combination.

Data produk: Produsen Kontaktor AC Industri Seri CQC6 OEM · Relai beban berlebih Thermal CQR2 Series