Калькулятор выбора пускателя двигателя — прямой пуск
Оцените ток трёхфазного двигателя при прямом пуске и пусковой ток, затем сравните контакторы CHAC CQC6 и диапазоны перегрузочных реле CQR2 из списка.
Создайте эталонный трёхфазный пускатель прямого включения, используя данные CQC6 и AC-3, а также опубликованные диапазоны подключаемых реле CQR2.
Результат
Справочник по пускателям DOL
CQC6-25Entered numeric checks met; verify complete installationCQC6-25 with CQR2-25 (17–25 A) is the first listed pairing covering the current, motor power and proposed relay setting.
I = Pshaft × 1,000 / (√3 × V × PF × η); Istart = I × start multiple; relay range must contain proposed settingCurrent and kW table matching plus a listed plug-in relay range do not establish Type 1/Type 2 coordination. Check starting duration, trip class, breaker curve, coil voltage, control circuit and the exact tested combination.
Почему этот результат?
At 400 V: contactor Ie ≥ 20.75 A (the greater of motor current and proposed setting); motor rating ≥ 11 kW; relay range must contain 20.75 A.
Выбранный эталон и прилегающие перечисленные варианты. Значения округлены для отображения; при проверке используются неокруглённые значения.
| Контактёр | AC-3 current / motor output | Listed overload relay | Причина |
|---|---|---|---|
| CQC6-18 | 18.00 A / 7.5 kW | CQR2-25 · 17–25 A | AC-3 ток ниже требуемого; номинальная мощность двигателя ниже требуемого |
| CQC6-25Выбранная ссылка | 25.00 A / 11 kW | CQR2-25 · 17–25 A | Первый указанный матч для этих проверок |
| CQC6-32 | 32.00 A / 15 kW | CQR2-38 · no range contains 20.75 A | No listed relay range contains the setting |
Просмотреть все проверенные варианты 12
| Контактёр | AC-3 current / motor output | Listed overload relay | Причина |
|---|---|---|---|
| CQC6-6 | 6.00 A / 2.2 kW | No listed plug-in pairing | AC-3 current below requirement; Motor-power rating below requirement; Plug-in compatibility not listed |
| CQC6-9 | 9.00 A / 4 kW | CQR2-25 · 17–25 A | AC-3 ток ниже требуемого; номинальная мощность двигателя ниже требуемого |
| CQC6-12 | 12.00 A / 5.5 kW | CQR2-25 · 17–25 A | AC-3 ток ниже требуемого; номинальная мощность двигателя ниже требуемого |
| CQC6-18 | 18.00 A / 7.5 kW | CQR2-25 · 17–25 A | AC-3 ток ниже требуемого; номинальная мощность двигателя ниже требуемого |
| CQC6-25Выбранная ссылка | 25.00 A / 11 kW | CQR2-25 · 17–25 A | Первый указанный матч для этих проверок |
| CQC6-32 | 32.00 A / 15 kW | CQR2-38 · no range contains 20.75 A | No listed relay range contains the setting |
| CQC6-38 | 38.00 A / 18.5 kW | No listed plug-in pairing | Plug-in compatibility not listed |
| CQC6-40 | 40.00 A / 18.5 kW | CQR2-95 · 17–25 A | Чеки проверены; позже указан вариант |
| CQC6-50 | 50.00 A / 22 kW | CQR2-95 · 17–25 A | Чеки проверены; позже указан вариант |
| CQC6-65 | 65.00 A / 30 kW | CQR2-95 · 17–25 A | Чеки проверены; позже указан вариант |
| CQC6-80 | 80.00 A / 37 kW | CQR2-95 · 17–25 A | Чеки проверены; позже указан вариант |
| CQC6-95 | 95.00 A / 45 kW | CQR2-95 · 17–25 A | Чеки проверены; позже указан вариант |
Entered condition checks
| Проверьте | Требование | Entered value | Status |
|---|---|---|---|
| Motor current and protective device | Breaker In ≥ 20.75 A | 32.00 A | Введённый чек соответствует |
| Кабельный трафик | Corrected Iz ≥ 32.00 A | 40.00 A | Введённый чек соответствует |
| Short-circuit capability | Declared capability ≥ 6.00 kA | 10.00 kA | Введённый чек соответствует |
Ещё предстоит подтвердить
- The pairing is based on listed plug-in compatibility and adjustment range; Type 1/Type 2 coordination is not verified.
- Confirm starting duration, trip class, breaker curve, coil supply and the actual control circuit.
Data source: CHAC CQC6 AC-3 rating table (открывается в новой вкладке) · CHAC CQR2 listed plug-in ranges (открывается в новой вкладке)
Формула и метод
Оцените ток трёхфазного двигателя при прямом пуске и пусковой ток, затем сравните контакторы CHAC CQC6 и диапазоны перегрузочных реле CQR2 из списка.
Как использовать этот калькулятор
- Enter motor shaft output, line voltage, efficiency and power factor; actual nameplate current overrides the estimate.
- Enter a justified start-current multiple and proposed overload setting factor.
- Review the CQC6 and CQR2 references with the exact wiring, trip class and manufacturer coordination data.
Границы расчёта
Direct-on-line three-phase motors only. Does not design star-delta, reversing, soft-starter or VFD arrangements. Plug-in compatibility is not proof of a tested short-circuit coordination combination.
DOL motor starter sizing and thermal overload relay selection
A DOL starter combines switching, overload protection and short-circuit protection. This tool uses CQC6 AC-3 columns for the contactor reference and the CQR2 table for a listed plug-in relay range that contains the proposed overload setting.
Ввод записей
| Ввод | Что нужно проверить |
|---|---|
| Моторный ток | При наличии — используйте фактический номинальный ток с таблички двигателя. В противном случае инструмент оценивает ток на основе мощности вала (кВт), КПД, коэффициента мощности и линейного напряжения. |
| Начало работы и настройка | Коэффициент пускового тока и коэффициент настройки по перегрузке являются входными параметрами проекта. Они не заменяют проверки продолжительности пуска и класса срабатывания. |
| Защита и диапазон реле | Инструмент проверяет введённые значения предельных токов автоматических выключателей, кабелей и токов короткого замыкания, а также указанный диапазон параметров подключаемых реле. Это не является доказательством испытанной согласованной комбинации. |
Пример работы · начальные значения форм
11 кВт, 400 В, ссылка на пускатель прямого включения
ПФ 0.85 · КПД 90% · запуск нескольких 6 · коэффициент перегрузки 1.00
Ток двигателя = 20.75 А; предполагаемый пусковой ток = 20.7549 × 6 = 124.53 А.
CQC6-25 соприкасается с нагруженными колоннами 400 V AC-3. У CQR2-25 есть перечисленный диапазон 17–25 A, содержащий 20.75 A.
CQC6-25
Это справочное руководство по контакторам и реле. Предложенная уставка, время срабатывания, класс защиты от перегрузки и проверенная комбинация устройств защиты от короткого замыкания ещё требуют подтверждения.
DOL starter sizing starts with motor full-load current
A direct-on-line starter applies the line supply to the motor through a contactor. Use motor nameplate current for component checks whenever it is available. The power-based estimate is useful for preliminary work when shaft kW, efficiency, power factor and line voltage are known.
Starting current is a separate quantity. Here it is estimated as running current multiplied by your entered starting-current multiple. For the default 11 kW example, 20.75 A running current and a multiple of six give about 124.53 A during starting; the actual motor and driven load determine the starting profile.
Motor starter components: contactor, overload relay and fault protection
The contactor switches the motor. The thermal overload relay responds to sustained overload according to its setting and trip characteristic. A suitable short-circuit protective device handles the fault-protection duty. These functions need to work together in an electric motor starter.
The tool compares CQC6 AC-3 current and motor-kW ratings, then looks for an explicitly listed CQR2 plug-in relay range containing the proposed setting. Plug-in compatibility establishes a component pairing; it does not establish a tested Type 1 or Type 2 coordinated starter.
Thermal overload relay setting and starting time
Choose a relay range that contains the required setting, then confirm the setting against motor data and the relay instructions. In the default example, the proposed 20.75 A setting falls within the listed CQR2-25 range of 17–25 A paired with CQC6-25.
A relay can have a suitable adjustment range yet be unsuitable for a long acceleration time. Check trip class, hot and cold starting conditions, starts per hour and the driven load. A motor protection circuit breaker is another protection option, but its use still requires the applicable contactor and coordination data.
Compatibility and coordination are different checks
- The CQR2 source identifies plug-in contactor families. Mechanical plug-in compatibility is not evidence of Type 1 or Type 2 short-circuit coordination.
- An overload relay does not replace the necessary short-circuit protective device. A breaker that carries running current can still be unsuitable for starting duty or fault protection.
Часто задаваемые вопросы
Can this select a star-delta starter?
No. The topology and relay location change the component-current relationships. This version is limited to a three-phase DOL arrangement.
Is the calculated overload setting mandatory?
No. The setting factor is an entered proposal. Final settings must follow motor data, relay instructions, start conditions and applicable rules.
Why might there be no complete match?
The motor/current combination can exceed the loaded CQC6 columns, or the proposed setting may not fit a listed CQR2 range for that contactor.
Does the result prove Type 2 coordination?
No. It does not check a tested manufacturer combination or its stated prospective-fault limit. Obtain the applicable coordination data.
What is the difference between a motor starter and a contactor?
Контактор обеспечивает коммутацию. Пускатель двигателя сочетает коммутацию с необходимыми функциями защиты двигателя. В данном примере прямого пуска при помощи устройства DOL инструмент анализирует контактор и реле тепловой защиты, при этом по‑прежнему требуются отдельные проверки на соответствие требованиям защиты от короткого замыкания и координации.
Можно ли выбирать тепловое реле только по его максимальному номинальному току?
Нет. Диапазон регулировки должен включать требуемое значение, а класс срабатывания — соответствовать условиям пуска. Кроме того, убедитесь в совместимости с контактором и соблюдении инструкций производителя.
Необходима помощь при выборе продукта CHAC?
При отправке запроса укажите напряжение системы, ток нагрузки и условия установки.
Контактор CQC6 и реле перегрузки CQR2 — ссылка
Текущие диапазоны регулировки и вставные контакторы из таблицы продукции CHAC CQR2. Каждый указанный диапазон представлен отдельно; названия моделей и обозначения диапазонов сохраняют исходную формулировку.
Справочные данные. Вычислите, чтобы выделить соответствующую строку.
CQR2-25
Plug-in contactors listed by CHAC:
Scroll horizontally on small screens to read all columns.
| Текущий диапазон корректировки RC(A) | Calculator reference |
|---|---|
| 0.1~0.16 | Listed adjustment rangeCurrent calculated range |
| 0.16~0.25 | Listed adjustment rangeCurrent calculated range |
| 0.25~0.40 | Listed adjustment rangeCurrent calculated range |
| 0.40~0.63 | Listed adjustment rangeCurrent calculated range |
| 0.63~1 | Listed adjustment rangeCurrent calculated range |
| 1~1.6 | Listed adjustment rangeCurrent calculated range |
| 1.6~2.5 | Listed adjustment rangeCurrent calculated range |
| 2.5~4 | Listed adjustment rangeCurrent calculated range |
| 4~6 | Listed adjustment rangeCurrent calculated range |
| 5.5-8 | Listed adjustment rangeCurrent calculated range |
| 7~10 | Listed adjustment rangeCurrent calculated range |
| 9~13 | Listed adjustment rangeCurrent calculated range |
| 12~18 | Listed adjustment rangeCurrent calculated range |
| 17-25 | Listed adjustment rangeCurrent calculated range |
CQR2-38
Plug-in contactors listed by CHAC:
Scroll horizontally on small screens to read all columns.
| Текущий диапазон корректировки RC(A) | Calculator reference |
|---|---|
| 23-32 | Listed adjustment rangeCurrent calculated range |
| 30~38 | Listed adjustment rangeCurrent calculated range |
CQR2-95
Plug-in contactors listed by CHAC:
Scroll horizontally on small screens to read all columns.
| Текущий диапазон корректировки RC(A) | Calculator reference |
|---|---|
| 17~25 | Listed adjustment rangeCurrent calculated range |
| 23~32 | Listed adjustment rangeCurrent calculated range |
| 30~40 | Listed adjustment rangeCurrent calculated range |
| 37~50 | Listed adjustment rangeCurrent calculated range |
| 48~65 | Listed adjustment rangeCurrent calculated range |
| 55~70 | Listed adjustment rangeCurrent calculated range |
| 63~85 | Listed adjustment rangeCurrent calculated range |
| 80~95 | Listed adjustment rangeCurrent calculated range |
Reading this reference
- Plug-in compatibility and adjustment-range coverage do not establish a tested Type 1 or Type 2 short-circuit coordinated starter.
- The source lists CQR2-38 with CQC6(SM/KMNC1)-32. This reference does not add CQC6-38 to that pairing.
- Use the original product page for the separately listed protection data, relay characteristics and installation requirements.
Source: CHAC CQR2 adjustment-range and plug-in table (открывается в новой вкладке) · CHAC CQC6 AC-3 ratings
Source checked: . This is the retrieval date, not a standard edition or product revision date.
Пример применения · Иллюстративные материалы
Pairing a pump contactor with a listed overload-relay range
For a 15 kW, 400 V DOL pump example with a 28 A motor-current input, the calculator shortlists CQC6-32 and a CQR2-38 relay range of 23–32 A. These come from CHAC’s published current, motor-power and plug-in pairing tables. An assumed six-times starting multiple gives 168 A, but does not establish starting duration or a breaker trip response. The proposed 28 A overload setting must be reviewed against the actual motor and relay instructions. Complete the selection with the exact protection and coordination data rather than presenting the table pairing as a tested starter combination.
Данные о продукте: Производитель промышленного контактора с переменным током серии CQC6 · Термореле серии CQR2