Kalkulator średnicy przewodu — miedź/PVC

Rozmiar kabli miedzianych/PVC w mm² z uwzględnieniem skorygowanej przenoszenia prądu i spadku napięcia rezystancyjnego. Obejmuje trzy obciążone przewody metodami A1, A2, B1, B2 oraz C.

Copper/PVC cable current-carrying capacity

Base ampacity values from Electrical Installation Guide, Figure G20. This is an external installation reference, not a CHAC cable product rating.

Reference data. Calculate to highlight the matching row.

Scroll horizontally on small screens to read all columns.

Copper/PVC base ampacity — three loaded conductors
Conductor area (mm²)A1 (A)A2 (A)B1 (A)B2 (A)C (A)
1.513.51315.51517.5
2.51817.5212024
42423282732
63129363441
104239504657
165652686276
257368898096
35898311099119
5010899134118144
70136125171149184
95164150207179223
120188172239206259
150216196262225299
185245223296255341
240286261346297403
300328298394339464
A1
Insulated conductors in conduit in a thermally insulated wall.
A2
Multicore cable in conduit in a thermally insulated wall.
B1
Insulated conductors in conduit on a wall.
B2
Multicore cable in conduit on a wall.
C
Cable clipped direct or on an unperforated tray, within the source method conditions.

Reading this reference

  • Copper conductors, PVC insulation, three loaded conductors, 70°C conductor limit and 30°C ambient air. Only methods A1, A2, B1, B2 and C are reproduced.
  • The numbers in this reference table remain the base values. The calculator applies temperature and other entered correction factors separately.
  • Do not apply these values to aluminium, XLPE, DC circuits, two loaded conductors, buried cables or parallel conductors. Verify the complete installation conditions in the source.

Source: Electrical Installation Guide — Figure G20 and installation methods (otwiera się w nowej karcie)

Source checked: . This is the retrieval date, not a standard edition or product revision date.

Przykład zastosowania · Wykresowe dane wejściowe

Checking a warm equipment feeder for ampacity and drop

For a 40 A load and 40 A protective-device reference, consider an 80 m, 400 V three-phase copper/PVC route using method B2, 40°C ambient and an entered grouping factor of 0.80. The calculator returns 16 mm²: its 62 A base capacity becomes 43.15 A after correction, and the resistive voltage drop is 1.81%, below the example’s 3% target. The cable values are installation-reference data, not CHAC cable ratings. When reviewing PXB6-63 or CQM6 protection, also check the actual route, fault withstand and trip behavior; passing voltage drop alone does not establish cable suitability.

Dane produktu: PXB6-63 Zmniejszona moc rozruchowa · CQM6 Standardowy złącze obrotowe w obudowie (MCCB) Producent OEM