CQM7 Thermal-Magnetic MCCB Manufacturer with OEM Branding Options
O Disjuntor térmico-magnético de moldagem da série CQM7 provides overload and short-circuit protection for low-voltage AC distribution systems, with a 16–800A range and AC 400/415V ratings. Panel builders and equipment manufacturers can select the frame, breaking capacity and accessories to suit their assemblies. For distributor orders or project procurement, share your required configuration and quantity with CHAC for review.
Visão Geral do Produto
The CQM7 Series Thermal-Magnetic Molded Case Circuit Breaker covers a rated current range of 16A-800A. Its compact design combines overload and short-circuit protection with accessory options for low-voltage switchboards and equipment assemblies. For OEM projects and distribution orders, the CQM7 catalogue gives purchasing and engineering teams a common reference for confirming ratings, dimensions and accessories before ordering.
Solicitações
Typical applications include industrial power distribution, commercial buildings, infrastructure, switchboards and motor protection. Panel builders and electrical contractors should match the selected CQM7 configuration to the circuit design, enclosure space and protection requirements. Importers and distributors can use the frame and current options to define a product range for their market, with local requirements checked for each configuration.
Principais especificações
Corrente nominal: 16A-800A
Tensão operacional nominal: AC 400/415V
Tensão de isolação nominal: 800V
Tensão de resistência nominal ao impulso: 8kV
Capacidade de ruptura por curto-circuito: Até 50kA Icu a 400/415V AC, dependendo do quadro elétrico e da designação da capacidade de ruptura
Tipo de viagem: Termo-magnético
Choose the Right CQM7 Frame for Your Project
Start with the circuit current and fault level, then compare the available CQM7 frames. The frame number identifies the frame rating; it does not mean that every breaker in that frame has the same rated current.
| CQM7 frame | Available rated currents (A) | Icu / Ics at AC 400/415 V (kA) |
|---|---|---|
| CQM7-125 | 16, 20, 32, 40, 50, 63, 80, 100, 125 | C: 25 / 15; S: 30 / 20 |
| CQM7-250 | 125, 140, 160, 180, 200, 225, 250 | C: 35 / 25; S: 40 / 30 |
| CQM7-400 | 250, 315, 350, 400 | S: 35 / 25; M: 50 / 35 |
| CQM7-630 | 250, 315, 350, 400, 500, 630 | S: 35 / 25; M: 50 / 35 |
| CQM7-800 | 500, 630, 700, 800 | S: 35 / 25; M: 50 / 35 |
The ratings above are for the published 3-pole models. C, S and M identify the listed breaking-capacity options. Match the selected option to the installation fault level and required service performance. Where current ratings overlap between frames, also compare mounting dimensions, conductor connections and accessory requirements.
Guia de Seleção
![]()
| Código do produto | Código de extensão | Grau do quadro do casco | Capacidade de corte | Método de operação | Número de polos | ||||
| CQM7 | G | 125 | C | P | 4 | ||||
| Disjuntor de gabinete moldado | —: A proteção térmica e magnética não é ajustável G: Alarme de sobrecarga sem função trip |
C | S | M | H | P: Operação com motor Z:Alavanca de ajuste de frequência W: Operação direta |
125A:3P 250A:3P 400A:3P 630A:3P 800A:3P |
||
| 125 | 125 | 25/15 | 30/20 | / | / | ||||
| 250 | 250 | 35/25 | 40/30 | / | / | ||||
| 400 | 400 | / | 35/25 | 50/35 | / | ||||
| 630 | 630 | / | 35/25 | 50/35 | / | ||||
| 800 | 800 | / | 35/25 | 50/35 | / | ||||
| Unidade de viagem e acessórios | Corrente nominal A | Função | Código da Opção 4P | Código especial | |
| 300 | 125A | 2 | A | I | |
| O primeiro dígito indica o tipo de trava. 2: Bloqueio instantâneo apenas 3: Retenção duplicada Nota: Os dois últimos dígitos são o designador do acessório (veja a tabela de acessórios). |
125 | 16,20,32,40,50,63,80,100,125 | 1: Para distribuição de energia 2: Para proteção do motor |
A:O polo N não está protegido e não pode ser combinado B:O pólo N não está protegido e pode ser combinado C:N-pole é protegido e pode ser combinado D:N-pole é protegido e não pode ser combinado |
I: Função de alarme de sobrecarga sem trip |
| 250 | 125,140,160,180,200,225,250 | ||||
| 400 | 250,315,350,400 | ||||
| 630 | 250,315,350,400,500,630 | ||||
| 800 | 500,630,700,800 | ||||
| Tensão do acessório | Tensão de operação elétrica | Instalação | Opção de bloco de terminal | |||
| Q1 | D1 | Q | 2 | |||
| Baixa tensão detentor Q1: AC220V Q2: AC 240V Q3: AC380V Q4: AC415V |
Shunt liberação F1:CA220V F2:AC380V F3:DC110V F4: DC24V |
Auxiliar alarme J1:AC125V J2:AC250V J3: DC125V J4: DC24V |
CD1 Operação elétrica D1:AC220V D2:AC230V D3:AC380V D4:AC400V |
CD2 Operação elétrica D5:AC230V D6:AC110V D7:DC220V D8:DC110 D9:AC110-240V D10:CA100-220V |
Q: Frente do placa H: Fronteira da placa C:Inserido |
1: Instalação 2: Instalação |
| Nota: Quando a operação com motorização for selecionada, consulte os acessórios externos para as duas tensões aplicáveis à operação com motorização. | ||||||
Principais parâmetros técnicos
| Número do modelo | CQM7-125 | CQM7-250 | ||||
| Corrente nominal do quadro Inm (A) | 125 | 250 | ||||
| Número de polos | 3 | 3 | ||||
| Corrente nominal em (A) a 40°C, 50°C, 55°C | 16, 20, 32, 40, 50, 63, 80, 100, 125 | 125, 140, 160, 180, 200, 225, 250 | ||||
| Tensão de operação nominal Ue (V), AC 50/60 Hz | 400/415 | 400/415 | ||||
| Tensão de isolação nominal Ui (V) | 800 | 800 | ||||
| Tensão de resistência a impulsos nominal Uimp (kV) | 8 | 8 | ||||
| Designação de capacidade de ruptura | C | S | C | S | ||
| Capacidade de ruptura de curto-circuito Icu/Ics (kA) | CA 400/415 V | 25/15 | 30/20 | 35/25 | 40/30 | |
| Categoria de seletividade | A | A | A | A | ||
| Número de ciclos operacionais (ciclo) | ATIVADO | 1000 | 1000 | |||
| OFF | 10000 | 10000 | ||||
| Mecanismos de viagem e tipos de proteção | Viagem magnética | Proteção da distribuição de energia | ● | ● | ● | ● |
| Proteção do motor | ● | ● | ● | ● | ||
| Travagem térmica-magnética | Proteção da distribuição de energia | ● | ● | ● | ● | |
| Proteção do motor | ● | ● | ● | ● | ||
| Acessórios | Contatos auxiliares | ● | ● | ● | ● | |
| Contatos de alarme | ● | ● | ● | ● | ||
| Desconexão do shunt | ● | ● | ● | ● | ||
| Detentor de tensão baixa | ● | ● | ● | ● | ||
| Mecanismo de operação manual | ● | ● | ● | ● | ||
| Mecanismo de operação motorizado | ● | ● | ● | ● | ||
| Fiação da placa de circuito principal | ● | ● | ● | ● | ||
| Inserido | ● | ● | ● | ● | ||
| Placa de acoplamento | ● | ● | ● | ● | ||
| Partição entre fases | ● | ● | ● | ● | ||
| Produtos derivados | Dedicado a medidores elétricos pré-pagos | ● | ● | ● | ● | |
| Alarme de sobrecarga sem trip | – | – | ● | ● | ||
| Dimensões gerais (mm) (a-b-c-ca) | ![]() |
3 P | 77×131×65×82 | 105×165×68×95 | ||
Nota:● para acessórios opcionais; “-” para não haver acessórios opcionais.
| Número do modelo | CQM7-400 | CQM7-630 | CQM7-800 | |||||
| Corrente nominal ao nível do quadro Inm(A) | 400 | 630 | 800 | |||||
| Número de polos | 3 | 3 | 3 | |||||
| Corrente nominal (A), a 40°C, 50°C e 55°C | 250, 315, 350, 400 | 250, 315, 350, 400, 500, 630 | 500, 630, 700, 800 | |||||
| Tensão de operação nominal Ue(V), CA 50/60Hz | 400/415 | 400/415 | 400/415 | |||||
| Tensão de isolação nominal Ui (V) | 800 | 800 | 800 | |||||
| Tensão de resistência de impulso nominal Uimp(KV) | 8 | 8 | 8 | |||||
| Designação de capacidade de ruptura | S | M | S | M | S | M | ||
| Capacidade de ruptura de curto-circuito Icu/Ics (kA) | AC400/415V | 35/25 | 50/35 | 35/25 | 50/35 | 35/25 | 50/35 | |
| Categoria de seletividade | A | A | A | A | A | A | ||
| Número de ciclos operacionais (ciclo) | ATIVADO | 1000 | 1000 | 500 | ||||
| OFF | 4000 | 4000 | 2500 | |||||
| Mecanismos de viagem e Tipos de proteção |
Viagem magnética | Proteção da distribuição de energia | ● | ● | ● | ● | ● | ● |
| Proteção do motor | ● | ● | ● | ● | ● | ● | ||
| Travagem térmica-magnética | Proteção da distribuição de energia | ● | ● | ● | ● | ● | ● | |
| Proteção do motor | ● | ● | ● | ● | ● | ● | ||
| Acessório | Contatos auxiliares | ● | ● | ● | ● | ● | ● | |
| Contatos de alarme | ● | ● | ● | ● | ● | ● | ||
| Desconexão do shunt | ● | ● | ● | ● | ● | ● | ||
| Detentor de tensão baixa | ● | ● | ● | ● | ● | ● | ||
| Mecanismo de operação manual | ● | ● | ● | ● | ● | ● | ||
| Mecanismo de operação motorizado | ● | ● | ● | ● | ● | ● | ||
| Fiação da placa de circuito principal | ● | ● | ● | ● | ● | ● | ||
| Inserido | ● | ● | ● | ● | ● | ● | ||
| Placa de acoplamento | ● | ● | ● | ● | ● | ● | ||
| Partição entre fases | ● | ● | ● | ● | ● | ● | ||
| Produtos derivados | Dedicado a medidores elétricos pré-pagos | ● | ● | ● | ● | ● | ● | |
| Alarme de sobrecarga sem trip | ● | ● | ● | ● | ● | ● | ||
| Dimensões gerais (mm) (a-b-c-ca) |
![]() |
3 P | 139×257×108×154 | 139×257×108×154 | 180×270×114×158 | |||
Nota:● para acessórios opcionais; “-” para não haver acessórios opcionais.
Características operacionais
1. As características operacionais em tempo inverso dos disjuntores de distribuição de energia quando todos os polos são energizados simultaneamente a uma temperatura ambiente de +40 °C (sem compensação de umidade) são apresentadas na tabela seguinte:
| Teste a designação atual | Configurando múltiplos atuais | Horário convencional | Estado inicial |
| Em ≤63 63<In | |||
| Corrente convencional sem acionamento | 1.05 | ≥1h ≥2h | Estado legal |
| Corrente de disparo convencional | 1.30 | <1h <2h | Estado quente |
2. As características de ação do tempo inverso dos disjuntores para proteção de motores sem compensação de umidade quando todos os polos estão energizados simultaneamente a uma temperatura do ar ambiente de +40℃ são apresentadas na tabela abaixo:
| Teste a designação atual | Configurando múltiplos atuais | Horário convencional | Estado inicial |
| Em ≤800 | |||
| Corrente convencional sem acionamento | 1.0 | ≥2h | Estado legal |
| Corrente de disparo convencional | 1.2 | <2h | Estado quente |
3. Características da ação em condições de curto-circuito: O valor de ajuste da corrente de curto-circuito do triângulo instantâneo do disjuntor para distribuição de energia é de 10In.
O valor de ajuste da corrente de curto-circuito do tripper instantâneo do disjuntor para proteção de motor é de 12In.
A precisão do valor de ajuste da corrente de curto-circuito do tripper instantâneo é de 20% do valor de ajuste da corrente de curto-circuito.
Lista de acessórios



1. A nossa empresa pode fornecer três novos produtos aos clientes para escolher, nomeadamente o interruptor auxiliar do lado direito, o dispositivo de tripé do lado esquerdo e o dispositivo de liberação de tensão inferior do lado esquerdo.
2. Para as especificações dos modelos 220, 320, 240, 340, 270 e 370, o interruptor auxiliar pode fornecer dois pares de interruptores. Por favor, especifique isso ao fazer o pedido.
3. Para as especificações 250 e 350, o dispositivo de tripé especial e o desajustamento de tensão para os modelos 400 e superiores só podem ser instalados em disjuntores de 3 polos.
CQM7-125 Curva de características operacionais

CQM7-250 Curva de Característica Operacional

CQM7-400 / 630 Curva de características operacionais

CQM7-800 Curva de características operacionais

Resumo e Dimensões de Instalação (mm)

| Caso moldado disjuntor |
Dimensões gerais | Instalação dimensões |
Bolt | |||||||||||||||||||||
| A | A1 | A2 | A3 | B | B1 | B2 | B3 | B5 | B6 | H | H1 | H2 | H3 | H4 | H5 | H6 | A4 | B4 | ||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |||||||||||||||||
| CQM7-125 | 77 | – | 50 | – | – | – | – | – | 131 | 116 | 90.2 | 45 | – | – | 82 | 68.3 | 3 | 65.3 | 56.5 | 25 | 25 | – | – | M6 |
| CQM7-250 | 105 | – | 70 | – | – | – | – | – | 165 | 144 | 101.2 | 60.8 | – | – | 95 | 73.1 | 6 | 68.1 | 61.4 | 22.3 | 23.1 | – | – | M8 |
| CQM7-400 | 139 | – | 88 | – | – | – | – | – | 257 | 224.5 | 150 | 97 | – | – | 154.2 | 110.5 | 4.5 | 108 | 99.5 | 35.2 | 36.5 | – | – | M10 |
| CQM7-630 | 136 | – | 88 | – | – | – | – | – | 257 | 224.5 | 150 | 97 | – | – | 154.2 | 110.5 | 4.5 | 108 | 99.5 | 35.2 | 36.5 | – | – | M10 |
| CQM7-800 | 180 | – | 116 | – | – | – | – | – | 270 | 235 | 150 | 96 | – | – | 158.2 | 116 | 5 | 114 | 103 | 43.5 | 44.8 | – | – | M12 |
Porquê escolher a CHAC
Com mais de 30 anos de experiência em fabrico, mais de 1100 funcionários, mais de 100 milhões de postes
Com uma capacidade anual e um processo de produção automatizado 90%, a CHAC garante uma capacidade de produção estável e rigorosos
Controlo de qualidade para clientes OEM/ODM globais. O nosso sistema de fabrico interno suporta a longo prazo
cooperação para marcas elétricas, importadores e distribuidores.
30+
ANOS DE EXPERIÊNCIA
Especializado em fabrico de baixa tensão elétrica
1100+
FUNCIONÁRIOS
Equipa profissional garante qualidade e entrega estáveis
100M+
CAPACIDADE ANUAL DE POSTOS
Capacidade de produção em larga escala para satisfazer a procura global
90%
PRODUÇÃO AUTOMATIZADA
Automação avançada para alta eficiência e consistência

Linha de Montagem Automatizada

Laboratório de Ensaios

Injeção e Estampagem

Inspeção de Qualidade





Solicite os documentos técnicos e de conformidade do CQM7 necessários para o seu projeto. As informações e as marcas apresentadas a nível da empresa não constituem aprovação de todas as configurações do CQM7 em todos os mercados.
O que podemos personalizar?
For electrical brands, equipment manufacturers and distributors sourcing CQM7 MCCBs, start with the frame, rated current within the published 16–800 A range, protection duty and catalogue-listed accessories. CHAC can review private-label marking, packaging and technical-document requirements for the agreed configuration. Include your destination market and order quantity in the enquiry; housing, internal or electrical changes require engineering confirmation.
Recinto
Design
Verifique as dimensões do quadro CQM7, a disposição de montagem e as tolerâncias para o seu painel. As alterações no alojamento necessitam de aprovação técnica.

Interno
Configuração
Escolha a configuração de viagem e as combinações de acessórios listadas no catálogo necessárias para o quadro CQM7 encomendado.

Branding &
Logótipo
For private-label orders, review logo, nameplate and label artwork while retaining the required CQM7 identification and electrical markings.

Embalagem
Design
Discuss unit cartons, shipping cartons, labels and manuals for your distribution channel, with packaging requirements agreed before the order is confirmed.

Elétrico
Configuração
Confirme a corrente nominal, a tensão de trabalho AC 400/415 V e a capacidade de ruptura. Especificar as tensões de comando dos acessórios separadamente.

Certificação
Apoio
Solicite os documentos técnicos necessários para a configuração exata do CQM7 e o mercado de destino. Verifique as aprovações por modelo e âmbito.

What to Confirm Before Ordering CQM7 MCCBs
A clear specification helps panel builders, OEM purchasing teams and distributors compare quotations for the same product. Use these four checks to define the technical and commercial scope of your enquiry.
Define the electrical configuration
List the CQM7 frame, rated current, AC system voltage, required Icu/Ics, poles and distribution or motor-protection duty. Include the selected trip type and accessories.
Attach the relevant specification or bill of materials so the quotation identifies the intended configuration.
Break down the quantity by model
For project or distributor orders, state the quantity for each configuration. Separate any sample request from the main order and provide your requested delivery schedule.
Ask CHAC to confirm availability and lead time for the agreed configuration and quantity.
Agree the branding and packaging scope
For OEM branding, provide logo artwork, proposed nameplate details and label requirements. Specify unit and shipping cartons, manuals and any distributor packaging needs.
Review the proposed artwork and packaging specification before approving the order.
Identify the documents your market requires
State the destination market and request the applicable datasheet, dimensional drawing, installation instructions and conformity documents for the exact model.
Check document scope against the ordered configuration; company-level certificates do not establish every product approval.
Transferir
Catálogo de produtos CQM7
Catálogo de disjuntores de gabinete moldado CQM7 AC com seleção de modelos de 16 a 800 A, classificações técnicas, opções de acessórios, curvas de operação e dimensões de instalação.
Precisa de Documentos Técnicos?
Contacte-nos para folhas de dados, certificados, desenhos, orientação de seleção ou suporte a projetos OEM/ODM.
FAQ do produto CQM7
Para que serve o disjuntor moldado CQM7?
O CQM7 oferece proteção contra sobrecarga e curto-circuito para circuitos de distribuição de baixa tensão. Suas aplicações publicadas incluem distribuição de energia industrial, edifícios comerciais, infraestrutura, painéis de distribuição e proteção de motores. Escolha a versão de distribuição ou proteção de motor para combinar com o circuito e os requisitos de coordenação.
Qual é a tensão de operação nominal do CQM7?
As tabelas técnicas do CQM7 especifcam a tensão de alimentação em CA de 400/415 V em 50/60 Hz. A classificação de isolamento em 800 V e a resistência a impulsos de 8 kV descrevem características diferentes; nenhuma delas aumenta a tensão de operação permitida. Utilize as classificações de tensão de operação e capacidade de ruptura para o modelo exato que você está solicitando.
Como escolher o tamanho do quadro do CQM7 e a corrente nominal?
A série cobre 16–800 A em todos os quadros do CQM7-125, -250, -400, -630 e -800. A classificação de quadro não é a mesma do valor nominal da corrente do disjuntor montado. Comece com a carga de projeto e os requisitos de proteção do condutor, então selecione uma classificação de corrente disponível no quadro apropriado. Verifique a temperatura ambiente, as condições do recinto e a coordenação de proteção antes de realizar a encomenda.
Qual é a diferença entre Icu e Ics em um MCCB CQM7?
Icu é a capacidade nominal de ruptura de curto-circuito máximo; Ics é a capacidade nominal de ruptura de curto-circuito em serviço. A tabela CQM7 lista pares Icu/Ics de 25/15 ou 30/20 kA para os quadros de 125, 35/25 ou 40/30 kA para os quadros de 250 e 35/25 ou 50/35 kA para os quadros de 400, 630 e 800. Verifique a indicação exata de capacidade de ruptura em relação ao nível de falha da instalação e aos requisitos de serviço. A capacidade máxima de Icu de 50 kA não se aplica a todos os modelos.
Quais configurações de poste do CQM7 estão apresentadas nas tabelas técnicas?
As principais tabelas técnicas e desenhos dimensionais publicados listam modelos de 3 polos para os quadros CQM7-125, -250, -400, -630 e -800. Apesar de o guia de pedidos também conter códigos de opção para polos neutros, não assuma que todos os quadros estejam disponíveis na versão de 4 polos. Solicite a configuração exata e o desenho aplicável antes de especificar um polo neutro.
O que deve ser verificado antes da instalação e comissionamento de um CQM7?
Um instalador qualificado deve verificar o modelo exato, a corrente nominal, a capacidade de ruptura, as dimensões de montagem, as conexões do condutor, o torque dos terminais e as tolerâncias exigidas, de acordo com as instruções de instalação. Confirme as tensões de comando dos acessórios e complete as verificações funcionais especificadas antes de ligar a energia. Use o desenho do quadro encomendado em vez de outro tamanho CQM7.
Como um MCCB termomagnético trava?
Em um MCCB termomagnético, o elemento térmico responde a uma sobrecarga sustentada, enquanto o elemento magnético responde a uma corrente de curto-circuito elevada. O catálogo CQM7 distingue configurações termomagnéticas e exclusivamente magnéticas, além de funções de distribuição e proteção de motor. Defina o tipo de proteção necessário; uma versão exclusivamente magnética não oferece a mesma proteção contra sobrecarga que uma versão termomagnética.
As configurações de viagem térmica e magnética do CQM7 são ajustáveis?
A configuração térmica-magnética padrão no guia de pedidos CQM7 é descrita como tendo proteção térmica e magnética não ajustável. Não assuma que todos os MCCBs tenham configurações ajustáveis. Se o projeto precisar de proteção ajustável, forneça os intervalos de ajuste necessários e um estudo de coordenação para que uma configuração ou produto adequado possa ser avaliado.
Quando devo optar por um MCCB em vez de um MCB?
Avalie um MCCB quando o circuito exige um intervalo de corrente, capacidade de ruptura, disposição de conexões ou acessórios de controle que o MCCB proposto não oferece. A família CQM7 chega a 800 A e oferece opções de acessórios específicas para cada quadro. Quando as classificações se sobrepõem, compare os dispositivos exatos e sua compatibilidade, dimensões e requisitos de instalação, em vez de optar apenas com base na categoria do produto.
O MCCB CQM7 também oferece proteção contra vazamento de terra?
O padrão CQM7 descrito aqui fornece proteção contra sobrecarga e curto-circuito. Essas funções não estabelecem proteção contra corrente residual ou fuga de terra. Se o projeto exigir proteção contra fuga, especifique essa função separadamente e confirme o dispositivo adequado ou a montagem coordenada. Um dispositivo de desvio isolado não detecta corrente de fuga.
A CQM7 com classificação de CA pode ser utilizada em circuitos DC ou fotovoltaicos?
Não aplique a classificação AC de 400/415 V a circuitos de DC. A interrupção de DC requer uma tensão DC declarada, disposição dos polos, direção do corrente e capacidade de ruptura para o modelo específico. As tabelas AC da CQM7 nesta página não estabelecem essas classificações. Para circuitos de PV ou bateria, selecione um produto com classificações documentadas para a aplicação DC pretendida.
Qual é a diferença entre uma viagem de shunt e uma liberação de tensão inferior?
Uma viagem de shunt ativa o disjuntor quando recebe o sinal de controle externo especificado. Uma liberação de tensão inferior responde quando a fonte de alimentação de controle cai abaixo das condições operacionais especificadas e pode impedir a fechadura sem uma fonte de alimentação adequada. O catálogo CQM7 lista ambos os tipos de acessórios. Confirme a estrutura, a combinação de acessórios, a tensão da bobina de CA ou CC e o diagrama de instalação antes de realizar a encomenda; as duas funções não são intercambiáveis.
Confirme a configuração correta do CQM7
Planning a panel-building project, distributor order or OEM supply enquiry? Send the CQM7 frame, rated current, AC system voltage, fault level, protection duty, accessories and quantity. Include the destination market and any branding or packaging requirements so CHAC can review the configuration and quotation scope.