Disjuntor de Ar Série CQW2

O Disjuntor de Ar Série CQW2 is a CHAC air circuit breaker for main low-voltage distribution protection. The page keeps the model-specific technical table and original product images so buyers can verify voltage, current, configuration, mounting and applicable standards before ordering. Final suitability depends on the complete circuit, installation method and destination-market rules.

Product family:
ACB
Primary function:
main low-voltage distribution protection
Typical context:
incomers, bus couplers and large feeders
Technical data:
See verified model table below
Configuration:
Confirm the exact model variant
Support:
OEM/ODM review available

Visão Geral do Produto

CQW2 Series Air Circuit Breaker is a air circuit breaker intended for main low-voltage distribution protection. The current product record identifies it for incomers, bus couplers and large feeders. Use the exact model variant and preserved technical source as the basis for procurement rather than assuming that every family member has the same rating.

Verified source summary: Type designation Code Position Code Symbol Meaning & Explanation ① Enterprise Code Zhejiang Chuangqi Electric Co., LTD. ② Product Code Universal Circuit Breaker ③ Design Serial Number Design Serial Number ④ Frame Rating Code 1600, 2000, 3200, 4000, 6300 ⑤ Number of Poles 3: 3-Pole, 4: 4-Pole ⑥ Mounting Type D: Drawout Type, F: Fixed Type ⑦ Rated Current 200~6300A ⑧ Intelligent Controller L: Electronic Type, M: Standa

Principais Características

  • Product type: air circuit breaker.
  • Primary function: main low-voltage distribution protection.
  • Application context: incomers, bus couplers and large feeders.
  • Model variants, dimensions and ratings remain in the preserved technical source.
  • Confirm installation method, environmental limits and local compliance before release.

Aplicações Típicas

Typical use can include incomers, bus couplers and large feeders when the project confirms system voltage, current, fault or surge exposure, conductor and enclosure requirements, and the selected variant’s installation instructions. This page does not replace the project design or the authority having jurisdiction.

Guia de Candidaturas e Seleção

Use the following decision points with the preserved model data. Product-family descriptions explain intent, but the exact technical table controls the ordered variant.

Ponto de seleção Disjuntor de Ar Série CQW2 O que o projeto deve confirmar
Aplicação ACB projects Confirm the actual system and environment
Selection basis main low-voltage distribution protection Use the exact model and technical table
Instalação Follow the model instructions Check mounting, clearances and termination
Compliance Use the listed standard where applicable Verify edition, scope and destination rules
Adjacent product Evaluate the related CHAC family where function differs Do not substitute without engineering review

Function

main low-voltage distribution protection

Match the protection or switching function to the system.

View related guidance →

Configuração

Model-specific options

Confirm current, voltage, poles, terminals or accessories from the table.

View related guidance →

Instalação

Mechanical and electrical fit

Check enclosure, mounting, wiring space and maintenance access.

View related guidance →

Project evidence

Documents and test records

Retain the approved drawing, technical sheet and commissioning record.

View related guidance →

Guia de Encomenda

  1. State the exact model and variant.
  2. Provide the system voltage, current, frequency and load or protection function.
  3. Confirm mounting, terminals, accessories, enclosure and environmental conditions.
  4. Share quantity, destination market and required technical documents.

Verificações de Instalação e Coordenação

  • Verify the model’s ratings and connection arrangement against the project drawings.
  • Check conductor, busbar, enclosure, clearances and tightening requirements using the product documentation.
  • Coordinate upstream and downstream protection or control devices where applicable.
  • Use qualified personnel for installation, testing, isolation and maintenance.

Designação do tipo

Code Position Code Symbol Meaning & Explanation
① Enterprise Code Zhejiang Chuangqi Electric Co., LTD.
② Product Code Universal Circuit Breaker
③ Design Serial Number Design Serial Number
④ Frame Rating Code 1600, 2000, 3200, 4000, 6300
⑤ Número de Polos 3: 3-Pole, 4: 4-Pole
⑥ Mounting Type D: Drawout Type, F: Fixed Type
⑦ Rated Current 200~6300A
⑧ Intelligent Controller L: Electronic Type, M: Standard Type, H: Communication Type
⑨ Control Circuit Voltage AC230V, AC400V, DC220V, DC110V

Especificações Técnicas

Parâmetro CQW2-1600 CQW2-2000 CQW2-3200
Rated Current In (A) 200, 400, 630, 800
1000, 1250, 1600
400, 630, 800, 1000
1250, 1600, 2000
2000, 2500, 2900,
N-pole Rated Current 100%In 100%In 100%In
Rated Operational Voltage Ue AC415V/690V AC415V/690V AC415V/690V
Rated Frequency f 50/60Hz 50/60Hz 50/60Hz
Rated Insulation Voltage Ui 1000V 1250V 1000V
Rated Impulse Withstand Voltage Uimp 12kV 12kV 12kV
Número de Polos 3, 4 3, 4 3, 4
Total Break Time ≤30ms ≤30ms ≤30ms
Closing Time ≤70ms ≤70ms ≤70ms
Rated Ultimate Short-Circuit AC415V 65kA 80kA 100kA
Breaking Capacity Icu (RMS) AC690V 42kA 65kA 75kA
Rated Service Short-Circuit AC415V 55kA 80kA 85kA
Breaking Capacity Ics (RMS) AC690V 35kA 65kA 65kA
Rated Making Capacity Icm AC415V 143kA 176kA 220kA
(Peak) AC690V 88kA 143kA 176kA
Rated Short-Time Withstand AC415V 42kA 60kA 85kA
Current Icw (RMS) AC690V 35kA 40kA 55kA
Operating Performance
(Number of operations)
Mechanical Life –
Maintenance-Free
10000 15000 15000
Mechanical Life –
With Maintenance
10000 15000 15000
Operating Frequency 20 operations/hour 20 operations/hour 20 operations/hour
Electrical Life – AC415V 15000 15000 15000
Electrical Life – AC690V 30000 30000 30000
Operating Frequency 60 operations/hour 60 operations/hour 60 operations/hour
Control and Protection Unit L Type (Electronic Type)
M Type (Standard Type)
H Type (Communication Type)
Connection Method Horizontal
Vertical
Padrão IEC60947-2, GB/T14048.2
Parâmetro CQW2-4000 CQW2-6300
Rated Current In (A) 3200, 3600, 4000 4000, 5000, 6300
N-pole Rated Current 100%In 100%In
Rated Operational Voltage Ue AC415V/690V AC415V/690V
Rated Frequency f 50/60Hz 50/60Hz
Rated Insulation Voltage Ui 1000V 1000V
Rated Impulse Withstand Voltage Uimp 12kV 12kV
Número de Polos 3, 4 3, 4
Total Break Time ≤30ms ≤30ms
Closing Time ≤70ms ≤70ms
Rated Ultimate Short-Circuit
Breaking Capacity Icu (RMS)
AC415V 100kA 120kA
AC690V 80kA 85kA
Rated Service Short-Circuit
Breaking Capacity Ics (RMS)
AC415V 85kA 100kA
AC690V 70kA 75kA
Rated Making Capacity Icm
(Peak)
AC415V 220kA 264kA
AC690V 176kA 187kA
Rated Short-Time Withstand
Current Icw (RMS)
AC415V 85kA 100kA
AC690V 70kA 75kA
Operating Performance
(Number of operations)
Mechanical Life –
Maintenance-Free
6000 1000
Mechanical Life –
With Maintenance
3000 800
Operating Frequency 20 operations/hour 20 operations/hour
Electrical Life – AC415V 12500 5000
Electrical Life – AC690V 25000 10000
Operating Frequency 60 operations/hour 60 operations/hour
Control and Protection Unit L Type (Electronic Type)
M Type (Standard Type)
H Type (Communication Type)
Connection Method Horizontal
Vertical
Padrão IEC60947-2, GB/T14048.2

Accessory List

Accessory Name Parameters
Padrão
Configuração
Closing Solenoid AC230V, AC400V, DC220V, DC110V
Shunt Release AC230V, AC400V, DC220V, DC110V
Energy Storage Motor AC230V, AC400V, DC220V, DC110V
Auxiliary Switch 4 changeover contacts (default), 5 changeover contacts, 4NO+4NC, 6NO+6NC
Others Phase barrier, Door frame, Drawer base three-position lock
Optional
Configuração
Undervoltage Release AC230V, AC400V
Instantaneous, Delayed: 0.5s, 1s, 3s, 5s
Trip Locking Device 1 lock + 1 key, 2 locks + 1 key, 3 locks + 2 keys, 6NO+6NC
Mechanical Interlock For 2 circuit breakers: Linkage interlock (vertical), Cable interlock
For 3 circuit breakers: Linkage interlock (vertical), Cable interlock
Others Residual Current Transformer, External Neutral Current Transformer, Relay Module
Communication Module (Profibus-DP), Power Module, Wireless Remote Control Module

Intelligent Controller

Parâmetro CQW2-L CQW2-M CQW2-2M
Basic
Functions
Overload long-time delay protection;
Short-time delay short-circuit protection;
Instantaneous short-circuit protection;
Ground fault protection;
Dial switch grading setting;
Running current bar graph indication;
Test function;
Fault recording function;
Thermal memory function
Overload long-time delay protection;
Short-time delay short-circuit protection;
Instantaneous short-circuit protection;
Ground fault protection (differential type);
LED digital display;
Key setting method;
Ammeter function;
Test function;
Fault recording function;
Thermal memory function
Overload long-time delay protection;
Short-time delay short-circuit protection;
Instantaneous short-circuit protection;
Ground fault protection (differential type);
LED digital display;
Key setting method;
Ammeter function;
Test function;
Fault recording function;
Thermal memory function;
Clock function;
Self-diagnosis function;
Contact pattern and mechanical operation count
Optional
Functions
MCR make-break and over-limit tripping;
Contact output;
3P+N type neutral protection
MCR make-break and over-limit tripping;
Contact output;
Voltage function;
Residual current type leakage protection;
Clock function;
Current unbalance protection;
Remote reset function;
Load monitoring function;
3P+N type neutral protection;
Low voltage ride-through
MCR make-break and over-limit tripping;
Contact output;
Voltage function;
Residual current type leakage protection;
Current unbalance protection;
Remote reset function;
Load monitoring function;
3P+N type neutral protection;
Low voltage ride-through
Optional
Accessories
DC Power Module (DC110V/220V)
External N-phase Transformer
DC Power Module (DC110V/220V)
External N-phase Transformer
Ground Current Transformer ZT100
Residual Current Transformer ZCT1
ST201 Relay Module
ST-4 Power Module
ST Handheld Programmer
DC Power Module (DC110V/220V)
External N-phase Transformer
Ground Current Transformer ZT100
Residual Current Transformer ZCT1
ST201 Relay Module
ST-4 Power Module
ST Handheld Programmer

Nota:

1.Only one of the following functions can be selected: 3P+N neutral protection, groundcurrent type leakage protection, or residual current leakage protection. The correspondingtransformer accessory must be additionally selected.

2.Only one signal unit (S1, S2, or S3) can be selected.

3.For detailed instructions on the intelligent controller, please refer to the “SW1 Series Intelligent Controller User Manual”.

Parâmetro CQW2-2H CQW2-3M CQW2-3H
Basic
Functions
Overload long-time delay protection;
Short-circuit short-time delay protection;
Short-circuit instantaneous protection;
Ground fault protection (differential type);
LED digital tube display;
Key setting method;
Ammeter function;
Fault memory function;
Thermal memory function;
Clock function;
Self-diagnosis function;
Contact pattern and mechanical operation count;
Communication function
Load monitoring (current method 1);
Multi-curve long-time delay protection;
Multi-curve short-time inverse-time protection;
Short-time definite-time protection;
Instantaneous protection;
Current unbalance (phase loss) protection;
Ground fault alarm;
Ground fault protection (default T-type);
Neutral protection;
Four-phase current and ground current measurement;
Thermal capacity;
Eight records of faults, alarms and status changes;
Historical current peak;
Contact equivalent;
Operation count;
Clock function;
Self-diagnosis;
Chinese graphical LCD display;
LCD status indicator;
Keyboard operation
Load monitoring (current method 1);
Multi-curve long-time delay protection;
Multi-curve short-time inverse-time protection;
Short-time definite-time protection;
Instantaneous protection;
Current unbalance (phase loss) protection;
Ground fault alarm;
Ground fault protection (default T-type);
Neutral protection;
Four-phase current and ground current measurement;
Thermal capacity;
Eight records of faults, alarms and status changes;
Historical current peak;
Contact equivalent;
Operation count;
Clock function;
Self-diagnosis;
Chinese graphical LCD display;
LCD status indicator;
Keyboard operation;
Communication function
Optional
Functions
MCR make-break and over-limit tripping;
Contact output;
Voltage function;
Residual current type leakage protection;
Clock function;
Current unbalance protection;
Remote reset function;
Load monitoring function;
3P+N type neutral protection;
Low voltage ride-through
Function Table: D, U, UD, P, PD, H
Select HD from the table (refer to function table description)
Signal Unit: S1, S2, S3
Load Monitoring: Current Method 2
3P+N Type Neutral Protection
Ground Current Type Leakage Protection
Residual Current Type Leakage Protection
Remote Reset Function
Function Table: D, U, UD, P, PD, H
Select HD from the table (refer to function table description)
Signal Unit: S1, S2, S3
Load Monitoring: Current Method 2
3P+N Type Neutral Protection
Ground Current Type Leakage Protection
Residual Current Type Leakage Protection
Remote Reset Function
Profibus-DP Communication Protocol
Device-net Communication Protocol
Optional
Accessories
DC Power Module (DC110V/220V)
External N-phase Transformer
Ground Current Transformer ZT100
Residual Current Transformer ZCT1
ST201 Relay Module
ST-4 Power Module
ST Handheld Programme
DC Power Module (DC110V/220V)
External N-phase Transformer
Ground Current Transformer ZT100
Residual Current Transformer ZCT1
ST201 Relay Module
Selective Zone Interlocking Protection Device
DC Power Module (DC110V/220V)
External N-phase Transformer
Ground Current Transformer ZT100
Residual Current Transformer ZCT1
ST201 Relay Module
Selective Zone Interlocking Protection Device
D U UD P
Demand Measurement(Current)
Demand Protection
Voltage Measurement
Frequency Measurement
Voltage Unbalance Rate Measurement
Phase Sequence Detection
Overvoltage Protection
Undervoltage Protection
Voltage Unbalance Protection
Overfrequency Protection
Underfrequency Protection
Phase Sequence Protection
Voltage Measurement
Frequency Measurement
Voltage Unbalance Rate Measurement
Phase Sequence Detection
Current Demand Measurement
Overvoltage Protection
Undervoltage Protection
Voltage Unbalance Protection
Overfrequency Protection
Underfrequency Protection
Phase Sequence Protection
Demand Protection
Voltage Measurement
Frequency Measurement
Voltage Unbalance Rate Measurement
Phase Sequence Detection
Power Measurement
Power Factor Measurement
Energy Measurement
Overvoltage Protection
Undervoltage Protection
Voltage Unbalance Protection
Overfrequency Protection
Underfrequency Protection
Phase Sequence Protection
PD H HD
Voltage Measurement
Frequency Measurement
Voltage Unbalance Rate Measurement
Phase Sequence Detection
Power Measurement
Power Factor Measurement
Energy Measurement
Demand Measurement (Current, Power)
Overvoltage Protection
Undervoltage Protection
Voltage Unbalance Protection
Overfrequency Protection
Underfrequency Protection
Phase Sequence Protection
Voltage Measurement
Frequency Measurement
Voltage Unbalance Rate Measurement
Phase Sequence Detection
Power Measurement
Power Factor Measurement
Energy Measurement
Harmonic Measurement
Undervoltage Protection
Voltage Unbalance Protection
Overfrequency Protection
Underfrequency Protection
Phase Sequence Protection
Voltage Measurement
Frequency Measurement
Voltage Unbalance Rate Measurement
Phase Sequence Detection
Power Measurement
Power Factor Measurement
Energy Measurement
Demand Measurement (Current, Power)
Undervoltage Protection
Overvoltage Protection
Undervoltage Protection
Voltage Unbalance Protection
Overfrequency Protection
Underfrequency Protection
Phase Sequence Protection
Reverse Power Protection

Secondary Circuit Wiring Diagram

Wiring diagram of secondary circuit for SW1-1600-6300 circuit breakers equipped with L/M type intelligent controllers (auxiliary switch default

configuration: 4 changeover contacts)

Terminal Number Function Description Symbol Explanation Observações
1, 2 Auxiliary power input: AC230V,
AC400V, DC220V, DC110V
SW1 SW1 Universal Circuit Breaker Customer self-provided
For DC power: 1 is (+), 2 is (-) S1~S4 Signal lamp Customer self-provided
3, 4, 5 Fault trip auxiliary contact,
contact capacity: AC250V, 3A
TA Current transformer
20 Grounding (PE) SAL Micro switch Customer self-provided
27, 28 Undervoltage release SB1 Open button Customer self-provided
29, 30 Shunt release SB2 Close button
31, 32 Closing electromagnet x Closing electromagnet
33, 34, 35 Motor-operated mechanism
(motor energy storage),
37 connect green wire,
38 connect black wire,
39 connect red wire
F Shunt release
36~48 Auxiliary contact terminal Q Undervoltage release
M Motor-operated mechanism Customer self-provided
SA Travel switch of motor-operated mechanism Customer self-provided
Fu Fuse Customer self-provided
PE Grounding
N Neutral line (N phase)
A, B, C Phase line
For customer optional use of AX auxiliary switch form AX Auxiliary switch

Wiring diagram of secondary circuit for SW1-1600-6300 circuitbreakers equipped with H type intelligent controllers (auxiliary :switch default configuration: 4 changeover contacts)

Terminal Number Function Description Symbol Explanation Observações
1, 2 Auxiliary power input: AC230V,
AC400V, DC220V, DC110V
SW1 SW1 Universal Circuit Breaker Customer self-provided
For DC power: 1 is (+), 2 is (-) S1~S4 Signal lamp Customer self-provided
3, 4, 5 Fault trip auxiliary contact,
contact capacity: AC250V, 3A
TA Current transformer
10, 11 Communication interface output,
10 is (+), 11 is (-)
SAL Micro switch Customer self-provided
12~15 DO1, Programmable signal output,
contact capacity: AC250V, 3A
SB1 Open button Customer self-provided
14, 15 DO2, Programmable signal output,
contact capacity: AC250V, 3A
SB2 Close button Customer self-provided
16, 17 DO3, Trip signal output, contact
capacity: AC250V, 3A
X Closing electromagnet
18, 19 DO4, Closing signal output,
contact capacity: AC250V, 3A
F Shunt release
20 Grounding (PE) Q Undervoltage release
21, 22, 23, 24 Voltage signal measurement,
21 connect N phase, 22 connect A
phase, 23 connect B phase,
24 connect C phase
M Motor-operated mechanism
25, 26 External N-phase transformer input SA Travel switch of motor-operated mechanism Customer self-provided
27, 28 Undervoltage release Fu Fuse Customer self-provided
29, 30 Shunt release PE Grounding
31, 32 Closing electromagnet N Neutral line (N phase)
33, 34, 35 Motor-operated mechanism (motor
energy storage), 37 connect green
wire, 38 connect black wire,
39 connect red wire
A, B, C Phase line
36~48 Auxiliary contact terminal AX Auxiliary switch
For customer optional use of AX auxiliary switch form ST-DP
Module
Required for Profibus-DP communication
ST-DP
Module
Required for communication function
ST201
Relay
Module
Required for communication function

Dimensões (mm)

CQW2-1600 Series Fixed Type Overall Dimensions (Unit: mm)

Corrente nominal H (mm)
200、400、630 6
800、1000 10
1250、1600 18

CQW2-1600 Series Drawout Type Installation Dimensions (Unit: mm)

Corrente nominal H (mm)
200、400、630 6
800、1000 10
1250、1600 18

CQW2-1600 Series Fixed Type Overall Dimensions (Unit: mrm)

In a (mm)
400~800A 10
1000~1600A 15
2000A 20

CQW2-1600 Series Drawout Type Installation Dimensions (Unit: mm)

In a (mm)
400~800A 10
1000~1600A 15
2000A 20

CQW2-1600 Series Fixed Type Overall Dimensions (Unit: rnm)

In a (mm) b (mm)
2000,2500A 20 408
2900~3200A 30 428

CQW2-1600 Series Drawout Type Installation Dimensions (Unit: mm)

In a (mm) b (mm) c (mm)
2000,2500A 20 506 552
2900-3200A 30 526 572

CQW2-4000 Series Drawout Type (3-Pole) Frame II Increased Capacity Type OvDimensions (Unit: mm)

CQW2-4000 Series Drawout Type (4-Pole) Overall Dimensions (Unit: mm)

CQW2-6300 Series (In=5000A, 4000A) Drawout Type Overall Dimensions (Unit: mm)

CQW2-6300 Series (In=6300A) Drawout Type (3-Pole) Overall Dimensions (Unit: mm)

CQW2 Series Enclosure Door Frame Outline and Irnstallation Dimensions (Unit: mm)

Número do modelo a b c
CQW2-2000 304 345 263
CQW2-3200, 4000/3P 366 405 325
CQW2-4000/4P 304 345 263
CQW2-6300 366 405 325

Porquê escolher a CHAC

Com mais de 30 anos de experiência em fabrico, mais de 1100 funcionários, mais de 100 milhões de postes
Com uma capacidade anual e um processo de produção automatizado 90%, a CHAC garante uma capacidade de produção estável e rigorosos
Controlo de qualidade para clientes OEM/ODM globais. O nosso sistema de fabrico interno suporta a longo prazo
cooperação para marcas elétricas, importadores e distribuidores.


30+

ANOS DE EXPERIÊNCIA

Especializado em fabrico de baixa tensão elétrica


1100+

FUNCIONÁRIOS

Equipa profissional garante qualidade e entrega estáveis


100M+

CAPACIDADE ANUAL DE POSTOS

Capacidade de produção em larga escala para satisfazer a procura global


90%

PRODUÇÃO AUTOMATIZADA

Automação avançada para alta eficiência e consistência

Linha de Montagem Automatizada

Linha de Montagem Automatizada

Laboratório de Ensaios

Laboratório de Ensaios

Injeção e Estampagem

Injeção e Estampagem

Inspeção de Qualidade

Inspeção de Qualidade

Certificação IEC
Certificação CE
Certificação CB
Certificação RoHS
Certificação ISO 14001

Um rigoroso sistema de controlo de qualidade garante que cada produto cumpre as normas globais.

O que podemos personalizar?

Flexible customization services are available for enclosure dimensions, component configuration,
branding and project requirements.

Design de Caixa

Recinto
Design

Tamanhos de caixas personalizadas, estruturas e detalhes de instalação.

Design de Caixa
Configuração Interna

Interno
Configuração

Layout interno flexível e opções de arranjo de componentes.

Configuração Interna
Branding e Logótipo

Branding &
Logótipo

Logótipos de marca própria, placas de identificação e identificação da marca.

Branding e Logótipo
Design de Embalagem

Embalagem
Design

Caixas personalizadas, etiquetas, manuais e soluções de embalagem.

Design de Embalagem
Configuração Elétrica

Elétrico
Configuração

Instalação elétrica à medida com base nos requisitos da aplicação.

Configuração Elétrica
Suporte de Certificação

Certificação
Apoio

Apoio a normas e requisitos de conformidade do mercado-alvo.

Suporte de Certificação

Transferir

PDF

Disjuntor de Ar Série CQW2

Visão geral completa de componentes elétricos de baixa tensão e referência para seleção de produtos.

Transferir PDF

SUP

Precisa de Documentos Técnicos?

Contacte-nos para folhas de dados, certificados, desenhos, orientação de seleção ou suporte a projetos OEM/ODM.

Contacte-nos

CQW2 Product FAQ

Where is the CQW2 ACB used?

It is intended for large low-voltage distribution positions such as incomers, bus couplers or feeders when the selected frame, controller and installation arrangement are suitable.

How do I choose the frame and current?

Use design current, service conditions, short-circuit study, selectivity, poles, mounting type and controller functions. Frame size alone is not sufficient.

What is Icu?

Icu is the rated ultimate short-circuit breaking capacity under the applicable product standard. Confirm the test voltage and exact variant before using the value in a design.

Fixed or drawout mounting?

Choose from the installation and maintenance strategy, required isolation and switchboard design. Verify the matching cradle and interlocks.

What controller options are available?

The CQW2 record identifies standard, electronic and communication controller options. Confirm protection functions and control voltage for the order.

How should an ACB be commissioned?

Test insulation, primary and secondary circuits, trip functions, interlocks, racking positions and coordination settings with qualified personnel.

Confirm the Right CQW2 Configuration

Send the exact model, operating conditions, quantity, destination market and required documents. CHAC will review the request against the published product data.