Термореле серии CQR2

The Термореле серии CQR2 is a CHAC thermal overload relay for adjustable motor overload protection. The page keeps the model-specific technical table and original product images so buyers can verify voltage, current, configuration, mounting and applicable standards before ordering. Final suitability depends on the complete circuit, installation method and destination-market rules.

Серия продуктов:
Тепловое реле
Основная функция:
adjustable motor overload protection
Типичный контекст:
motor starters, fans and pump control
Технические характеристики:
См. таблицу проверенных моделей ниже
Конфигурация:
Уточните модель
Поддержка:
Доступна оценка качества продукции OEM/ODM

Обзор продукции

CQR2 Series Thermal overload relay is a thermal overload relay intended for adjustable motor overload protection. The current product record identifies it for motor starters, fans and pump control. Use the exact model variant and preserved technical source as the basis for procurement rather than assuming that every family member has the same rating.

Verified source summary: Type designation Selection Guide Instructions for Use CQR2 Series Thermal Overload Relay Panel Symbols and Functional Button Description Trip Test (Performed BEFORE energizing the main circuit): Open the cover. Press the test button with a screwdriver. The NC contacts will open and the NO contacts will close. The status change can be observed through the indicator window (yellow mark visible indicates tripped state;

Основные особенности

  • Product type: thermal overload relay.
  • Primary function: adjustable motor overload protection.
  • Application context: motor starters, fans and pump control.
  • Model variants, dimensions and ratings remain in the preserved technical source.
  • Confirm installation method, environmental limits and local compliance before release.

Типичные применения

Typical use can include motor starters, fans and pump control when the project confirms system voltage, current, fault or surge exposure, conductor and enclosure requirements, and the selected variant’s installation instructions. This page does not replace the project design or the authority having jurisdiction.

Приложение и руководство по отбору

Use the following decision points with the preserved model data. Product-family descriptions explain intent, but the exact technical table controls the ordered variant.

Точка отбора Термореле серии CQR2 Что должно подтвердить проект
Приложение Thermal Relay projects Confirm the actual system and environment
Selection basis adjustable motor overload protection Use the exact model and technical table
Installation Follow the model instructions Check mounting, clearances and termination
Соблюдение требований Use the listed standard where applicable Verify edition, scope and destination rules
Adjacent product Evaluate the related CHAC family where function differs Do not substitute without engineering review

Функция

adjustable motor overload protection

Match the protection or switching function to the system.

View related guidance →

Конфигурация

Model-specific options

Confirm current, voltage, poles, terminals or accessories from the table.

View related guidance →

Installation

Mechanical and electrical fit

Check enclosure, mounting, wiring space and maintenance access.

View related guidance →

Project evidence

Documents and test records

Retain the approved drawing, technical sheet and commissioning record.

View related guidance →

Руководство по оформлению заказа

  1. State the exact model and variant.
  2. Provide the system voltage, current, frequency and load or protection function.
  3. Confirm mounting, terminals, accessories, enclosure and environmental conditions.
  4. Share quantity, destination market and required technical documents.

Проверки установки и координации

  • Verify the model’s ratings and connection arrangement against the project drawings.
  • Check conductor, busbar, enclosure, clearances and tightening requirements using the product documentation.
  • Coordinate upstream and downstream protection or control devices where applicable.
  • Use qualified personnel for installation, testing, isolation and maintenance.

Тип обозначения

Cqr2 Series Thermal Overload Relay product image

Selection Guide

Cqr2 Series Thermal Overload Relay product image

Instructions for Use

CQR2 Series Thermal Overload Relay Panel Symbols and Functional Button Description

Cqr2 Series Thermal Overload Relay product image

Trip Test (Performed BEFORE energizing the main circuit):

Open the cover. Press the test button with a screwdriver. The NC contacts will open and the NO contacts will close. The status change can be observed through the indicator window (yellow mark visible indicates tripped state; mark hidden indicates reset state – see illustration above).

Reset Mode Setting (Performed BEFORE energizing the main circuit):

The relay leaves the factory set to manual reset mode. To select automatic reset mode, press and hold the reset button while turning it clockwise 90°. It is not advisable to change the reset mode while the circuit is energized and running.

Setting Current Adjustment (Performed BEFORE energizing the main circuit):

The relay leaves the factory set to the minimum setting current. To select a different setting current value, open the cover and turn the current setting dial with a screwdriver. Align the arrow on the dial with the current value corresponding to the full-load rated current of the motor being protected.

Emergency Stop:

Press the Stop Button. Pressing the stop button only opens the NC contacts; it does not affect the NO contacts. Releasing the stop button resets the NC contacts.

Dimensions (mm)

CQR2-25

Cqr2 Series Thermal Overload Relay product image

CQR2-38

Cqr2 Series Thermal Overload Relay product image

CQR2-95

Cqr2 Series Thermal Overload Relay product image

Технические характеристики

Product Model CQR2-25 CQR2-38 CQR2-95
Current rating 25 38 95
Rated insulation voltage V 690 690 690
Rated impulse withstand voltage V 6000 6000 6000
Enclosure protection grade IP20(Front side) IP20(Front side) IP20(Front side)
Phase loss protection ● ● ●
Manual and automatic reset ● ● ●
Temperature compensation ● ● ●
Tripping indication ● ● ●
Test button ● ● ●
Stop button ● ● ●
Installation method Insertable Insertable Insertable
Auxiliary contact 1NO+1NC 1NO+1NC 1NO+1NC
AC-15220V rated current A 2.73 2.73 2.73
AC-15380V rated current A 1.58 1.58 1.58
DC-13220V rated current A 0.2 0.2 0.2
Cross-sectional area of conductor(mm²) Main circuit Single-core or stranded wire 1 ~ 4 6~10 6~35
Wire connection screw M4 M4 M10
Auxiliary circuit Single-core or stranded wire 1 ~ 2.5 1~2.5 1-2.5
Wire connection screw M3.5 M3.5 M3.5

Tripping Characteristics

Товар No. Setting Current Multiple Operating Time Purpose / Test Condition
Overload Protection 1 1.05 No operation within 2 hours Starting from Cold State
2 1.2 Operation within 2 hours Starting from Hot State (after Item 1)
3 1.5 Operation within 2 minutes Starting after reaching thermal equilibrium at setting current
4 7.2 2S<TP≤10S Starting from Cold State
Phase Failure Protection 5 Any Two Phases One Phase No operation within 2 hours Starting from Cold State
1 0.9
6 1.15 0 Operation within 2 hours Starting from Hot State (after Item 5)

Adjustable Trip Setting Range

Product Model Current adjustment range RC(A) Plug-in contactors Short-circuit protection fuse (A)
aM gG
CQR2-25 0.1~0.16 CQC6(SM/KMNC1)-09
CQC6(SM/KMNC1)-12
CQC6(SM/KMNC1)-18
CQC6(SM/KMNC1)-25
0.25 2
0.16~0.25 0.5 2
0.25~0.40 1 2
0.40~0.63 1 2
0.63~1 2 4
1~1.6 2 4
1.6~2.5 4 6
2.5~4 6 10
4~6 8 16
5.5-8 12 20
7~10 12 20
9~13 16 25
12~18 20 35
17-25 25 50
CQR2-38 23-32 CQC6(SM/KMNC1)-32 40 63
30~38 40 80
CQR2-95 17~25 CQC6(SM/KMNC1)-40
CQC6(SM/KMNC1)-50
CQC6(SM/KMNC1)-65
CQC6(SM/KMNC1)-80
CQC6(SM/KMNC1)-95
25 50
23~32 40 63
30~40 40 100
37~50 63 100
48~65 63 100
55~70 80 125
63~85 80 125
80~95 100 160

Accessories Description

Приложение Model number Приложение
MB-1 Combined with M12 to form an independent mounting product
Cqr2 Series Thermal Overload Relay product image MB-2 Combined with M25 to form an independent mounting product
Cqr2 Series Thermal Overload Relay product image MB-3 Combined with M38 to form an independent mounting product
Cqr2 Series Thermal Overload Relay product image MB-4 Combined with M95 to form an independent mounting product

Почему стоит выбрать CHAC

С более чем 30-летним опытом производства, 1100 сотрудниками и 100 млн полюсов
Ежегодный производственный потенциал и 90% автоматизированных производственных линий обеспечивают стабильный производственный потенциал и строгий контроль качества.
контроль качества для глобальных клиентов из категории OEM/ODM. Наша собственная система производства обеспечивает долгосрочную стабильность
сотрудничество с производителями электротоваров, импортерами и дистрибьюторами.

Изображение продукта выключателя воздушного замыкания серии Cqw2
30+

МЫСЛИ О ВРЕМЕНИ

Специализируется на производстве электрооборудования низкого напряжения

Изображение продукта выключателя воздушного замыкания серии Cqw2
1100+

Сотрудники

Профессиональная команда обеспечивает стабильное качество и своевременную поставку

Изображение продукта выключателя воздушного замыкания серии Cqw2
100 миллионов+

ГОДИЧЕСКИЙ КОМПАКТ ПОЛОВ

Большой производственный потенциал для удовлетворения мирового спроса

Изображение продукта выключателя воздушного замыкания серии Cqw2
90%

Автоматизированное производство

Передовая автоматизация для высокой эффективности и стабильности

Изображение продукта термозащитерного реле серии CQR2

Автоматизированная производственная линия

Изображение продукта термозащитерного реле серии CQR2

Лаборатория тестирования

Изображение продукта термозащитерного реле серии CQR2

Инъекция и литье

Изображение продукта термозащитерного реле серии CQR2

Проверка качества

Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2

Строгое система контроля качества гарантирует, что каждый продукт соответствует мировым стандартам.

Что мы можем настроить?

CHAC supports customization of coil voltage, auxiliary contact configuration,
electrical parameters, product branding,packaging design and engineering development according to customers’ equipment and market requirements.

Изображение продукта термозащитерного реле серии CQR2

Напряжение на катушке

Варианты напряжения для роторных и постоянных магнитных роторов, адаптированные под требования конкретного применения.

Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2

Дополнительные контакты

Гибкие комбинации вспомогательных контактов для различных функций управления.

Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2

Электрические параметры

Текущие характеристики, диапазоны защиты и функциональные параметры могут быть настроены по желанию заказчика.

Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2

Брендность продукции

Поддержка использования фирменных логотипов, табличек с названием и идентификации продукции.

Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2

Дизайн упаковки

Наборы из картонных коробок, этикетки, инструкции и решения по упаковке.

Изображение продукта термозащитерного реле серии CQR2
Изображение продукта термозащитерного реле серии CQR2

Разработка инженерных решений

Поддержка от оптимизации чертежей до разработки продукции и подбора приложений.

Изображение продукта термозащитерного реле серии CQR2

Скачать

PDF

Термореле CQR2 серии

Полный обзор продукции электрооборудования низкого напряжения и справочник по выбору продукции.

 

SUP

Нужен технический документ?

Для получения информационных листовок, сертификатов, чертежей, рекомендаций по выбору или поддержки проектов OEM/ODM обращайтесь к нам.

Связаться с нами

CQR2 Product FAQ

What does the CQR2 protect?

It provides adjustable thermal overload protection for compatible AC motor starters. It is not a replacement for short-circuit protection.

How do I choose the relay range?

Select a range that contains the motor's rated current, then set it from the nameplate and installation conditions.

What is manual versus automatic reset?

Manual reset requires an intentional reset after a trip. Automatic reset can restart the control sequence when permitted by the machine risk assessment.

Does it detect phase failure?

The product record includes phase-failure protection. Confirm the exact variant, motor connection and test procedure.

Can it connect to a CQC6 contactor?

The page identifies CQC6 integration as an application. Confirm the mechanical interface and current range for the selected combination.

What should be recorded after testing?

Record the set current, trip test result, reset mode, auxiliary-contact operation and responsible technician.

Confirm the Right CQR2 Configuration

Send the exact model, operating conditions, quantity, destination market and required documents. CHAC will review the request against the published product data.

Запросить расчет стоимости