Interruptores automáticos en caja moldeada de la serie CQM5

El CQM5 MCCB provides overload and short-circuit protection within its published 10–800A range. Specification should follow the system voltage, load, conductor coordination, prospective fault current and applicable rules—not the ampere value alone.

Polacos
3P / 4P
Corriente nominal:
10–800A
Voltaje nominal
AC 380/400/415V and AC 660/690V
Trip / Protection:
overload and short-circuit protection
Datos de última hora:
12–100kA Icu and 10–75kA Ics values by frame, voltage and breaking class
Estándar
IEC 60947-2 and GB/T 14048.2

Descripción del producto

CQM5 is a molded case breaker for AC 380/400/415V and AC 660/690V distribution and protection applications. Its published range covers 10–800A with 3P / 4P options. Selection depends on the complete power-system design, including fault level, coordination, conductor ampacity, enclosure conditions and local rules.

The saved model record lists IEC 60947-2 and GB/T 14048.2 as the applicable standard reference. No certification claim is added beyond the model record.

Características clave

  • Published current range: 10–800A.
  • Pole options: 3P / 4P.
  • Protection function: overload and short-circuit protection.
  • Trip or setting information: thermal-magnetic trip.
  • Short-circuit data: 12–100kA Icu and 10–75kA Ics values by frame, voltage and breaking class.
  • Electrical reference: AC 380/400/415V and AC 660/690V.
  • Accessories, terminals and installation details must be confirmed for the ordered frame and configuration.

Aplicaciones típicas

Typical applications include commercial, industrial and infrastructure distribution or motor circuits. These are evaluation contexts rather than universal approvals. Confirm the exact frame, voltage, breaking duty, trip unit, accessories and installation method before specification.

Guía de Solicitudes y Selección

Use the verified CQM5 values below to create a shortlist, then validate the complete circuit. An MCCB rating does not replace conductor calculations, fault-current analysis, coordination review or local installation requirements.

Punto de selección CQM5 reference Lo que el proyecto debe confirmar
Corriente nominal 10–800A Design current, conductor ampacity, installation method, temperature and grouping
Voltaje AC 380/400/415V and AC 660/690V Sistema de suministro y capacidad nominal de los equipos
Polacos 3P / 4P Live conductors and neutral treatment
Trip / protection thermal-magnetic trip Load profile, fault response and coordination
Capacidad de corte 12–100kA Icu and 10–75kA Ics values by frame, voltage and breaking class Prospective short-circuit current at the installation point

Fixed vs Adjustable Protection

A fixed thermal-magnetic device can suit a stable design, while an adjustable trip unit may help coordination when the project study requires field settings.

Trip Coordination
Compare MCCB Options →

MCCB vs MCB

An MCCB is normally evaluated for higher current, fault duty or accessory flexibility; an MCB may be more suitable for compact final circuits.

Current & Fault Duty
Compare MCCB and MCB →

Icu vs Ics

The saved data for CQM5 lists 12–100kA Icu and 10–75kA Ics values by frame, voltage and breaking class. Match the declared duty to the prospective short-circuit current and continuity objective.

Short-Circuit Study
Review Technical Support →

Pole and Neutral Arrangement

Published pole options are 3P / 4P. Confirm which conductors must be switched, protected and isolated together.

System Arrangement
View MCCB Range →

Guía de pedidos

  1. State the exact model: CQM5.
  2. Provide frame and rated current within the published range: 10–800A.
  3. Confirm poles: 3P / 4P.
  4. Specify the trip unit or protection function: thermal-magnetic trip.
  5. Provide system voltage, frequency, application, expected fault level, destination market and quantity.
  6. List required accessories, terminals, documents and any approved OEM/ODM marking or packaging requirements.

Comprobaciones de Instalación y Coordinación

  • Use the exact model drawing and instructions; do not infer terminal positions, supply direction or accessory compatibility from another MCCB.
  • Verify conductor material and cross-section against the circuit calculation, terminal data, temperature and grouping.
  • Confirm Icu/Ics or DC fault duty, upstream/downstream coordination, enclosure conditions, altitude and clearances.
  • Installation, isolation, testing and maintenance must be performed by qualified personnel under applicable rules.

Lista de accesorios

Designación del tipo

Code Position Code Symbol Meaning & Explanation
CQ Enterprise Code: Zhejiang Chuangqi Electric Co., LTD.
M Product Category: Molded Case Circuit Breaker
5 Design Serial Number
125 Rated Frame Current (A): Options: 63, 100, 125, 250, 400, 630, 800
M Breaking Capacity Class:
• C – Basic Type     • L – Standard Type     • M – Higher Breaking Type     • H – High Breaking Type
Operation Mode:
• (No Code) – Manual Direct Operation     • Z – Rotary Handle Operation     • P – Electric Operation
4 Number of Poles:    • 3 – Three Poles     • 4 – Four Poles
300 Trip Unit & Accessories Code:
• 3 – Electronic Trip (Compound Trip)     • 2 – Magnetic Trip Only (Single Magnetic Trip)
• 00 – No Accessories (Refer to accessory table for specific codes)
Application Type:    • (No Code) – Distribution Protection     • 2 – Motor Protection
B N-Pole Type (For 4P products only, 3P has no code):
• Type A: N-pole is always connected, without overcurrent release.
• Type B: N-pole breaks with other poles, without overcurrent release.
• Type C: N-pole breaks with other poles, with overcurrent release.
• Type D: N-pole is always connected, with overcurrent release.
125A Rated Current: See technical parameter table for available values.
Terminal & Connection Type:
• (No Code) – Front Terminal Connection     • B – Rear Terminal Connection     • C – Plug-in Type

Especificaciones técnicas

Número de modelo CQM5-63 CQM5-100
Rated current of frame level Inm(A) 63 100
Rated current In(A),at 40℃ 10, 16, 20, 32, 40, 50, 63 10, 16, 20, 32, 40, 50, 63, 80, 100
Rated operating voltage Ue(V) AC380/400/415V AC380/400/415V
AC660/690V AC660/690V
Rated insulation voltage Ui (V) 1000 1000
Tensión nominal de choque soportada Uimp (kV) 8 8
Vida mecánica 20000 20000
Electrical life(AC415V) 8000 8000
Trip mechanisms and protection types Thermal-magnetic trip Thermal-magnetic trip
Selectivity category A A
Número de polos 3P 4P 3P 4P
Breaking capacity designation L M C C
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 36 55 55 40 40
AC660/690V / 12 12 12 12
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 36 40 40 30 30
AC660/690V / 10 10 10 10
Phase spacing (mm) 25 25
Arc distance (mm) ≤50 ≤50
Operating ambient temp -35℃ to +70℃ -35℃ to +70℃
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Instantaneous protection Power distribution protection In≤32A:400A; In≥40A:10In In≤32A:400A; In≥40A:10In
Electric motor protection In≤32A:400A; In≥40A:12In In≤32A:400A; In≥40A:12In
Overall dimensions
(mm) (L-W-H)
3 P 130-75-65 130-75-65
4 P 130-100-65 130-100-65

Note:● for optional accessories;”-”for no optional accessories.

Número de modelo CQM5-125 CQM5-250
Rated current of frame level Inm(A) 125 250
Rated current In(A),at 40℃ 10, 16, 20, 32, 40, 50, 63, 80, 100, 125 100, 125, 140, 160, 180, 200, 225, 250
Rated operating voltage Ue(V) AC380/400/415V AC380/400/415V
AC660/690V AC660/690V
Rated insulation voltage Ui (V) 1000 1000
Tensión nominal de choque soportada Uimp (kV) 8 8
Vida mecánica 20000 20000
Electrical life(AC415V) 8000 8000
Trip mechanisms and protection types Thermal-magnetic trip Thermal-magnetic trip
Selectivity category A A
Número de polos 3P 3P, 4P 4P 3P 3P, 4P 4P
Breaking capacity designation C L M H C L M H
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 36 50 70 100 36 50 70 100
AC660/690V / / 20 / / / 20 /
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 25 36 50 70 25 36 50 70
AC660/690V / / 10 / / / 10 /
Phase spacing (mm) 30 35
Arc distance (mm) ≤50 ≤100
Operating ambient temp -35 ℃ to +70℃ -35 ℃ to +70℃
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Instantaneous protection Power distribution protection In≤40A: 400A; In≥50A: 10In 10 en
Electric motor protection In≤40A: 400A; In≥50A: 12In 12In
Overall dimensions
(mm) (L-W-H)
3 P 155-90-75.5 165-105-75
4 P 155-120-87 165-140-100

Note:● for optional accessories;”-”for no optional accessories.

Número de modelo CQM5-400 CQM5-630
Rated current of frame level Inm(A) 400 630
Rated current In(A),at 40℃ 225, 250, 315, 350, 400 400, 500, 630
Rated operating voltage Ue(V) AC380/400/415V AC380/400/415V
AC660/690V AC660/690V
Rated insulation voltage Ui (V) 1000 1000
Tensión nominal de choque soportada Uimp (kV) 8 8
Vida mecánica 10000 1000
Electrical life(AC415V) 7000 7000
Trip mechanisms and protection types Thermal-magnetic trip Thermal-magnetic trip
Selectivity category A A
Número de polos 3P 4P 3P 3P 4P 3P
Breaking capacity designation C L M / H L M / H
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 36 50 70 70 100 50 70 70 100
AC660/690V / / 20 20 / / 20 20 /
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 36 50 70 70 75 50 70 70 75
AC660/690V / / 15 15 / / 15 15 /
Phase spacing (mm) 48 70
Arc distance (mm) ≤100 ≤100
Operating ambient temp -35℃ to +70℃ -35℃ to +70℃
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Instantaneous protection Power distribution protection 10 en 10 en
Electric motor protection 12In 12In
Overall dimensions
(mm) (L-W-H)
3 P 275-150-104.5 275-150-104.5
4 P 275-198-104.5 275-198-104.5

Note:● for optional accessories;”-”for no optional accessories.

Número de modelo CQM5-800
Rated current of frame level Inm(A) 800
Rated current In(A),at 40℃ 400, 500, 630, 700, 800
Rated operating voltage Ue(V) AC380/400/415V
AC660/690V
Rated insulation voltage Ui (V) 1000
Tensión nominal de choque soportada Uimp (kV) 8
Vida mecánica 10000
Electrical life(AC415V) 7000
Trip mechanisms and protection types Thermal-magnetic trip
Selectivity category A
Número de polos 3P 4P 3P
Breaking capacity designation L M / H
Rated ultimate short-circuit breaking capacity (Icu) (kA) AC380/400/415V 50 70 70 100
AC660/690V / 20 20 /
Rated service short-circuit breaking capacity (Ics) (kA) AC380/400/415V 50 70 70 75
AC660/690V / 15 15 /
Phase spacing (mm) 70
Arc distance (mm) ≤100
Operating ambient temp -35℃ to +70℃
Accessory Auxiliary contacts
Alarm contacts
Shunt Release
Under-Voltage Release
Motor Operating Mechanism
Manual Handle Assembly
Fixed Type Rear-Mounting Kit
Plug-in Type, Front-of-Panel
Plug-in Type, Rear-of-Panel
Mechanical Interlock
Instantaneous protection Power distribution protection 10 en
Electric motor protection 12In
Overall dimensions
(mm) (L-W-H)
3 P 280-210-112
4 P 280-280-112

Note:● for optional accessories;”-”for no optional accessories.

Dimensiones (mm)

CQM5-63/100

Front Terminal Connection Dimensions (X-X, Y-Y denote center points for 3P breakers)

CQM5-125 (C, L, M, H Types)

Front Terminal Connection Dimensions

(X-X, Y-Y denote center points for 3P breakers)

Número de modelo H(mm) H1 (mm)
CQM5-125C、125L 75.5 101.5
CQM5-125M、125H 87 113

CQM5-250 (C, L, M, H Types)

Front Terminal Connection Dimensions

(X-X, Y-Y denote center points for 3P breakers)

Número de modelo H (mm) H1 (mm)
CQM5-250C、250L 75 103.7
CQM5-250M、250H 100 128.7

CQM5-400 (C, L, M, H Types)

CQM5-630 (C, L, M, H Types)

Front Terminal Connection Dimensions (X-X, Y-Y denote center points for 3P breakers)

CQM5-800 ( L, M, H Types)

Front Terminal Connection Dimensions (X-X, Y-Y denote center points for 3breakers)

Note: Undefined tolerances comply with grade GB/T 1804-80.

¿Por qué elegir CHAC?

Con más de 30 años de experiencia en fabricación, más de 1100 empleados, más de 100 millones de postes
Con una capacidad anual y un proceso de producción automatizado 90%, CHAC ofrece una capacidad de producción estable y un estricto
control de calidad para clientes OEM/ODM globales. Nuestro sistema de fabricación interno respalda a largo plazo
Cooperación para marcas eléctricas, importadores y distribuidores.


30+

AÑOS DE EXPERIENCIA

Especializado en fabricación eléctrica de bajo voltaje


1100+

EMPLEADOS

Equipo profesional garantiza calidad y entrega estables


100M+

CAPACIDAD ANUAL DE LOS POLOS

Capacidad de producción a gran escala para satisfacer la demanda mundial


90%

PRODUCCIÓN AUTOMATIZADA

Automatización avanzada para alta eficiencia y consistencia

Línea de ensamblaje automatizada

Línea de ensamblaje automatizada

Laboratorio de pruebas

Laboratorio de pruebas

Inyección y Estampado

Inyección y Estampado

Inspección de calidad

Inspección de calidad

Certificación IEC
Certificación CE
Certificación CB
Certificación RoHS
Certificación ISO 14001

Un estricto sistema de control de calidad garantiza que cada producto cumpla con los estándares mundiales.

¿Qué podemos personalizar?

For CQM5 projects, CHAC can review private-label marking, packaging, approved appearance options, published 10–800A electrical configurations and technical-document requirements. Requests outside the published range are subject to engineering evaluation, testing, minimum order quantity and project feasibility.

Diseño de cerramiento

Recinto
Diseño

Tamaños, estructuras y detalles de instalación de recintos personalizados.

Diseño de cerramiento
Configuración interna

Interno
Configuración

Opciones flexibles de diseño interno y disposición de componentes.

Configuración interna
Marca y Logotipo

Marca e
Logo

Logotipos de marca propia, placas de identificación e identificación de marca.

Marca y Logotipo
Diseño de empaque

Empaquetado
Diseño

Soluciones de embalaje, cajas personalizadas, etiquetas y manuales.

Diseño de empaque
Configuración eléctrica

Eléctrico
Configuración

Instalación eléctrica adaptada a los requisitos de la aplicación.

Configuración eléctrica
Soporte de Certificación

Certificación
Apoyo

Soporte para estándares del mercado objetivo y requisitos de cumplimiento.

Soporte de Certificación

Descargar

PDF

Interruptor Automático de Caja Moldeada Serie CQM5

Descripción general completa de componentes eléctricos de bajo voltaje y referencia para la selección de productos.

Descargar PDF

Arriba

¿Necesita documentos técnicos?

Contáctenos para obtener hojas de datos, certificados, planos, orientación de selección o soporte para proyectos OEM/ODM.

Contáctanos

CQM5 Product FAQ

What is the CQM5 MCCB used for?

The CQM5 is specified for overload and short-circuit protection in AC 380/400/415V and AC 660/690V systems within the published 10–800A range. Suitability depends on the fault study, conductor coordination, enclosure and local rules.

How does the CQM5 molded case circuit breaker work?

The protection mechanism responds to the fault conditions stated for this model: overload and short-circuit protection. Trip behaviour, settings and interruption duty must be checked against the ordered frame and product instructions.

How do I choose the CQM5 rated current and poles?

Start with the design current and conductor calculation, then choose a published current within 10–800A and poles from 3P / 4P. Neutral treatment, fault level, ambient conditions and coordination also need review.

What breaking capacity should I check on the CQM5?

Use the declared 12–100kA Icu and 10–75kA Ics values by frame, voltage and breaking class for the exact frame, voltage and configuration. The prospective short-circuit current at the installation point must be within the applicable duty; a larger ampere value alone is not a selection rule.

Can the CQM5 replace an MCB or an earth-leakage device?

An MCCB is not automatically a like-for-like replacement. The CQM5 provides overload and short-circuit protection; residual-current protection, DC interruption, adjustable settings and other functions must be confirmed separately from the project requirement.

How should the CQM5 be installed and tested?

Use only the exact model drawing, terminal identification and accessory instructions. A qualified person should verify isolation, conductor size, torque, clearances, settings, fault duty and functional tests before energising the circuit.

Confirm the Right CQM5 Configuration

Send the frame, rated current, poles, protection function, system voltage, expected fault level, destination market and quantity. CHAC will review the request against the published model range.