Contactor de CC de alto voltaje serie STE2 (Sellado epoxi redondo)
El Contactor de CC de alto voltaje serie STE2 (Sellado epoxi redondo) is a CHAC high-voltage DC contactor for controlled DC switching and isolation. The page keeps the model-specific technical table and original product images so buyers can verify voltage, current, configuration, mounting and applicable standards before ordering. Final suitability depends on the complete circuit, installation method and destination-market rules.
Descripción del producto
STE2 Series High-voltage DC contactor (Round Epoxy Sealing) is a high-voltage DC contactor intended for controlled DC switching and isolation. The current product record identifies it for battery, charging and high-voltage DC systems. Use the exact model variant and preserved technical source as the basis for procurement rather than assuming that every family member has the same rating.
Verified source summary: Type designation Product model Working voltage Working current Load polarity Coil polarity Auxiliary contact STE2-50 1500 50 Non-polarity Non-polarity / STE2-100 1500 100 Non-polarity Non-polarity / STE2-150 1500 150 Non-polarity Non-polarity / STE2-200 1500 200 Non-polarity Non-polarity 1NO STE2-250 1500 250 Non-polarity Non-polarity 1NO STE2-300 1500 300 Non-polarity Non-polarity 1NO STE2-400 1500 400 Non-polarity
Características clave
Aplicaciones típicas
Typical use can include battery, charging and high-voltage DC systems when the project confirms system voltage, current, fault or surge exposure, conductor and enclosure requirements, and the selected variant’s installation instructions. This page does not replace the project design or the authority having jurisdiction.
Guía de Solicitudes y Selección
Use the following decision points with the preserved model data. Product-family descriptions explain intent, but the exact technical table controls the ordered variant.
| Punto de selección | Contactor de CC de alto voltaje serie STE2 (Sellado epoxi redondo) | Lo que el proyecto debe confirmar |
|---|---|---|
| Solicitud | High-Voltage DC Contactor projects | Confirm the actual system and environment |
| Selection basis | controlled DC switching and isolation | Use the exact model and technical table |
| Instalación | Follow the model instructions | Check mounting, clearances and termination |
| Cumplimiento | Use the listed standard where applicable | Verify edition, scope and destination rules |
| Adjacent product | Evaluate the related CHAC family where function differs | Do not substitute without engineering review |
Function
controlled DC switching and isolation
Match the protection or switching function to the system.
Configuración
Model-specific options
Confirm current, voltage, poles, terminals or accessories from the table.
Instalación
Mechanical and electrical fit
Check enclosure, mounting, wiring space and maintenance access.
Project evidence
Documents and test records
Retain the approved drawing, technical sheet and commissioning record.
Guía de pedidos
- State the exact model and variant.
- Provide the system voltage, current, frequency and load or protection function.
- Confirm mounting, terminals, accessories, enclosure and environmental conditions.
- Share quantity, destination market and required technical documents.
Comprobaciones de Instalación y Coordinación
- Verify the model’s ratings and connection arrangement against the project drawings.
- Check conductor, busbar, enclosure, clearances and tightening requirements using the product documentation.
- Coordinate upstream and downstream protection or control devices where applicable.
- Use qualified personnel for installation, testing, isolation and maintenance.
Designación del tipo

| Modelo de producto | Tensión de trabajo | Corriente de trabajo | Polaridad de carga | Polaridad de la bobina | Contacto auxiliar |
| STE2-50 | 1500 | 50 | Apolaridad | Apolaridad | / |
| STE2-100 | 1500 | 100 | Apolaridad | Apolaridad | / |
| STE2-150 | 1500 | 150 | Apolaridad | Apolaridad | / |
| STE2-200 | 1500 | 200 | Apolaridad | Apolaridad | 1NO |
| STE2-250 | 1500 | 250 | Apolaridad | Apolaridad | 1NO |
| STE2-300 | 1500 | 300 | Apolaridad | Apolaridad | 1NO |
| STE2-400 | 1500 | 400 | Apolaridad | Apolaridad | 1NO |
| STE2-500 | 1500 | 500 | Apolaridad | Apolaridad | 1NO |
| STE2-600 | 1500 | 600 | Apolaridad | Apolaridad | 1NO |
| STE2-800 | 1000 | 800 | Apolaridad | Apolaridad | 1NO |
Especificaciones técnicas
| Modelo de producto | STE2-50 | STE2-100 | |
| Formulario de contacto | 1H | 1H | |
| Contacto auxiliar | / | NO | |
| Polaridad de contacto | Apolaridad | Apolaridad | |
| Resistencia de contacto | ≤1mΩ(at 50A) | ≤1 mΩ (a 100 A) | |
| Tensión de funcionamiento | ≤75%Un | ≤75%Un | |
| Corriente máxima de ruptura | 50A | 100A | |
| Resistencia eléctrica | 12~1500V | 12~1500V | |
| Corriente máxima de ruptura | 500A(320V DC) | 1000A(320V DC) | |
| Resistencia eléctrica | ≥1×10³ times(50A/750VDC) ≥400 times(20A/1000VDC) ≥150 times(10A/1500VDC) |
≥2×10³ times(100A/750VDC) ≥1×10³ times(100A/1000VDC) ≥600 times(15A/1500VDC) |
|
| Transporte de corriente | 50A: Continuo para 100A:10min 200A:50s |
100A: Continuo para 150A:10min 300A:50s |
|
| Tensión soportada dieléctrica | Entre contactos abiertos | 3500VAC | 3500VAC |
| Entre bobinas de contacto | 3500VAC | 3500VAC | |
| Resistencia Mecánica | 2×10⁵ veces | 2×10⁵ veces | |
| Voltaje de la bobina | 12V, 24V | 12V,24V,48V | |
| Consumo de energía de la bobina | 12V:5.5W 24V:6W | 12V:5.5W 24V:6.0W | |
| Método de extracción de carga | Hilo interno | Hilo interno | |
| Método de salida de la bobina | cable conductor | cable conductor | |
| Peso | About 115g | About 160g | |
| Vibrar | 80Hz~2000Hz 49m/s² | 80Hz~2000Hz 49m/s² | |
| Humedad | 5%~95%RH | 5%~95%RH | |
| Rango de humedad | -45℃~+85℃ | -45℃~+85℃ | |
| Dimensiones externas (mm) | 51.6×35.6×43.2 | 53.8×35.6×58.5 | |
Nota:
1. Los parámetros anteriores son todos valores iniciales, medidos a una temperatura ambiente de 23 ℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Modelo de producto | STE2-150 | STE2-200 | STE2-250 | |
| Formulario de contacto | 1H | 1H | 1H | |
| Contacto auxiliar | NO | NO | NO | |
| Polaridad de contacto | Apolaridad | Apolaridad | Apolaridad | |
| Resistencia de contacto | ≤1mΩ(at 150A) | ≤1mΩ(at 200A) | ≤1mΩ(at 250A) | |
| Tensión de funcionamiento | ≤75%Un | ≤75%Un | ≤75%Un | |
| Corriente máxima de ruptura | 150A | 200A | 250 A | |
| Resistencia eléctrica | 12~1500V | 12~1500V | 12~1500V | |
| Corriente máxima de ruptura | 1000A(320VDC) | 2000A(320VDC) | 2000A(320VDC) | |
| Resistencia eléctrica | ≥2×10³ times(100A/750VDC) ≥1×10³ times(150A/1000VDC) ≥600 times(30A/1500VDC) |
≥2×10³ times(200A/750VDC) ≥1×10³ times(200A/1000VDC) ≥1×10³ times(50A/1500VDC) |
≥2×10³ times(250A/750VDC) ≥1×10³ times(250A/1000VDC) ≥1×10³ times(50A/1500VDC) |
|
| Transporte de corriente | 150A: Continuo por 180A:10min 300A:50s |
200A: Continuo para 300A:10min 400A:180s |
250A: Continuo para 300A:10min 400A:180s |
|
| Tensión soportada dieléctrica | Entre contactos abiertos | 3500VAC | 3500VAC | 3500VAC |
| Entre bobinas de contacto | 3500VAC | 3500VAC | 3500VAC | |
| Resistencia Mecánica | 2×10⁵ veces | 2×10⁵ veces | 2×10⁵ veces | |
| Voltaje de la bobina | 12V,24V,36V,48V | 12V,24V,36V,48V | 12V,24V,36V,48V | |
| Consumo de energía de la bobina | 12V,24V,48V:5.76W 36V:2.5W | 6W | 6W | |
| Método de extracción de carga | Rosca externa | Rosca externa | Rosca externa | |
| Método de salida de la bobina | cable conductor | cable conductor | cable conductor | |
| Peso | About 430g | About 430g | About 430g | |
| Vibrar | 80Hz~2000Hz 49m/s² | 80Hz~2000Hz 49m/s² | 80Hz~2000Hz 49m/s² | |
| Humedad | 5%~95%RH | 5%~95%RH | 5%~95%RH | |
| Rango de humedad | -45℃~+85℃ | -45℃~+85℃ | -45℃~+85℃ | |
| Dimensiones externas (mm) | 53.8×35.2×59.5 | 80.5×63.6×73.8 | 80.5×63.6×73.8 | |
Nota:
1. Los parámetros anteriores son todos valores iniciales, medidos a una temperatura ambiente de 23 ℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Modelo de producto | STE2-300 | STE2-400 | |
| Formulario de contacto | 1H | 1H | |
| Contacto auxiliar | NO | NO | |
| Polaridad de contacto | Apolaridad | Apolaridad | |
| Resistencia de contacto | ≤1mΩ(at 300A) | ≤1mΩ(at 400A) | |
| Tensión de funcionamiento | ≤75%Un | ≤75%Un | |
| Corriente máxima de ruptura | 300A | 400A | |
| Resistencia eléctrica | 12~1500V | 12~1500V | |
| Corriente máxima de ruptura | 2000A(320V DC) | 2500A(320V DC) | |
| Resistencia eléctrica | ≥2×10³ times(300A/750VDC) ≥1×10³ times(300A/1000VDC) ≥1×10³ times(80A/1500VDC) |
≥3×10³ times(400A/750VDC) ≥1×10³ veces (400A/1000VDC) ≥1×10³ times(200A/1500VDC) |
|
| Transporte de corriente | 300A: Continuo durante 350A:10min 400A:180s |
400A: Continuo durante 500A:10min 600A:180s |
|
| Tensión soportada dieléctrica | Entre contactos abiertos | 3500VAC | 3500VAC |
| Entre bobinas de contacto | 3500VAC | 3500VAC | |
| Resistencia Mecánica | 2×10⁵ veces | 2×10⁵ veces | |
| Voltaje de la bobina | 12V,24V,36V,48V | 12V,24V,36V | |
| Consumo de energía de la bobina | 6W | 3W | |
| Método de extracción de carga | Rosca externa | Rosca externa | |
| Método de salida de la bobina | cable conductor | cable conductor | |
| Peso | About 430g | About 990g | |
| Vibrar | 80Hz~2000Hz 49m/s² | 80Hz~2000Hz 49m/s² | |
| Humedad | 5%~95%RH | 5%~95%RH | |
| Rango de humedad | -45℃~+85℃ | -45℃~+85℃ | |
| Dimensiones externas (mm) | 80.5×63.6×73.8 | 66.6×78.1×104.5 | |
Nota:
1. Los parámetros anteriores son todos valores iniciales, medidos a una temperatura ambiente de 23 ℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Modelo de producto | STE2-500 | STE2-600 | STE2-800 | |
| Formulario de contacto | 1H | 1H | 1H | |
| Contacto auxiliar | NO | NO | NO | |
| Polaridad de contacto | Apolaridad | Apolaridad | Apolaridad | |
| Resistencia de contacto | ≤1mΩ(at 500A) | ≤1mΩ(at 600A) | ≤1mΩ(at 800A) | |
| Tensión de funcionamiento | ≤75%Un | ≤75%Un | ≤75%Un | |
| Corriente máxima de ruptura | 500A | 600A | 800A | |
| Resistencia eléctrica | 12~1500V | 12~1500V | 12~1500V | |
| Corriente máxima de ruptura | 2500A(320VDC) | 2500A(320V DC) | 2500A(320V DC) | |
| Resistencia eléctrica | ≥2×10³ times(500A/750VDC) ≥1×10³ times(500A/1000VDC) ≥1×10³ times(250A/1500VDC) |
≥2×10³ times(600A/750VDC) ≥1×10³ times(600A/1000VDC) ≥1×10³ times(300A/1500VDC) |
≥600 times(800A/750VDC) ≥1×10³ times(450A/1000VDC) ≥200 times(350A/1500VDC) |
|
| Transporte de corriente | 500A:Continuous for 550A:10min 600A:180s |
600A: Continuo por 650A:10min 700A:180s |
800A:Continuous for 900A:10min 1000A:120s |
|
| Tensión soportada dieléctrica | Entre contactos abiertos | 3500VAC | 3500VAC | 3500VAC |
| Entre bobinas de contacto | 3500VAC | 3500VAC | 3500VAC | |
| Resistencia Mecánica | 2×10⁵ veces | 2×10⁵ veces | 2×10⁵ veces | |
| Voltaje de la bobina | 12V,24V,36V | 12V,24V,36V | 12V,24V,36V | |
| Consumo de energía de la bobina | 3W | 3W | 3W | |
| Método de extracción de carga | Rosca externa | Rosca externa | Rosca externa | |
| Método de salida de la bobina | cable conductor | cable conductor | cable conductor | |
| Peso | About 990g | About 990g | About 990g | |
| Vibrar | 80Hz~2000Hz 49m/s² | 80Hz~2000Hz 49m/s² | 80Hz~2000Hz 49m/s² | |
| Humedad | 5%~95%RH | 5%~95%RH | 5%~95%RH | |
| Rango de humedad | -45℃~+85℃ | -45℃~+85℃ | -45℃~+85℃ | |
| Dimensiones externas (mm) | 66.6×78.1×104.5 | 66.6×78.1×104.5 | 66.6×78.1×104.5 | |
Nota:
1. Los parámetros anteriores son todos valores iniciales, medidos a una temperatura ambiente de 23 ℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
¿Por qué elegir CHAC?
Con más de 30 años de experiencia en fabricación, más de 1100 empleados, más de 100 millones de postes
Con una capacidad anual y un proceso de producción automatizado 90%, CHAC ofrece una capacidad de producción estable y un estricto
control de calidad para clientes OEM/ODM globales. Nuestro sistema de fabricación interno respalda a largo plazo
Cooperación para marcas eléctricas, importadores y distribuidores.
30+
AÑOS DE EXPERIENCIA
Especializado en fabricación eléctrica de bajo voltaje
1100+
EMPLEADOS
Equipo profesional garantiza calidad y entrega estables
100M+
CAPACIDAD ANUAL DE LOS POLOS
Capacidad de producción a gran escala para satisfacer la demanda mundial
90%
PRODUCCIÓN AUTOMATIZADA
Automatización avanzada para alta eficiencia y consistencia

Línea de ensamblaje automatizada

Laboratorio de pruebas

Inyección y Estampado

Inspección de calidad





Un estricto sistema de control de calidad garantiza que cada producto cumpla con los estándares mundiales.
¿Qué podemos personalizar?
CHAC admite la personalización del voltaje de la bobina y la configuración de los contactos auxiliares.,
parámetros eléctricos, marca del producto, diseño de envasado y desarrollo de ingeniería según los equipos y requisitos de mercado de los clientes.
Voltaje de la bobina
Opciones de voltaje de bobina de CA y CC adaptadas a los requisitos de la aplicación.

Contactos Auxiliares
Combinaciones flexibles de contactos auxiliares para diferentes funciones de control.

Parámetros eléctricos
Las clasificaciones actuales, los rangos de protección y los parámetros funcionales se pueden personalizar.

Marca de producto
Logotipos de marca privada, placas de identificación y soporte para la identificación de productos.

Diseño de empaque
Soluciones de embalaje, cajas personalizadas, etiquetas y manuales.

Desarrollo de Ingeniería
Soporte desde la optimización de dibujos hasta el desarrollo de productos y la adaptación de aplicaciones.

Descargar
Contactor de CC de alto voltaje serie STE
Descripción general completa de componentes eléctricos de bajo voltaje y referencia para la selección de productos.
¿Necesita documentos técnicos?
Contáctenos para obtener hojas de datos, certificados, planos, orientación de selección o soporte para proyectos OEM/ODM.
STE2 Product FAQ
What is the STE2 used for?
It is a high-voltage DC switching device for the system and variant shown in the technical table. Confirm the working voltage, current, polarity and load category.
Why does DC contactor polarity matter?
Some variants specify load or coil polarity because DC arc management and magnetic blowout depend on the internal design. Follow the marked polarity.
How do I select the voltage and current?
Use the actual steady, inrush and breaking current, system voltage, duty cycle and fault-clearing strategy. The family range is not a blanket rating for every variant.
What does ceramic or epoxy sealing change?
The sealing construction is part of the product design and environmental suitability. Compare the exact datasheet for temperature, insulation and endurance.
Can it switch a battery or charger circuit?
It may be suitable when the variant's DC voltage, current, breaking duty and insulation data match the application. Confirm the complete design.
What should be tested before energizing?
Check coil operation, contact resistance, insulation, polarity, pre-charge or discharge sequence and the emergency isolation procedure.
Confirm the Right STE2 Configuration
Send the exact model, operating conditions, quantity, destination market and required documents. CHAC will review the request against the published product data.