Perhitungan Pemilihan Kontaktor — AC-1 / AC-3

Hitung arus kontak AC dan bandingkan beban AC tiga fasa dengan tabel arus CHAC CQC6 dan motor-kW pada tegangan 230, 400 atau 690 V.

CQC6 AC contactor ratings

Published AC-3 operational current and controlled three-phase squirrel-cage motor power. The voltage groups below retain the labels used in the CHAC product table.

Reference data. Calculate to highlight the matching row.

Scroll horizontally on small screens to read all columns.

CQC6 AC-3 current and motor-power ratings
Nomor model220V/230V380V/400V660V/690V
AC-3 Ie (A)Motor power (kW)AC-3 Ie (A)Motor power (kW)AC-3 Ie (A)Motor power (kW)
CQC6 -661.562.24.83
CQC6 -992946.65.5
CQC6 -12123.5125.58.97.5
CQC6 -18184187.51210
CQC6 -2525625111815
CQC6 -32327.5321520.218.5
CQC6 -383893818.520.218.5
CQC6 -4040114018.53430
CQC6 -50501550223933
CQC6 -656518.565304237
CQC6 -80802280374945
CQC6 -95952595454945

Reading this reference

  • The calculator uses the 230, 400 or 690 V selection within the corresponding published voltage group.
  • This table covers AC-3 only. The separate conventional free-air thermal current row is not an AC-1 operational Ie selection table.
  • Confirm the exact coil supply, switching duty and installation conditions in the product documentation.

Source: CHAC CQC6 product technical table (buka di tab baru)

Source checked: . This is the retrieval date, not a standard edition or product revision date.

Contoh aplikasi · Masukan ilustratif

Matching a 15 kW motor to both CQC6 AC-3 columns

For a pump-control example, enter 15 kW shaft output, 400 V, AC-3 duty and an illustrative 28 A nameplate current, with no added current allowance. The calculator shortlists CQC6-32: the CHAC table lists 32 A and 15 kW in the 380V/400V group. CQC6-25 is below both requirements at 25 A and 11 kW. This is why checking only the model’s ampere value can be misleading. Use the table match to continue the selection, then confirm the coil supply, switching duty, installation conditions and required protection for the actual motor circuit.

Data produk: Produsen Kontaktor AC Industri Seri CQC6 OEM