مرحلة الحمل الزائد الحراري من سلسلة CQR2
ال مرحلة الحمل الزائد الحراري من سلسلة CQR2 is a CHAC thermal overload relay for adjustable motor overload protection. The page keeps the model-specific technical table and original product images so buyers can verify voltage, current, configuration, mounting and applicable standards before ordering. Final suitability depends on the complete circuit, installation method and destination-market rules.
Product Overview
CQR2 Series Thermal overload relay is a thermal overload relay intended for adjustable motor overload protection. The current product record identifies it for motor starters, fans and pump control. Use the exact model variant and preserved technical source as the basis for procurement rather than assuming that every family member has the same rating.
Verified source summary: Type designation Selection Guide Instructions for Use CQR2 Series Thermal Overload Relay Panel Symbols and Functional Button Description Trip Test (Performed BEFORE energizing the main circuit): Open the cover. Press the test button with a screwdriver. The NC contacts will open and the NO contacts will close. The status change can be observed through the indicator window (yellow mark visible indicates tripped state;
Key Features
Typical Applications
Typical use can include motor starters, fans and pump control when the project confirms system voltage, current, fault or surge exposure, conductor and enclosure requirements, and the selected variant’s installation instructions. This page does not replace the project design or the authority having jurisdiction.
Applications and Selection Guide
Use the following decision points with the preserved model data. Product-family descriptions explain intent, but the exact technical table controls the ordered variant.
| Selection point | مرحلة الحمل الزائد الحراري من سلسلة CQR2 | What the project must confirm |
|---|---|---|
| تطبيق | Thermal Relay projects | Confirm the actual system and environment |
| Selection basis | adjustable motor overload protection | Use the exact model and technical table |
| Installation | Follow the model instructions | Check mounting, clearances and termination |
| Compliance | Use the listed standard where applicable | Verify edition, scope and destination rules |
| Adjacent product | Evaluate the related CHAC family where function differs | Do not substitute without engineering review |
Function
adjustable motor overload protection
Match the protection or switching function to the system.
إعدادات
Model-specific options
Confirm current, voltage, poles, terminals or accessories from the table.
Installation
Mechanical and electrical fit
Check enclosure, mounting, wiring space and maintenance access.
Project evidence
Documents and test records
Retain the approved drawing, technical sheet and commissioning record.
Ordering Guide
- State the exact model and variant.
- Provide the system voltage, current, frequency and load or protection function.
- Confirm mounting, terminals, accessories, enclosure and environmental conditions.
- Share quantity, destination market and required technical documents.
Installation and Coordination Checks
- Verify the model’s ratings and connection arrangement against the project drawings.
- Check conductor, busbar, enclosure, clearances and tightening requirements using the product documentation.
- Coordinate upstream and downstream protection or control devices where applicable.
- Use qualified personnel for installation, testing, isolation and maintenance.
تعيين النوع

دليل الاختيار

تعليمات الاستخدام
رموز لوحة مرحلة الحماية الحرارية الزائدة من سلسلة CQR2 وصفحة الأزرار الوظيفية

اختبار التعثر (يُجرى قبل تنشيط الدائرة الرئيسية):
افتح الغطاء. اضغط على زر الاختبار باستخدام مفك براغي. ستفتح نقاط التوصيل المغلقة (NC) وتغلق نقاط التوصيل المفتوحة (NO). يمكن ملاحظة تغيير الحالة من خلال نافذة المؤشر (العلامة الصفراء المرئية تشير إلى حالة التعثر؛ العلامة المخفية تشير إلى حالة إعادة الضبط - انظر الرسم التوضيحي أعلاه).
إعداد وضع إعادة الضبط (يتم إجراؤه قبل تنشيط الدائرة الرئيسية):
يُغادر المرحل (الريليه) المصنع مضبوطاً على وضع إعادة الضبط اليدوي. لتحديد وضع إعادة الضبط التلقائي، اضغط مع الاستمرار على زر إعادة الضبط أثناء تدويره في اتجاه عقارب الساعة بمقدار 90 درجة. لا يُنصح بتغيير وضع إعادة الضبط بينما تكون الدائرة الكهربائية تحت الجهد وتعمل.
ضبط التيار الحالي (يُنفذ قبل تنشيط الدائرة الرئيسية):
يترك المرحل المصنع مضبوطاً على الحد الأدنى لتيار الضبط. لاختيار قيمة تيار ضبط مختلفة، افتح الغطاء وأدر قرص ضبط التيار باستخدام مفك براغي. قم بمحاذاة السهم الموجود على القرص مع قيمة التيار المقابلة لتيار الحمل الكامل للمحرك المراد حمايته.
إيقاف الطوارئ
اضغط على زر التوقف. يؤدي الضغط على زر التوقف إلى فتح نقاط التلامس المغلقة (NC) فقط؛ ولا يؤثر على نقاط التلامس المفتوحة (NO). يؤدي تحرير زر التوقف إلى إعادة ضبط نقاط التلامس المغلقة (NC).
الأبعاد (مم)
CQR2-25

CQR2-38

CQR2-95

المواصفات الفنية
| طراز المنتج | CQR2-25 | CQR2-38 | CQR2-95 | ||
| التقييم الحالي | 25 | 38 | 95 | ||
| جهد العزل المقدر فولت | 690 | 690 | 690 | ||
| جهد التحمل نبضياً المقدر V | 6000 | 6000 | 6000 | ||
| درجة حماية الغلاف | IP20 (الجانب الأمامي) | IP20 (الجانب الأمامي) | IP20 (الجانب الأمامي) | ||
| حماية ضد فقدان الوجه | ● | ● | ● | ||
| إعادة تعيين يدوية وتلقائية | ● | ● | ● | ||
| تعويض درجات الحرارة | ● | ● | ● | ||
| إشارة الفصل | ● | ● | ● | ||
| زر الاختبار | ● | ● | ● | ||
| زر الإيقاف | ● | ● | ● | ||
| طريقة التثبيت | قَابِلٌ لِلْإِدْرَاج | قَابِلٌ لِلْإِدْرَاج | قَابِلٌ لِلْإِدْرَاج | ||
| نقاط تلامس مساعدة | مفتوح عادةً + مغلق عادةً | مفتوح عادةً + مغلق عادةً | مفتوح عادةً + مغلق عادةً | ||
| تيار مقنن AC-15 220V بـ A | 2.73 | 2.73 | 2.73 | ||
| AC-15380V التيار المقنن A | 1.58 | 1.58 | 1.58 | ||
| تيار مقنن DC-13220V أمبير | 0.2 | 0.2 | 0.2 | ||
| مقطع الموصل (مم²) | الدائرة الرئيسية | سلك أحادي النواة أم سلك مجدول | 1 ~ 4 | 6~10 | 6~35 |
| مسمار توصيل الأسلاك | إم 4 | إم 4 | M10 | ||
| Auxiliary circuit | سلك أحادي النواة أم سلك مجدول | 1 ~ 2.5 | 1~2.5 | 1-2.5 | |
| مسمار توصيل الأسلاك | M3.5 | M3.5 | M3.5 | ||
Tripping Characteristics
| Item | No. | Setting Current Multiple | Operating Time | Purpose / Test Condition | |
| Overload Protection | 1 | 1.05 | No operation within 2 hours | Starting from Cold State | |
| 2 | 1.2 | Operation within 2 hours | Starting from Hot State (after Item 1) | ||
| 3 | 1.5 | Operation within 2 minutes | Starting after reaching thermal equilibrium at setting current | ||
| 4 | 7.2 | 2S<TP≤10S | Starting from Cold State | ||
| Phase Failure Protection | 5 | Any Two Phases | One Phase | No operation within 2 hours | Starting from Cold State |
| 1 | 0.9 | ||||
| 6 | 1.15 | 0 | Operation within 2 hours | Starting from Hot State (after Item 5) | |
Adjustable Trip Setting Range
| طراز المنتج | Current adjustment range RC(A) | Plug-in contactors | Short-circuit protection fuse (A) | |
| aM | gG | |||
| CQR2-25 | 0.1~0.16 | CQC6(SM/KMNC1)-09 CQC6(SM/KMNC1)-12 CQC6(SM/KMNC1)-18 CQC6(SM/KMNC1)-25 |
0.25 | 2 |
| 0.16~0.25 | 0.5 | 2 | ||
| 0.25~0.40 | 1 | 2 | ||
| 0.40~0.63 | 1 | 2 | ||
| 0.63~1 | 2 | 4 | ||
| 1~1.6 | 2 | 4 | ||
| 1.6~2.5 | 4 | 6 | ||
| 2.5~4 | 6 | 10 | ||
| 4~6 | 8 | 16 | ||
| 5.5-8 | 12 | 20 | ||
| 7~10 | 12 | 20 | ||
| 9~13 | 16 | 25 | ||
| 12~18 | 20 | 35 | ||
| 17-25 | 25 | 50 | ||
| CQR2-38 | 23-32 | CQC6(SM/KMNC1)-32 | 40 | 63 |
| 30~38 | 40 | 80 | ||
| CQR2-95 | 17~25 | CQC6(SM/KMNC1)-40 CQC6(SM/KMNC1)-50 CQC6(SM/KMNC1)-65 CQC6(SM/KMNC1)-80 CQC6(SM/KMNC1)-95 |
25 | 50 |
| 23~32 | 40 | 63 | ||
| 30~40 | 40 | 100 | ||
| 37~50 | 63 | 100 | ||
| 48~65 | 63 | 100 | ||
| 55~70 | 80 | 125 | ||
| 63~85 | 80 | 125 | ||
| 80~95 | 100 | 160 | ||
Accessories Description
| تطبيق | Model number | تطبيق |
| MB-1 | Combined with M12 to form an independent mounting product | |
![]() |
MB-2 | Combined with M25 to form an independent mounting product |
![]() |
MB-3 | Combined with M38 to form an independent mounting product |
![]() |
MB-4 | Combined with M95 to form an independent mounting product |
لماذا تختار CHAC
مع خبرة تصنيع تزيد عن 30 عامًا، وأكثر من 1100 موظف، وأكثر من 100 مليون عمود
بفضل طاقتها الإنتاجية السنوية ونظام الإنتاج الآلي 90%، توفر شركة CHAC طاقة إنتاجية مستقرة ومعايير صارمة
مراقبة الجودة لعملاء OEM/ODM العالميين. يدعم نظام التصنيع الداخلي الخاص بنا على المدى الطويل
تعاون مع العلامات التجارية الكهربائية والمستوردين والموزعين.
30+
سنوات الخبرة
متخصص في تصنيع المعدات الكهربائية منخفضة الجهد
1100+
الموظفين
فريق محترف يضمن جودة ثابتة والتسليم
١٠٠ مليون+
السعة السنوية للأعمدة
قدرة إنتاجية واسعة النطاق لتلبية الطلب العالمي
90%
الإنتاج الآلي
الأتمتة المتقدمة لتحقيق كفاءة واتساق عاليين

خط التجميع الآلي

مختبر اختبار

حقن وختم

فحص الجودة





نظام صارم لمراقبة الجودة يضمن أن كل منتج يلبي المعايير العالمية.
ما الذي يمكننا تخصيصه؟
تدعم تشاك تخصيص جهد الملف وتكوين نقاط التلامس المساعدة،,
المعلمات الكهربائية، والعلامة التجارية للمنتج، وتصميم التعبئة والتغليف، والتطوير الهندسي وفقاً لمعدات العملاء ومتطلبات السوق.
جهد الملف
خيارات جهد ملف التيار المتردد وتيار مستمر مصممة لتناسب متطلبات التطبيق.

ملامسات مساعدة
مجموعات اتصالات مساعدة مرنة لوظائف تحكم مختلفة.

المعاملات الكهربائية
يمكن تخصيص التصنيفات الحالية، ونطاقات الحماية، والمعلمات الوظيفية.

علامة تجارية للمنتج
شعارات الملصقات الخاصة، ولوحات الأسماء، ودعم تعريف المنتج.

تصميم عبوات
علب مخصصة، وملصقات، وأدلة، وحلول تغليف.

التطوير الهندسي
الدعم من تحسين الرسم إلى تطوير المنتج وتطابق التطبيقات.

تنزيل
مرحل الحمل الزائد الحراري سلسلة CQR2
نظرة عامة كاملة على مكونات كهربائية منخفضة الجهد ومرجع لاختيار المنتج.
هل تحتاج إلى وثائق فنية؟
اتصل بنا للحصول على أوراق البيانات، والشهادات، والرسومات، وإرشادات الاختيار، أو دعم مشاريع OEM/ODM.
CQR2 Product FAQ
What does the CQR2 protect?
It provides adjustable thermal overload protection for compatible AC motor starters. It is not a replacement for short-circuit protection.
How do I choose the relay range?
Select a range that contains the motor's rated current, then set it from the nameplate and installation conditions.
What is manual versus automatic reset?
Manual reset requires an intentional reset after a trip. Automatic reset can restart the control sequence when permitted by the machine risk assessment.
Does it detect phase failure?
The product record includes phase-failure protection. Confirm the exact variant, motor connection and test procedure.
Can it connect to a CQC6 contactor?
The page identifies CQC6 integration as an application. Confirm the mechanical interface and current range for the selected combination.
What should be recorded after testing?
Record the set current, trip test result, reset mode, auxiliary-contact operation and responsible technician.
Confirm the Right CQR2 Configuration
Send the exact model, operating conditions, quantity, destination market and required documents. CHAC will review the request against the published product data.