Công tắc cách ly khung DC dòng CQW5NEDZ

The CHAC CQW5NEDZ DC frame isolation switch provides switching and isolation for photovoltaic and energy-storage main circuits. Three frame sizes cover rated currents from 400A to 4000A at 1500V DC; select the frame and utilization category for the application.

Các mẫu:
CQW5NEDZ-1600 / CQW5NEDZ-2500 / CQW5NEDZ-4000
Người Ba Lan:
2P
Định mức dòng điện:
400–4000A, depending on frame
Điện áp định mức:
1500V DC
Rated Impulse Withstand Voltage:
15kV (1600/2500 frame); 18kV (4000 frame)
Utilization Category:
DC-22A / DC-PV2 (1600 frame); DC-23A / DC-PV2 (2500/4000 frames)
Tiêu chuẩn
IEC 60947-3 / GB/T 14048.3
Tùy chỉnh:
Dịch vụ OEM/ODM trọn gói

Giới thiệu sản phẩm

CHAC CQW5NEDZ DC frame isolation switch serves higher-current DC main-circuit applications. Its 1600A, 2500A and 4000A frames operate at 1500V DC, with frame-specific utilization categories and short-time withstand ratings.

Đối với các nhà nhập khẩu, nhà phân phối và nhà sản xuất thiết bị, CHAC có thể xem xét cấu hình yêu cầu dựa trên các yêu cầu về mạch điện và tài liệu thị trường đích. Hai bên sẽ thống nhất về mẫu mã, bản vẽ và yêu cầu về đánh dấu trước khi phê duyệt mẫu hoặc đặt hàng lại.

Các điểm lựa chọn chính

  • Frame and current: 1600 / 2500 / 4000A frames; listed currents across 400–4000A. Use the available current steps for the selected frame.
  • Voltage and poles: 1500V DC; 2P. Confirm the layout and connection arrangement.
  • Utilization category: 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2. Do not transfer one frame’s switching duty to another.
  • One-second withstand: 1600: 50kA; 2500: 85kA; 4000: 100kA. Keep the frame and duration with the current rating when coordinating protection.

Các ứng dụng điển hình

Evaluate CQW5NEDZ for PV and energy-storage DC main circuits requiring switching and isolation. Coordinate the complete assembly with its fault-protection design, control supplies and installation conditions; an isolation switch is not an automatic overcurrent breaker.

Hướng dẫn đăng ký và tuyển chọn

Mục lựa chọn CQW5NEDZ configuration Những điều cần xác minh
Khung hình và hiện tại 1600 / 2500 / 4000A frames; listed currents across 400–4000A Use the available current steps for the selected frame.
Voltage and poles 1500V DC; 2P Confirm the layout and connection arrangement.
Utilization category 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 Do not transfer one frame’s switching duty to another.
One-second withstand 1600: 50kA; 2500: 85kA; 4000: 100kA Keep the frame and duration with the current rating when coordinating protection.

Use these checks to compare the protection function, configuration and related CHAC products before specifying CQW5NEDZ. Related products are selection alternatives or system components, not automatic replacements.

So sánh CQD5NEZ với chức năng cần thiết

Công tắc cách ly CHAC CQD5NEZ DC được thiết kế để cách ly mạch điện ở mức điện áp lên đến 1500V DC. Hai kích thước khung bao gồm dòng điện định mức từ 80A đến 630A, với chế độ hoạt động phía trước hoặc phía bên để phù hợp với bố trí thiết bị.

Sản phẩm liên quanThiết kế hệ thốngKiểm tra sự tương thích

Compare CQM5NEZ for the required function

Bộ ngắt mạch dạng vỏ bọc CHAC CQM5NEZ DC có sẵn với các thiết bị khởi động chỉ dùng từ tính hoặc từ tính nhiệt cho các mạch DC 1500V. Chọn phiên bản từ tính khi cần bảo vệ quá tải và ngắn mạch. Các khung 350A và 630A có khả năng bảo vệ dòng điện từ 63A đến 630A, với công suất ngắt được xác định theo khung và phiên bản M/H.

Sản phẩm liên quanThiết kế hệ thốngKiểm tra sự tương thích

Need Help Specifying CQW5NEDZ?

Gửi yêu cầu về mạch điện, cấu hình được chọn, thị trường đích và số lượng cho việc đánh giá cụ thể về từng mẫu sản phẩm.

Yêu cầu báo giá

Match the frame to switching and fault-withstand duty

The three frames differ in more than current. Compare utilization category, short-time withstand duty, dimensions and connection spacing. The 100kA/1s value belongs to the 4000 frame and must not be generalized across the range.

Define the control supplies before cabinet wiring

State the voltages for the motor mechanism, closing and release functions and the required signaling. Where control voltages differ, follow the separate-supply requirements in the approved drawing. Confirm the ready-to-close and interlock logic before commissioning.

How to Specify a CQW5NEDZ Order

Hãy sử dụng các thông tin cấu hình dưới đây trong thông số mua hàng. Hãy lưu giữ bản vẽ đã phê duyệt cùng thông tin nhận dạng sản phẩm trong đơn hàng để có thể kiểm tra các đơn hàng lặp lại một cách thống nhất.

Chi tiết đơn hàng Thông tin cần bao gồm
Khung hình và hiện tại 1600 / 2500 / 4000A frames; listed currents across 400–4000A — Use the available current steps for the selected frame.
Voltage and poles 1500V DC; 2P — Confirm the layout and connection arrangement.
Utilization category 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 — Do not transfer one frame’s switching duty to another.
One-second withstand 1600: 50kA; 2500: 85kA; 4000: 100kA — Keep the frame and duration with the current rating when coordinating protection.
Dự án và tài liệu Cung cấp tài liệu về ứng dụng, điều kiện lắp đặt và yêu cầu thị trường đích.
Số lượng và nhận dạng Bày trình số lượng, yêu cầu mẫu, ngôn ngữ đóng gói và bất kỳ thương hiệu nào được đề xuất; xác nhận tính khả thi trước khi phê duyệt.

Kiểm tra sự phù hợp của việc lắp đặt trước khi phê duyệt

  • Use the CQW5NEDZ dimension drawing to verify mounting, terminal access, operating clearance and conductor bending space.
  • Xác nhận việc chuẩn bị dây dẫn, khả năng tương thích với thiết bị đầu cuối và hướng dẫn thắt chặt để có cấu hình chính xác. Bảng tham chiếu dây dẫn không thay thế quy cách cáp dự án.
  • Đánh giá nhiệt độ, điều kiện bảo vệ và sự bố trí bảo vệ với nhà thiết kế thiết bị. Không nên kết luận về khả năng tương thích chỉ dựa trên tên của mẫu tương tự.
  • Phải có nhân viên có đủ trình độ lắp đặt và kiểm tra thiết bị theo hướng dẫn của mô hình và các quy trình kiểm tra và cách ly áp dụng.

Tên loại

Không. Mã Mô tả
① CQ Mã công ty
② W Frame-Type Switch
③ 5 Mã thiết kế
④ NEDZ Năng lượng mới – DC
⑤ 1600 / 2500 / 4000 Kích thước khung hình
⑥ 2 Số lượng người Ba Lan: 2P
⑦ □ Định mức dòng điện
⑧ □ Control Voltage
⑨ □ Fixed Type

Điều kiện hoạt động

Ambient Temperature -40℃ to +70℃
24-hour Average Temperature ≤+35℃
Normal Operating Altitude ≤5000m
Độ ẩm tương đối ≤50% at +40℃
Max. Monthly Average Relative Humidity 0.9
Corresponding Monthly Average Min. Temperature +25℃
Installation Position Vertical
Installation Inclination ≤5°
Mức độ ô nhiễm 3
Installation Category – Main Circuit IV
Installation Category – Auxiliary / Control Circuit III
Degree of Protection IP30 / IP40 (IP40 when installed in a cabinet compartment with a door frame.)
Utilization Category 1600A:DC-22A / DC-PV2 2500A,4000A:DC-23A / DC-PV2

Đặc điểm kỹ thuật

Tham số CQW5NEDZ-1600 CQW5NEDZ-2500 CQW5NEDZ-4000
Frame size (A) 1600 2500 4000
Dòng điện định mức (A) 400, 630, 800, 1000, 1250, 1600 800, 1000, 1250, 1600, 2000, 2500 800, 1000, 1250, 1600, 2000, 2500, 2800, 2900, 3200, 3600, 4000
Number of poles 2P 2P 2P
Rated operational voltage Ue (V) DC1500 DC1500 DC1500
Rated insulation voltage Ui (V) 2000 2500 2500
Rated impulse withstand voltage Uimp (kV) 15 15 18
Pole spacing (mm) 80 95 115
Rated short-circuit making capacity Icm (kA) 50 85 100
Rated short-time withstand current Icw 50 kA/1 s, 120 kA/0.1 s 85 kA/1 s, 150 kA/0.2 s 100 kA/1 s, 160 kA/0.2 s
Utilization category DC-22A, DC-PV2 DC-23A, DC-PV2 DC-23A, DC-PV2
Total breaking time, without intentional delay (ms) — ≤25 ≤25
Closing time (ms) ≤70 ≤70 ≤70
Electrical endurance (cycles) 500 500 (DC-23A); 1,500 (DC-PV2) 500 (DC-23A); 1,500 (DC-PV2)
Mechanical endurance maintenance-free (cycles) 10000 15000 15000
Mechanical endurance with maintenance (cycles) — 25000 25000
Temperature rise at a reference ambient temperature of 50°C (K) — <50 <50
Arcing distance (mm) — 0 0
Installation type Fixed type Fixed type Fixed type
Connection type — Horizontal connection Horizontal connection
Overall dimensions (W × D × H), mm 214 × 240 × 320 278 × 329 × 403 298 × 372 × 406
Environmental compliance — RoHS 2.0 RoHS 2.0
Applicable standards GB/T 14048.3, IEC 60947-3 GB/T 14048.3, IEC 60947-3 GB/T 14048.3, IEC 60947-3

Electrical circuit diagram

CQW5NEDZ-2500

CQW5NEDZ-4000

Symbols and descriptions

Symbol Mô tả
X Closing solenoid
F Loại bỏ shunt
FU Fuse (user supplied)
M Motor operating mechanism
QS Isolating switch
S1 Indicator lamp (user supplied)
SA Motor mechanism limit switch
Symbol Mô tả
SB2 Close pushbutton (user supplied)
SB3 Open pushbutton (user supplied)
XT Secondary circuit terminal
Q Loại bỏ điện áp thấp
PF Ready-to-close contact

Notes

(1) Dashed-line wiring is to be connected by the user.

(2) If the control voltages of Q, X, F and M differ, connect them to separate suitable power supplies.

(3) Terminal 29 may be connected directly to the power supply for automatic spring charging, or through a normally open pushbutton for manual spring charging.

Tổng thể và kích thước lắp đặt

CQW5NEDZ-1600

CQW5NEDZ-2500

Đánh giá hiện tại L/mm
800–1600A 8
1600–2500A 10

CQW5NEDZ-4000

Đánh giá hiện tại L/mm
800–2500A 10
2800–4000A 20

Tại sao nên chọn CHAC

CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQW5NEDZ, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.

01

Xác nhận thông số kỹ thuật

Agree the CQW5NEDZ configuration, circuit duty and installation requirements.

02

XEM SÁCH CHÚA BÀO

Xác nhận các bản vẽ cụ thể của mẫu sản phẩm và các yêu cầu của thị trường đích.

03

CHẤP NHẬN MẪU

Ghi lại các yêu cầu cấu hình và đánh dấu đã được chấp nhận.

04

Xác nhận đơn đặt hàng

Hợp đồng bao gồm các yêu cầu về bao bì, nhận dạng và giao hàng trong báo giá.

Dây chuyền lắp ráp tự động CHAC

Dây chuyền lắp ráp tự động

Phòng thí nghiệm CHAC

Phòng thí nghiệm kiểm nghiệm

CHAC Injection & Stamping

Xay và dập

Đơn vị kiểm tra chất lượng CHAC

Kiểm tra chất lượng

Chúng tôi có thể tùy chỉnh những gì?

Discuss CQW5NEDZ product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.

Logo & Thương hiệu

Gửi hình ảnh thiết kế logo và yêu cầu đánh dấu để xem xét đối với khu vực in sẵn và các thông tin đánh dấu sản phẩm bắt buộc.

CHAC CQW5NEDZ product view

Bao bì và Hướng dẫn sử dụng

Xác định các yêu cầu về nhãn mác thùng carton, ngôn ngữ đóng gói, nhận dạng sản phẩm và hướng dẫn cho thị trường đích.

CHAC CQW5NEDZ product view

Lựa chọn cấu hình

Specify CQW5NEDZ with the required frame and current, operating conditions and protection duty. Confirm the complete order combination.

CHAC CQW5NEDZ product view

Yêu cầu về hội đồng quản trị

Cung cấp các yêu cầu về lắp đặt và kết nối để xem xét. Các thay đổi đối với vỏ máy, các đầu nối hoặc cách vận hành yêu cầu sự chấp thuận kỹ thuật.

CHAC CQW5NEDZ product view

Bản ghi thị trường

Request documents covering the exact CQW5NEDZ model and destination market. A standard reference alone is not evidence of certification.

CHAC CQW5NEDZ product view

Phiếu chấp thuận mẫu

Thỏa thuận về thông số kỹ thuật mẫu, sửa đổi bản vẽ và tiêu chí chấp nhận trước khi xác nhận đơn đặt hàng sản xuất.

CHAC CQW5NEDZ product view

Các tài liệu kỹ thuật và hỗ trợ

DOC

CQW5NEDZ Technical Documents

Request the CQW5NEDZ datasheet, configuration drawing, installation instructions and available model-specific market documents.Mẫu yêu cầu dữ liệu

SUP

Cần tài liệu kỹ thuật?

Gửi đơn đăng ký, yêu cầu về điện, bố trí lắp ráp và thị trường đích để định cấu hình và xem xét tài liệu.Liên hệ với chúng tôi

CQW5NEDZ Product FAQ

What is the difference between Icw and breaking capacity?

Icw describes short-time withstand duty for a stated duration; it does not describe automatic fault interruption. CQW5NEDZ is a DC frame isolation switch, so the fault-clearing device and coordination must be specified separately.

Does every CQW5NEDZ frame have a 100kA rating?

No. The one-second withstand values are 50kA for the 1600 frame, 85kA for the 2500 frame and 100kA for the 4000 frame. Use the exact frame and duration in the design review.

Can all operating accessories share one control supply?

Only when the selected accessory voltages and circuit design permit it. The product instructions require appropriate separate supplies if the control voltages differ. Confirm the motor, closing and release requirements against the exact wiring diagram.

Can I choose CQW5NEDZ by current rating alone?

No. Check operating voltage, poles, utilization category, switching duty, fault coordination and the installation layout together. Confirm the selected combination in the model-specific documentation before approving a substitute.

Can an isolator be switched under load?

Only within its documented switching duty and voltage/current combination. Confirm the applicable utilization category and instructions for CQW5NEDZ; do not assume that every device called an isolator has the same load-break capability.

What information is needed for a CQW5NEDZ quotation?

Provide the supply voltage, required current, load duty, pole arrangement, installation drawing and fault-coordination requirements. Add control or auxiliary-contact needs where applicable, plus quantity and destination market.

Specify the Right CQW5NEDZ Configuration

Gửi cho CHAC cấu hình, ứng dụng, thị trường đích và số lượng ước tính mà bạn cần. Chúng tôi sẽ xem xét kỹ các thông số kỹ thuật được yêu cầu và cung cấp các tài liệu kỹ thuật và đề xuất thương mại liên quan.

Yêu cầu báo giá