Switch Isolasi Frame DC Seri CQW5NEDZ
Sakelar isolasi rangka DC CHAC CQW5NEDZ menyediakan fungsi pemutusan dan isolasi untuk sirkuit utama fotovoltaik dan penyimpanan energi. Tiga ukuran rangka mencakup arus pengenal dari 400A hingga 4000A pada tegangan DC 1500V; pilihlah rangka dan kategori penggunaan yang sesuai dengan aplikasi.
Gambaran Produk
CHAC CQW5NEDZ DC frame isolation switch serves higher-current DC main-circuit applications. Its 1600A, 2500A and 4000A frames operate at 1500V DC, with frame-specific utilization categories and short-time withstand ratings.
Bagi para importir, distributor, dan produsen peralatan, CHAC dapat meninjau konfigurasi yang diminta sesuai dengan persyaratan sirkuit serta dokumen pasar tujuan. Pastikan kesepakatan mengenai model yang tepat, gambar teknis, dan persyaratan penandaan sebelum persetujuan sampel atau pemesanan ulang.
Poin-Poin Pilihan Utama
Aplikasi Biasa
Evaluate CQW5NEDZ for PV and energy-storage DC main circuits requiring switching and isolation. Coordinate the complete assembly with its fault-protection design, control supplies and installation conditions; an isolation switch is not an automatic overcurrent breaker.
Permohonan dan Panduan Pemilihan
| Item seleksi | CQW5NEDZ configuration | Hal yang harus diverifikasi |
|---|---|---|
| Frame and current | 1600 / 2500 / 4000A frames; listed currents across 400–4000A | Use the available current steps for the selected frame. |
| Voltage and poles | 1500V DC; 2P | Confirm the layout and connection arrangement. |
| Utilization category | 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 | Do not transfer one frame’s switching duty to another. |
| One-second withstand | 1600: 50kA; 2500: 85kA; 4000: 100kA | Keep the frame and duration with the current rating when coordinating protection. |
Use these checks to compare the protection function, configuration and related CHAC products before specifying CQW5NEDZ. Related products are selection alternatives or system components, not automatic replacements.
Match the frame to switching and fault-withstand duty
The three frames differ in more than current.
Define the control supplies before cabinet wiring
State the voltages for the motor mechanism, closing and release functions and the required signaling.
Compare CQD5NEZ for the required function
The CHAC CQD5NEZ DC isolator switch is designed for circuit isolation at up to 1500V DC. Two frame sizes cover rated currents from 80A to 630A, with front or side operation to suit the equipment layout.
Compare CQM5NEZ for the required function
Pemutus sirkuit CHAC CQM5NEZ DC tersedia dengan unit trip magnetik saja atau termal-magnetik untuk rangkaian DC 1500V. Pilih versi termal-magnetik jika memerlukan perlindungan overload maupun short-circuit. Frame 350A dan 630A mencakup arus nominal mulai dari 63A hingga 630A, dengan kapasitas pemutusan yang ditentukan oleh frame dan versi M/H.
Need Help Specifying CQW5NEDZ?
Send the circuit requirements, selected configuration, destination market and quantity for a model-specific review.
Match the frame to switching and fault-withstand duty
The three frames differ in more than current. Compare utilization category, short-time withstand duty, dimensions and connection spacing. The 100kA/1s value belongs to the 4000 frame and must not be generalized across the range.
Define the control supplies before cabinet wiring
State the voltages for the motor mechanism, closing and release functions and the required signaling. Where control voltages differ, follow the separate-supply requirements in the approved drawing. Confirm the ready-to-close and interlock logic before commissioning.
How to Specify a CQW5NEDZ Order
Use the configuration details below in the purchase specification. Keep the approved drawing revision and product identification with the order so repeat deliveries can be checked consistently.
| Rincian pesanan | Information to include |
|---|---|
| Frame and current | 1600 / 2500 / 4000A frames; listed currents across 400–4000A — Use the available current steps for the selected frame. |
| Voltage and poles | 1500V DC; 2P — Confirm the layout and connection arrangement. |
| Utilization category | 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 — Do not transfer one frame’s switching duty to another. |
| One-second withstand | 1600: 50kA; 2500: 85kA; 4000: 100kA — Keep the frame and duration with the current rating when coordinating protection. |
| Project and documents | Supply the application, installation conditions and destination-market document requirements. |
| Quantity and identification | State the quantity, sample requirement, packaging language and any proposed branding; confirm feasibility before approval. |
Check Installation Fit Before Approval
Penamaan tipe

| No. | Code | Description |
| ① | CQ | Company Code |
| ② | W | Frame-Type Switch |
| ③ | 5 | Design Code |
| ④ | NEDZ | New Energy – DC |
| ⑤ | 1600 / 2500 / 4000 | Frame Size |
| ⑥ | 2 | Number of Poles: 2P |
| ⑦ | □ | Rated Current |
| ⑧ | □ | Control Voltage |
| ⑨ | □ | Fixed Type |
Operating Conditions
| Ambient Temperature | -40℃ to +70℃ |
| 24-hour Average Temperature | ≤+35℃ |
| Normal Operating Altitude | ≤5000m |
| Relative Humidity | ≤50% at +40℃ |
| Max. Monthly Average Relative Humidity | 0.9 |
| Corresponding Monthly Average Min. Temperature | +25℃ |
| Installation Position | Vertical |
| Installation Inclination | ≤5° |
| Pollution Degree | 3 |
| Installation Category – Main Circuit | IV |
| Installation Category – Auxiliary / Control Circuit | III |
| Tingkat Perlindungan | IP30 / IP40 (IP40 when installed in a cabinet compartment with a door frame.) |
| Utilization Category | 1600A:DC-22A / DC-PV2 2500A,4000A:DC-23A / DC-PV2 |
Spesifikasi Teknis
| Parameter | CQW5NEDZ-1600 | CQW5NEDZ-2500 | CQW5NEDZ-4000 |
| Frame size (A) | 1600 | 2500 | 4000 |
| Rated current (A) | 400, 630, 800, 1000, 1250, 1600 | 800, 1000, 1250, 1600, 2000, 2500 | 800, 1000, 1250, 1600, 2000, 2500, 2800, 2900, 3200, 3600, 4000 |
| Jumlah tiang | 2P | 2P | 2P |
| Rated operational voltage Ue (V) | DC1500 | DC1500 | DC1500 |
| Rated insulation voltage Ui (V) | 2000 | 2500 | 2500 |
| Rated impulse withstand voltage Uimp (kV) | 15 | 15 | 18 |
| Pole spacing (mm) | 80 | 95 | 115 |
| Rated short-circuit making capacity Icm (kA) | 50 | 85 | 100 |
| Rated short-time withstand current Icw | 50 kA/1 s, 120 kA/0.1 s | 85 kA/1 s, 150 kA/0.2 s | 100 kA/1 s, 160 kA/0.2 s |
| Utilization category | DC-22A, DC-PV2 | DC-23A, DC-PV2 | DC-23A, DC-PV2 |
| Total breaking time, without intentional delay (ms) | — | ≤25 | ≤25 |
| Closing time (ms) | ≤70 | ≤70 | ≤70 |
| Electrical endurance (cycles) | 500 | 500 (DC-23A); 1,500 (DC-PV2) | 500 (DC-23A); 1,500 (DC-PV2) |
| Mechanical endurance maintenance-free (cycles) | 10000 | 15000 | 15000 |
| Mechanical endurance with maintenance (cycles) | — | 25000 | 25000 |
| Temperature rise at a reference ambient temperature of 50°C (K) | — | <50 | <50 |
| Arcing distance (mm) | — | 0 | 0 |
| Installation type | Fixed type | Fixed type | Fixed type |
| Connection type | — | Horizontal connection | Horizontal connection |
| Overall dimensions (W × D × H), mm | 214 × 240 × 320 | 278 × 329 × 403 | 298 × 372 × 406 |
| Environmental compliance | — | RoHS 2.0 | RoHS 2.0 |
| Applicable standards | GB/T 14048.3, IEC 60947-3 | GB/T 14048.3, IEC 60947-3 | GB/T 14048.3, IEC 60947-3 |
Electrical circuit diagram
CQW5NEDZ-2500

CQW5NEDZ-4000

Symbols and descriptions
| Symbol | Description |
| X | Closing solenoid |
| F | Pembebasan shunt |
| FU | Fuse (user supplied) |
| M | Motor operating mechanism |
| QS | Isolating switch |
| S1 | Indicator lamp (user supplied) |
| SA | Motor mechanism limit switch |
| Symbol | Description |
| SB2 | Close pushbutton (user supplied) |
| SB3 | Open pushbutton (user supplied) |
| XT | Secondary circuit terminal |
| Q | Pengecekan tegangan bawah |
| PF | Ready-to-close contact |
Notes
(1) Dashed-line wiring is to be connected by the user.
(2) If the control voltages of Q, X, F and M differ, connect them to separate suitable power supplies.
(3) Terminal 29 may be connected directly to the power supply for automatic spring charging, or through a normally open pushbutton for manual spring charging.
Overall and mounting dimensions
CQW5NEDZ-1600

CQW5NEDZ-2500

| Rating saat ini | L/mm |
| 800–1600A | 8 |
| 1600–2500A | 10 |
CQW5NEDZ-4000

| Rating saat ini | L/mm |
| 800–2500A | 10 |
| 2800–4000A | 20 |
Mengapa Memilih CHAC
CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQW5NEDZ, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.
01
KONFIRMASI SPESIFIKASI
Agree the CQW5NEDZ configuration, circuit duty and installation requirements.
02
TINJAU DOKUMEN-DOKUMEN
Konfirmasikan gambar yang spesifik untuk model dan persyaratan pasar tujuan.
03
SETUJUI SAMPEL
Catat konfigurasi yang diterima dan persyaratan penandaan.
04
TENTUKAN CEK PESANAN
Setujui persyaratan pengemasan, identifikasi, dan pengiriman dalam penawaran.

Barisan Perakitan Otomatis

Laboratorium Pengujian

Injeksi & Stamping

Pemeriksaan Kualitas
Apa yang Dapat Kami Sesuaikan?
Discuss CQW5NEDZ product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.
Logo & Branding
Kirimkan karya seni logo dan persyaratan penandaan untuk ditinjau sesuai dengan area cetak yang tersedia serta penandaan produk wajib.

Kemasan & Manual
Tentukan label karton, bahasa pada kemasan, identifikasi produk, serta persyaratan instruksi untuk pasar tujuan.

Pemilihan Konfigurasi
Specify CQW5NEDZ with the required frame and current, operating conditions and protection duty. Confirm the complete order combination.

Assembly Requirements
Provide the mounting and connection requirements for review. Changes to the housing, terminals or operating arrangement require engineering approval.

Dokumentasi Pasar
Request documents covering the exact CQW5NEDZ model and destination market. A standard reference alone is not evidence of certification.

Persetujuan Sampel
Setujui spesifikasi sampel, revisi gambar, dan kriteria penerimaan sebelum memastikan pesanan produksi.

Dokumen Teknis dan Dukungan
CQW5NEDZ Technical Documents
Request the CQW5NEDZ datasheet, configuration drawing, installation instructions and available model-specific market documents.Minta Lembar Data
Butuh Dokumen Teknis?
Send the application, electrical requirements, assembly layout and destination market for configuration and document review.Hubungi Kami
CQW5NEDZ Product FAQ
What is the difference between Icw and breaking capacity?
Icw describes short-time withstand duty for a stated duration; it does not describe automatic fault interruption. CQW5NEDZ is a DC frame isolation switch, so the fault-clearing device and coordination must be specified separately.
Does every CQW5NEDZ frame have a 100kA rating?
No. The one-second withstand values are 50kA for the 1600 frame, 85kA for the 2500 frame and 100kA for the 4000 frame. Use the exact frame and duration in the design review.
Can all operating accessories share one control supply?
Only when the selected accessory voltages and circuit design permit it. The product instructions require appropriate separate supplies if the control voltages differ. Confirm the motor, closing and release requirements against the exact wiring diagram.
Can I choose CQW5NEDZ by current rating alone?
No. Check operating voltage, poles, utilization category, switching duty, fault coordination and the installation layout together. Confirm the selected combination in the model-specific documentation before approving a substitute.
Can an isolator be switched under load?
Only within its documented switching duty and voltage/current combination. Confirm the applicable utilization category and instructions for CQW5NEDZ; do not assume that every device called an isolator has the same load-break capability.
What information is needed for a CQW5NEDZ quotation?
Provide the supply voltage, required current, load duty, pole arrangement, installation drawing and fault-coordination requirements. Add control or auxiliary-contact needs where applicable, plus quantity and destination market.
Specify the Right CQW5NEDZ Configuration
Send CHAC your required configuration, application, destination market and estimated quantity. We will review the requested specification and provide the relevant technical documents and commercial proposal.