CQW5NEDZ Series DC Frame Isolation Switch

The CHAC CQW5NEDZ DC frame isolation switch provides switching and isolation for photovoltaic and energy-storage main circuits. Three frame sizes cover rated currents from 400A to 4000A at 1500V DC; select the frame and utilization category for the application.

Models:
CQW5NEDZ-1600 / CQW5NEDZ-2500 / CQW5NEDZ-4000
Poles:
2P
Rated Current:
400–4000A, depending on frame
Rated Voltage:
1500V DC
Rated Impulse Withstand Voltage:
15kV (1600/2500 frame); 18kV (4000 frame)
Utilization Category:
DC-22A / DC-PV2 (1600 frame); DC-23A / DC-PV2 (2500/4000 frames)
Standard:
IEC 60947-3 / GB/T 14048.3
Customization:
One-Stop OEM/ODM Service

Product Overview

The CHAC CQW5NEDZ DC frame isolation switch serves higher-current DC main-circuit applications. Its 1600A, 2500A and 4000A frames operate at 1500V DC, with frame-specific utilization categories and short-time withstand ratings.

For importers, distributors and equipment manufacturers, CHAC can review the requested configuration against the circuit requirements and destination-market documents. Agree the exact model, drawings and marking requirements before sample approval or a repeat order.

Key Selection Points

  • Frame and current: 1600 / 2500 / 4000A frames; listed currents across 400–4000A. Use the available current steps for the selected frame.
  • Voltage and poles: 1500V DC; 2P. Confirm the layout and connection arrangement.
  • Utilization category: 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2. Do not transfer one frame’s switching duty to another.
  • One-second withstand: 1600: 50kA; 2500: 85kA; 4000: 100kA. Keep the frame and duration with the current rating when coordinating protection.

Typical Applications

Evaluate CQW5NEDZ for PV and energy-storage DC main circuits requiring switching and isolation. Coordinate the complete assembly with its fault-protection design, control supplies and installation conditions; an isolation switch is not an automatic overcurrent breaker.

Applications and Selection Guide

Selection item CQW5NEDZ configuration What to verify
Frame and current 1600 / 2500 / 4000A frames; listed currents across 400–4000A Use the available current steps for the selected frame.
Voltage and poles 1500V DC; 2P Confirm the layout and connection arrangement.
Utilization category 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 Do not transfer one frame’s switching duty to another.
One-second withstand 1600: 50kA; 2500: 85kA; 4000: 100kA Keep the frame and duration with the current rating when coordinating protection.

Use these checks to compare the protection function, configuration and related CHAC products before specifying CQW5NEDZ. Related products are selection alternatives or system components, not automatic replacements.

Compare CQD5NEZ for the required function

The CHAC CQD5NEZ DC isolator switch is designed for circuit isolation at up to 1500V DC. Two frame sizes cover rated currents from 80A to 630A, with front or side operation to suit the equipment layout.

Related ProductSystem DesignVerify Compatibility

Compare CQM5NEZ for the required function

The CHAC CQM5NEZ DC molded case circuit breaker is available with magnetic-only or thermal-magnetic trip units for 1500V DC circuits. Select a thermal-magnetic version when both overload and short-circuit protection are required. The 350A and 630A frames cover rated currents from 63A to 630A, with breaking capacity determined by frame and M/H version.

Related ProductSystem DesignVerify Compatibility

Need Help Specifying CQW5NEDZ?

Send the circuit requirements, selected configuration, destination market and quantity for a model-specific review.

Request a Quote

Match the frame to switching and fault-withstand duty

The three frames differ in more than current. Compare utilization category, short-time withstand duty, dimensions and connection spacing. The 100kA/1s value belongs to the 4000 frame and must not be generalized across the range.

Define the control supplies before cabinet wiring

State the voltages for the motor mechanism, closing and release functions and the required signaling. Where control voltages differ, follow the separate-supply requirements in the approved drawing. Confirm the ready-to-close and interlock logic before commissioning.

How to Specify a CQW5NEDZ Order

Use the configuration details below in the purchase specification. Keep the approved drawing revision and product identification with the order so repeat deliveries can be checked consistently.

Order detail Information to include
Frame and current 1600 / 2500 / 4000A frames; listed currents across 400–4000A — Use the available current steps for the selected frame.
Voltage and poles 1500V DC; 2P — Confirm the layout and connection arrangement.
Utilization category 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 — Do not transfer one frame’s switching duty to another.
One-second withstand 1600: 50kA; 2500: 85kA; 4000: 100kA — Keep the frame and duration with the current rating when coordinating protection.
Project and documents Supply the application, installation conditions and destination-market document requirements.
Quantity and identification State the quantity, sample requirement, packaging language and any proposed branding; confirm feasibility before approval.

Check Installation Fit Before Approval

  • Use the CQW5NEDZ dimension drawing to verify mounting, terminal access, operating clearance and conductor bending space.
  • Confirm conductor preparation, terminal compatibility and tightening instructions for the exact configuration. A conductor reference table does not replace project cable sizing.
  • Review temperature, enclosure conditions and the protective arrangement with the equipment designer. Do not infer compatibility from a similar model name.
  • Have qualified personnel install and verify the equipment using the model instructions and applicable isolation and testing procedures.

Type designation

No. Code Description
① CQ Company Code
② W Frame-Type Switch
③ 5 Design Code
④ NEDZ New Energy – DC
⑤ 1600 / 2500 / 4000 Frame Size
⑥ 2 Number of Poles: 2P
⑦ □ Rated Current
⑧ □ Control Voltage
⑨ □ Fixed Type

Operating Conditions

Ambient Temperature -40℃ to +70℃
24-hour Average Temperature ≤+35℃
Normal Operating Altitude ≤5000m
Relative Humidity ≤50% at +40℃
Max. Monthly Average Relative Humidity 0.9
Corresponding Monthly Average Min. Temperature +25℃
Installation Position Vertical
Installation Inclination ≤5°
Pollution Degree 3
Installation Category – Main Circuit IV
Installation Category – Auxiliary / Control Circuit III
Degree of Protection IP30 / IP40 (IP40 when installed in a cabinet compartment with a door frame.)
Utilization Category 1600A:DC-22A / DC-PV2 2500A,4000A:DC-23A / DC-PV2

Technical Specifications

Parameter CQW5NEDZ-1600 CQW5NEDZ-2500 CQW5NEDZ-4000
Frame size (A) 1600 2500 4000
Rated current (A) 400, 630, 800, 1000, 1250, 1600 800, 1000, 1250, 1600, 2000, 2500 800, 1000, 1250, 1600, 2000, 2500, 2800, 2900, 3200, 3600, 4000
Number of poles 2P 2P 2P
Rated operational voltage Ue (V) DC1500 DC1500 DC1500
Rated insulation voltage Ui (V) 2000 2500 2500
Rated impulse withstand voltage Uimp (kV) 15 15 18
Pole spacing (mm) 80 95 115
Rated short-circuit making capacity Icm (kA) 50 85 100
Rated short-time withstand current Icw 50 kA/1 s, 120 kA/0.1 s 85 kA/1 s, 150 kA/0.2 s 100 kA/1 s, 160 kA/0.2 s
Utilization category DC-22A, DC-PV2 DC-23A, DC-PV2 DC-23A, DC-PV2
Total breaking time, without intentional delay (ms) — ≤25 ≤25
Closing time (ms) ≤70 ≤70 ≤70
Electrical endurance (cycles) 500 500 (DC-23A); 1,500 (DC-PV2) 500 (DC-23A); 1,500 (DC-PV2)
Mechanical endurance maintenance-free (cycles) 10000 15000 15000
Mechanical endurance with maintenance (cycles) — 25000 25000
Temperature rise at a reference ambient temperature of 50°C (K) — <50 <50
Arcing distance (mm) — 0 0
Installation type Fixed type Fixed type Fixed type
Connection type — Horizontal connection Horizontal connection
Overall dimensions (W × D × H), mm 214 × 240 × 320 278 × 329 × 403 298 × 372 × 406
Environmental compliance — RoHS 2.0 RoHS 2.0
Applicable standards GB/T 14048.3, IEC 60947-3 GB/T 14048.3, IEC 60947-3 GB/T 14048.3, IEC 60947-3

Electrical circuit diagram

CQW5NEDZ-2500

CQW5NEDZ-4000

Symbols and descriptions

Symbol Description
X Closing solenoid
F Shunt release
FU Fuse (user supplied)
M Motor operating mechanism
QS Isolating switch
S1 Indicator lamp (user supplied)
SA Motor mechanism limit switch
Symbol Description
SB2 Close pushbutton (user supplied)
SB3 Open pushbutton (user supplied)
XT Secondary circuit terminal
Q Undervoltage release
PF Ready-to-close contact

Notes

(1) Dashed-line wiring is to be connected by the user.

(2) If the control voltages of Q, X, F and M differ, connect them to separate suitable power supplies.

(3) Terminal 29 may be connected directly to the power supply for automatic spring charging, or through a normally open pushbutton for manual spring charging.

Overall and mounting dimensions

CQW5NEDZ-1600

CQW5NEDZ-2500

Current rating L/mm
800–1600A 8
1600–2500A 10

CQW5NEDZ-4000

Current rating L/mm
800–2500A 10
2800–4000A 20

Why Choose CHAC

CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQW5NEDZ, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.

01

CONFIRM THE SPECIFICATION

Agree the CQW5NEDZ configuration, circuit duty and installation requirements.

02

REVIEW THE DOCUMENTS

Confirm model-specific drawings and destination-market requirements.

03

APPROVE THE SAMPLE

Record the accepted configuration and marking requirements.

04

DEFINE ORDER CHECKS

Agree packaging, identification and delivery requirements in the quotation.

CHAC Automated Assembly Line

Automated Assembly Line

CHAC Testing Laboratory

Testing Laboratory

CHAC Injection & Stamping

Injection & Stamping

CHAC Quality Inspection

Quality Inspection

What Can We Customize?

Discuss CQW5NEDZ product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.

Logo & Branding

Submit logo artwork and marking requirements for review against the available print area and mandatory product markings.

CHAC CQW5NEDZ product view

Packaging & Manuals

Define carton labels, packaging language, product identification and instruction requirements for the destination market.

CHAC CQW5NEDZ product view

Configuration Selection

Specify CQW5NEDZ with the required frame and current, operating conditions and protection duty. Confirm the complete order combination.

CHAC CQW5NEDZ product view

Assembly Requirements

Provide the mounting and connection requirements for review. Changes to the housing, terminals or operating arrangement require engineering approval.

CHAC CQW5NEDZ product view

Market Documentation

Request documents covering the exact CQW5NEDZ model and destination market. A standard reference alone is not evidence of certification.

CHAC CQW5NEDZ product view

Sample Approval

Agree the sample specification, drawing revision and acceptance criteria before confirming a production order.

CHAC CQW5NEDZ product view

Technical Documents and Support

DOC

CQW5NEDZ Technical Documents

Request the CQW5NEDZ datasheet, configuration drawing, installation instructions and available model-specific market documents.Request Datasheet

SUP

Need Technical Documents?

Send the application, electrical requirements, assembly layout and destination market for configuration and document review.Contact Us

CQW5NEDZ Product FAQ

What is the difference between Icw and breaking capacity?

Icw describes short-time withstand duty for a stated duration; it does not describe automatic fault interruption. CQW5NEDZ is a DC frame isolation switch, so the fault-clearing device and coordination must be specified separately.

Does every CQW5NEDZ frame have a 100kA rating?

No. The one-second withstand values are 50kA for the 1600 frame, 85kA for the 2500 frame and 100kA for the 4000 frame. Use the exact frame and duration in the design review.

Can all operating accessories share one control supply?

Only when the selected accessory voltages and circuit design permit it. The product instructions require appropriate separate supplies if the control voltages differ. Confirm the motor, closing and release requirements against the exact wiring diagram.

Can I choose CQW5NEDZ by current rating alone?

No. Check operating voltage, poles, utilization category, switching duty, fault coordination and the installation layout together. Confirm the selected combination in the model-specific documentation before approving a substitute.

Can an isolator be switched under load?

Only within its documented switching duty and voltage/current combination. Confirm the applicable utilization category and instructions for CQW5NEDZ; do not assume that every device called an isolator has the same load-break capability.

What information is needed for a CQW5NEDZ quotation?

Provide the supply voltage, required current, load duty, pole arrangement, installation drawing and fault-coordination requirements. Add control or auxiliary-contact needs where applicable, plus quantity and destination market.

Specify the Right CQW5NEDZ Configuration

Send CHAC your required configuration, application, destination market and estimated quantity. We will review the requested specification and provide the relevant technical documents and commercial proposal.

Request a Quote