مفتاح عزل الإطار DC من سلسلة CQW5NEDZ
The CHAC CQW5NEDZ DC frame isolation switch provides switching and isolation for photovoltaic and energy-storage main circuits. Three frame sizes cover rated currents from 400A to 4000A at 1500V DC; select the frame and utilization category for the application.
مواصفات المنتج
الجنة العليا للأشخاص ذوي الإعاقة CQW5NEDZ DC frame isolation switch serves higher-current DC main-circuit applications. Its 1600A, 2500A and 4000A frames operate at 1500V DC, with frame-specific utilization categories and short-time withstand ratings.
بالنسبة للمستوردين والموزعين وشركات تصنيع المعدات، يمكن لشركة CHAC مراجعة التكوين المطلوب وفقًا لمتطلبات الدائرة الكهربائية ووثائق سوق الوجهة. يُرجى الاتفاق على الطراز الدقيق والرسومات ومتطلبات العلامات قبل اعتماد العينة أو تقديم طلب تكرار.
نقاط الاختيار الرئيسية
الاستخدامات النموذجية
Evaluate CQW5NEDZ for PV and energy-storage DC main circuits requiring switching and isolation. Coordinate the complete assembly with its fault-protection design, control supplies and installation conditions; an isolation switch is not an automatic overcurrent breaker.
طلبات واقتراحات واختيار المرشحين
| مكون الاختيار | CQW5NEDZ configuration | ما يجب التحقق منه |
|---|---|---|
| الإطار والحالة الراهنة | 1600 / 2500 / 4000A frames; listed currents across 400–4000A | Use the available current steps for the selected frame. |
| Voltage and poles | 1500V DC; 2P | Confirm the layout and connection arrangement. |
| فئة الاستخدام | 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 | Do not transfer one frame’s switching duty to another. |
| One-second withstand | 1600: 50kA; 2500: 85kA; 4000: 100kA | Keep the frame and duration with the current rating when coordinating protection. |
Use these checks to compare the protection function, configuration and related CHAC products before specifying CQW5NEDZ. Related products are selection alternatives or system components, not automatic replacements.
Match the frame to switching and fault-withstand duty
The three frames differ in more than current.
Define the control supplies before cabinet wiring
State the voltages for the motor mechanism, closing and release functions and the required signaling.
Compare CQD5NEZ for the required function
تم تصميم مفتاح فصل التيار المستمر CHAC CQD5NEZ لعزل الدائرة عند جهد يصل إلى 1500V تيار مستمر. يغطي حجمان للإطار تيارات مقدرة تتراوح من 80A إلى 630A، مع تشغيل أمامي أو جانبي بما يناسب تخطيط المعدات.
Compare CQM5NEZ for the required function
يتم توفير قاطع الدائرة المدمج CHAC CQM5NEZ DC مع وحدات إيقاف التيار الكهربائي الميكانيكي أو الحراري الميكانيكي لدوائر التيار الكهربائي 1500 فولت. اختر نسخة حرارية ميكانيكية عند الحاجة إلى حماية من الحمل الزائد والقصور. تغطي الأطر 350A و630A تيارين محددين بمعدل 63A إلى 630A، مع تحديد قدرة كسر التيار الكهربائي حسب الأطر والنسخة M/H.
Need Help Specifying CQW5NEDZ?
أرسل متطلبات الدائرة، والتكوين المختار، وسوق التصدير، والكمية لإجراء مراجعة خاصة بالنموذج.
Match the frame to switching and fault-withstand duty
The three frames differ in more than current. Compare utilization category, short-time withstand duty, dimensions and connection spacing. The 100kA/1s value belongs to the 4000 frame and must not be generalized across the range.
Define the control supplies before cabinet wiring
State the voltages for the motor mechanism, closing and release functions and the required signaling. Where control voltages differ, follow the separate-supply requirements in the approved drawing. Confirm the ready-to-close and interlock logic before commissioning.
How to Specify a CQW5NEDZ Order
يرجى استخدام تفاصيل التكوين الواردة أدناه في مواصفات الشراء. احتفظ بنسخة من مراجعة الرسم المعتمد وهوية المنتج مع الطلب لضمان إمكانية التحقق المتسق من عمليات التسليم المتكررة.
| تفاصيل الطلب | المعلومات المطلوب تضمينها |
|---|---|
| الإطار والحالة الراهنة | 1600 / 2500 / 4000A frames; listed currents across 400–4000A — Use the available current steps for the selected frame. |
| Voltage and poles | 1500V DC; 2P — Confirm the layout and connection arrangement. |
| فئة الاستخدام | 1600: DC-22A / DC-PV2; 2500/4000: DC-23A / DC-PV2 — Do not transfer one frame’s switching duty to another. |
| One-second withstand | 1600: 50kA; 2500: 85kA; 4000: 100kA — Keep the frame and duration with the current rating when coordinating protection. |
| المشروع والوثائق | قم بتوفير متطلبات التطبيق وظروف التركيب ووثائق السوق المستهدف. |
| الكمية والتحديد | يُرجى تحديد الكمية، ومتطلبات العينة، ولغة التعبئة والتغليف، وأي علامة تجارية مقترحة؛ مع التأكد من الجدوى قبل الموافقة. |
تحقق من ملاءمة التركيب قبل الموافقة
تعيين النوع

| لا. | Code | الوصف |
| ① | CQ | Company Code |
| ② | W | Frame-Type Switch |
| ③ | 5 | Design Code |
| ④ | NEDZ | New Energy – DC |
| ⑤ | 1600 / 2500 / 4000 | Frame Size |
| ⑥ | 2 | Number of Poles: 2P |
| ⑦ | □ | Rated Current |
| ⑧ | □ | Control Voltage |
| ⑨ | □ | Fixed Type |
Operating Conditions
| Ambient Temperature | -40℃ to +70℃ |
| 24-hour Average Temperature | ≤+35℃ |
| Normal Operating Altitude | ≤5000m |
| Relative Humidity | ≤50% at +40℃ |
| Max. Monthly Average Relative Humidity | 0.9 |
| Corresponding Monthly Average Min. Temperature | +25℃ |
| Installation Position | Vertical |
| Installation Inclination | ≤5° |
| درجة التلوث | 3 |
| Installation Category – Main Circuit | IV |
| Installation Category – Auxiliary / Control Circuit | III |
| درجة الحماية | IP30 / IP40 (IP40 when installed in a cabinet compartment with a door frame.) |
| Utilization Category | 1600A:DC-22A / DC-PV2 2500A,4000A:DC-23A / DC-PV2 |
المواصفات الفنية
| معامل | CQW5NEDZ-1600 | CQW5NEDZ-2500 | CQW5NEDZ-4000 |
| Frame size (A) | 1600 | 2500 | 4000 |
| التيار المقنن (أمبير) | 400, 630, 800, 1000, 1250, 1600 | 800, 1000, 1250, 1600, 2000, 2500 | 800, 1000, 1250, 1600, 2000, 2500, 2800, 2900, 3200, 3600, 4000 |
| عدد الأقطاب | 2P | 2P | 2P |
| Rated operational voltage Ue (V) | DC1500 | DC1500 | DC1500 |
| جهد العزل المقدر Ui (V) | 2000 | 2500 | 2500 |
| الجهد المقاوم للتأثير الكهربي Uimp (كيلو فولت) | 15 | 15 | 18 |
| Pole spacing (mm) | 80 | 95 | 115 |
| Rated short-circuit making capacity Icm (kA) | 50 | 85 | 100 |
| Rated short-time withstand current Icw | 50 kA/1 s, 120 kA/0.1 s | 85 kA/1 s, 150 kA/0.2 s | 100 kA/1 s, 160 kA/0.2 s |
| فئة الاستخدام | DC-22A, DC-PV2 | DC-23A, DC-PV2 | DC-23A, DC-PV2 |
| Total breaking time, without intentional delay (ms) | — | ≤25 | ≤25 |
| Closing time (ms) | ≤70 | ≤70 | ≤70 |
| Electrical endurance (cycles) | 500 | 500 (DC-23A); 1,500 (DC-PV2) | 500 (DC-23A); 1,500 (DC-PV2) |
| Mechanical endurance maintenance-free (cycles) | 10000 | 15000 | 15000 |
| Mechanical endurance with maintenance (cycles) | — | 25000 | 25000 |
| Temperature rise at a reference ambient temperature of 50°C (K) | — | <50 | <50 |
| Arcing distance (mm) | — | 0 | 0 |
| Installation type | Fixed type | Fixed type | Fixed type |
| Connection type | — | Horizontal connection | Horizontal connection |
| Overall dimensions (W × D × H), mm | 214 × 240 × 320 | 278 × 329 × 403 | 298 × 372 × 406 |
| Environmental compliance | — | RoHS 2.0 | RoHS 2.0 |
| Applicable standards | GB/T 14048.3, IEC 60947-3 | GB/T 14048.3, IEC 60947-3 | GB/T 14048.3, IEC 60947-3 |
Electrical circuit diagram
CQW5NEDZ-2500

CQW5NEDZ-4000

Symbols and descriptions
| Symbol | الوصف |
| X | Closing solenoid |
| F | إطلاق الشنت |
| FU | Fuse (user supplied) |
| M | Motor operating mechanism |
| QS | Isolating switch |
| S1 | Indicator lamp (user supplied) |
| SA | Motor mechanism limit switch |
| Symbol | الوصف |
| SB2 | Close pushbutton (user supplied) |
| SB3 | Open pushbutton (user supplied) |
| XT | Secondary circuit terminal |
| Q | إطلاق التيار الكهربائي عند انخفاضه |
| PF | Ready-to-close contact |
Notes
(1) Dashed-line wiring is to be connected by the user.
(2) If the control voltages of Q, X, F and M differ, connect them to separate suitable power supplies.
(3) Terminal 29 may be connected directly to the power supply for automatic spring charging, or through a normally open pushbutton for manual spring charging.
Overall and mounting dimensions
CQW5NEDZ-1600

CQW5NEDZ-2500

| التقييم الحالي | L/mm |
| 800–1600A | 8 |
| 1600–2500A | 10 |
CQW5NEDZ-4000

| التقييم الحالي | L/mm |
| 800–2500A | 10 |
| 2800–4000A | 20 |
لماذا تختار CHAC
CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQW5NEDZ, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.
01
CONFIRM THE SPECIFICATION
Agree the CQW5NEDZ configuration, circuit duty and installation requirements.
02
REVIEW THE DOCUMENTS
Confirm model-specific drawings and destination-market requirements.
03
APPROVE THE SAMPLE
Record the accepted configuration and marking requirements.
04
DEFINE ORDER CHECKS
Agree packaging, identification and delivery requirements in the quotation.

خط التجميع الآلي

مختبر اختبار

حقن وختم

فحص الجودة
ما الذي يمكننا تخصيصه؟
Discuss CQW5NEDZ product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.
الشعار والعلامة التجارية
Submit logo artwork and marking requirements for review against the available print area and mandatory product markings.

Packaging & Manuals
Define carton labels, packaging language, product identification and instruction requirements for the destination market.

Configuration Selection
Specify CQW5NEDZ with the required frame and current, operating conditions and protection duty. Confirm the complete order combination.

Assembly Requirements
Provide the mounting and connection requirements for review. Changes to the housing, terminals or operating arrangement require engineering approval.

Market Documentation
Request documents covering the exact CQW5NEDZ model and destination market. A standard reference alone is not evidence of certification.

Sample Approval
Agree the sample specification, drawing revision and acceptance criteria before confirming a production order.

Technical Documents and Support
CQW5NEDZ Technical Documents
Request the CQW5NEDZ datasheet, configuration drawing, installation instructions and available model-specific market documents.Request Datasheet
هل تحتاج إلى وثائق فنية؟
Send the application, electrical requirements, assembly layout and destination market for configuration and document review.اتصل بنا
CQW5NEDZ Product FAQ
What is the difference between Icw and breaking capacity?
Icw describes short-time withstand duty for a stated duration; it does not describe automatic fault interruption. CQW5NEDZ is a DC frame isolation switch, so the fault-clearing device and coordination must be specified separately.
Does every CQW5NEDZ frame have a 100kA rating?
No. The one-second withstand values are 50kA for the 1600 frame, 85kA for the 2500 frame and 100kA for the 4000 frame. Use the exact frame and duration in the design review.
Can all operating accessories share one control supply?
Only when the selected accessory voltages and circuit design permit it. The product instructions require appropriate separate supplies if the control voltages differ. Confirm the motor, closing and release requirements against the exact wiring diagram.
Can I choose CQW5NEDZ by current rating alone?
No. Check operating voltage, poles, utilization category, switching duty, fault coordination and the installation layout together. Confirm the selected combination in the model-specific documentation before approving a substitute.
Can an isolator be switched under load?
Only within its documented switching duty and voltage/current combination. Confirm the applicable utilization category and instructions for CQW5NEDZ; do not assume that every device called an isolator has the same load-break capability.
What information is needed for a CQW5NEDZ quotation?
Provide the supply voltage, required current, load duty, pole arrangement, installation drawing and fault-coordination requirements. Add control or auxiliary-contact needs where applicable, plus quantity and destination market.
Specify the Right CQW5NEDZ Configuration
Send CHAC your required configuration, application, destination market and estimated quantity. We will review the requested specification and provide the relevant technical documents and commercial proposal.