CQB7ZN-80 Remote Intelligent Small Circuit Breaker
Overview and applications
The CQB7ZN-80 remote intelligent small circuit breaker can be remotely controlled and operated through communication methods such as WIFI and Bluetooth using a PC or mobile device, and can provide real-time feedback on the circuit breaker status to the device. The product integrates TUYA platform chips, which can easily connect to all TUYA systems and provide data interfaces and customized software services.The product is widely used for remote intelligent control in scenarios such as apartments, schools, and municipal factories.The functions of leakage protection, metering, over voltage and under voltage protection can be customized separately.
Standards: IEC/EN 60947-2, EU ROHS environmental protection requirements, Intelligent control circuit breaker technical specification.
Technical data
| Specifications | |
| Rated voltage (V) | AC230V(1P+N 2P) AC400V(3P+N 4P) |
| Rated current (A) | 6、10、16、20、25、32、40、50、63、80 |
| Poles | 1P+N、2P、3P+N、4P |
| Rated breaking capacity Icn(A) | 6000V |
| Frame size rated current (A) | 80 |
| Mechanical & Electrical life | Mechanical≥10000,Electrical≥6000 |
| Tripping characteristics | C |
| Frequency | 50Hz |
| Pollution degree | Level 2 |
| Protection class | IP20 |
| Overvoltage category | Ⅱ Ⅲ |
| Standards | IEC60898-1、GB/T10963.1 |
| Compliant certification | CCC |
Table1 Tripping characteristics (Reference temp.30°C)
| Test | Test current (A) | Starting state | Tripping or non-tripping time limit | Expected Result | Remark |
| a | 1.13In | Cold | t≤1h(In≤63A) t≤2h(In>63A) |
No tripping | |
| b | 1.45In | Following experiment a | t<1h(In≤63A) t<2h(In>63A) |
Trip | Current smoothly rises to specified value within 5s |
| c | 2.55In | Cold | 1s<t<120s | Trip | |
| d | 5In | Cold | t≤0.1s | No tripping | Switch on the power supply by closing the auxiliary switch |
| e | 10In | Cold | t<0.1s | Trip | Switch on the power supply by closing the auxiliary switch |
Note: The term”cold “means that the test is carried out at a reference calibration temperature without load before the test.
Conductor requirements and cross section
| Copper cross-section(mm²) | Rated current In(A) |
| 6 | 16<In≤32 |
| 10 | 32<In≤50 |
| 16 | 50<In≤63 |
| 25 | 63<In≤100 |
Dimensions(unit:mm)

Ordering Specifications
When ordering a circuit breaker, please specify the following:
a) Product model, such as CQB7ZN-80;
b) Number of poles of the circuit breaker, such as 1P+N, 2P, 3P+N, 4P;
c) Instantaneous tripping type, such as C;
d) Rated current of the circuit breaker, such as 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A;
e) Order quantity, such as 100 units.
Order:
CQB7ZN-80 2P C/80A 100 pieces