PXB9L-40 Series Electromagnetic Leakage Miniature Circuit Breaker

The PXB9L-40 series electromagnetic residual current operated circuit breaker is designed by CHAC Electric to provide comprehensive protection for electrical circuits. These MCBs are suitable for AC 50Hz/60Hz systems with a rated voltage of 230V/400V and a rated current up to 40A. They offer isolation, overload, leakage, and short-circuit protection, effectively preventing insulation failure of electrical equipment. Our PXB9L-40 series is ideal for residential and commercial distribution systems, providing reliable and robust protection. We utilize advanced production technology and strict quality control to ensure the reliability and durability of our products. This makes them an ideal choice for customers seeking efficient and durable electrical protection solutions in different distribution scenarios.

Overview&Description

1.Provides ground fault/leakage current, short circuit, overloadprotection and isolation

2.Provides additional protection against direct human contact

3.Effectively prevent electrical equipment insulation failure

4.Comprehensive protection for residential and commercialpower distribution systems

Technical data

Specifications
Rated voltage Ue 230V
Rated current(A) 6、10、13、16、20、25、32、40
Rated frequency 50Hz
Number of poles 1P+N
Rated breaking capacity Icn=Ics(A) 6000
Mechanical & Electrical life Mechanical life 10000 、Electrical life 4000
Tripping characteristics B、C、D
Pollution degree 2
Protection degree IP20
Standards EN/IEC 61009-1、GB/T 16917.1
Tighten torque(Nm) 3.5
Type of residual current AC、A
Rated residual operating current I△n (mA) 30
Rated service breaking capacity lcn=lcs(A) 6000
Rated residual making&breaking capacity I△m(A) 500

Table1 Tripping characteristics (Reference temp.30℃)

Item Tripping Curve Test current In(A) Initial Status Time limit for tripping or non-tripping Expected result Remark
a B、C、D 1.13In Cold t≤1h Non-tripping Current smoothly rises to specified value within 5s
b B、C、D 1.45In Following item a test t<1h Tripping
c B、C、D 2.55In Cold 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
Tripping
d B 3In Cold t≤0.1s Non-tripping Switch on the power supply by closing the auxiliary switch
C 5In
D 10In
e B 5In Cold t<0.1s Tripping Switch on the power supply by closing the auxiliary switch
C 10In
D 20In

Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.