PXB6HDC-63 DC Miniature Circuit Breaker

The PXB6HDC-63 is specified for DC overload and short-circuit protection. Select it using the published voltage, current, pole and protection data, then confirm conductor coordination, fault conditions, enclosure requirements and local installation rules.

Poles:
1P / 2P
Rated Current:
1–63A
Rated Voltage:
1P DC 220/250V; 2P DC 440/500V
Primary Function:
DC overload and short-circuit protection
Selection Data:
6kA Ics
Standard:
IEC 60898-2; GB/T 10963.2

Product Overview

PXB6HDC-63 is a DC miniature circuit breaker 63A for 1P DC 220/250V; 2P DC 440/500V applications. It is intended for PV, telecom, energy-storage or control circuits when the DC fault study supports the rating; this describes an evaluation context, not a universal approval. Confirm the complete circuit design before specifying the product.

DC overload and short-circuit protection is distinct from adjacent protection functions. Do not infer AC/DC suitability, residual-current protection, automatic control or isolation performance from the product family name alone.

Key Features

  • DC circuit protection – Rated for DC 220/250V with 1P or DC 440/500V with 2P, as specified in the technical table.
  • Wide Current Range – Comprehensive rated currents from 1A to 63A to meet diverse application needs.
  • High Environmental Endurance – Operational temperature range from -25℃ to +70℃, suitable for harsh conditions.
  • Published pole options: 1P / 2P.
  • Published electrical context: 1P DC 220/250V; 2P DC 440/500V.
  • Primary function: DC overload and short-circuit protection.
  • Selection reference: 6kA Ics.
  • Applicable standard reference: IEC 60898-2; GB/T 10963.2.
  • Final selection must use the exact model table, drawings and installation instructions.

Typical Applications

PV, telecom, energy-storage or control circuits when the DC fault study supports the rating. Verify system voltage, expected fault current or leakage, wiring arrangement, environment, coordination and applicable rules for the ordered configuration.

 

Applications and Selection Guide

Use the verified PXB6HDC-63 records below to create a shortlist. Product labels do not replace the project calculation, coordination review or exact installation instructions.

Selection point PXB6HDC-63 reference What the project must confirm
Rated current 1–63A Design current, conductor capacity, ambient and grouping
Voltage and frequency 1P DC 220/250V; 2P DC 440/500V Supply system and equipment rating
Poles 1P / 2P Conductors to be switched, protected or isolated
Protection / control DC overload and short-circuit protection Required function and adjacent-device coordination
Fault / residual data 6kA Ics Prospective short-circuit or leakage conditions

AC vs DC Interruption

DC interruption duty is not interchangeable with AC. Confirm the model’s DC voltage, pole arrangement, Icu/Ics and wiring instructions.

DC Fault Duty
Review Circuit Protection →

Model-Specific Ratings

Use the exact technical table for rated voltage, current, poles, terminals, life and environmental limits.

Verified Data
View Technical Support →

Installation and Coordination

Check the complete circuit, conductor sizing, fault or leakage conditions, enclosure and local rules before energising.

Engineering Check
Discuss a Configuration →

Ordering Information

State model, rating, poles, system, quantity, destination market and document requirements so the configuration can be reviewed.

Project Inputs
Send Project Details →

 

Ordering Guide

  1. State the exact model: PXB6HDC-63.
  2. Provide rated current and voltage from the published technical table.
  3. Confirm poles and the required protection, isolation or control function.
  4. Provide application, expected fault/leakage conditions, destination market and quantity.
  5. List accessory, terminal, documentation and approved marking or packaging requirements.

Ordering Specification

Please specify the following when ordering:

  • Product Model: PXB6HDC-63
  • Number of Poles: 1P, 2P,
  • Rated Current : e.g., 16A
  • Rated Current (In): 1, 1.6, 2, 2.5, 3, 4, 5, 6, 8,10, 13, 16, 20, 25, 32, 40, 50, 63A
  • Quantity: e.g., 100 pcs
  • PXB6HDC-63 2P 16A 100 pcs

The quantity shown is an ordering example, not a minimum order quantity.

Installation and Coordination Checks

  • Use the exact model drawing and instructions; do not infer wiring or accessory compatibility from another product.
  • Verify conductor size, terminal torque, enclosure conditions, temperature, grouping and clearances.
  • Coordinate upstream and downstream devices and confirm the required fault, leakage or voltage response.
  • Installation, testing and maintenance must be completed by qualified personnel under applicable rules.

Type designation

CHAC PXB6HDC-63 DC Miniature Circuit Breaker - type designation

Tripping curves

CHAC PXB6HDC-63 DC Miniature Circuit Breaker - tripping curves

Dimensions(mm)

CHAC PXB6HDC-63 DC Miniature Circuit Breaker - installation dimensions in millimetres

Technical Specifications

Parameter Specification
Rated Voltage (V) 1P AC 230V/240V DC 220V/250V
2P AC 400V/415V DC 440V/500V
Rated Current (A) 1, 1.6, 2, 2.5, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63
Rated Insulation Voltage (Ui) 500V
Number of Poles 1P, 2P
Service Breaking Capacity (Ics)(kA) 6
Mechanical Endurance ≥10,000 operations
Electrical Endurance ≥1,500 operations(at rated conditions)
Termination Capacity ≤25mm²
Tightening Torque(N·m) 2.5
Protection Class IP20
Operating Temperature -25℃~+70℃
Standard IEC60898-2、GB/T 10963.2;
Certification CE·CB·CCC|DEKRA Certified

Tripping Characteristics (Reference Temperature: 30°C)

Test No. Type AC Test Current DC Test Current Initial Condition Tripping or Non-tripping Time Limits Expected Result Remarks
a B, C 1.13 In Colda t≤1h(In≤63A)
t≤2h(In>63A)
Non-tripping
b B, C 1.45 In Immediately after test a t<1h(In≤63A)
t<2h(In>63A)
Tripping Current rises steadily within 5s
c B, C 2.55 In Colda 1s≤t≤60s(In≤32A)
1s≤t≤120s(In>32A)
Tripping
d B 3 In 4 In Colda 0.1s<t<45s(In≤32A)
0.1s<t<90s(In>32A)
Tripping Close the auxiliary switch and connect the power supply.
C 5 In 7 In 0.1s<t<15s(In≤32A)
0.1s<t<30s(In>32A)
e B 5 In 10 In Colda t<0.1s Tripping Close the auxiliary switch and connect the power supply.
C 7 In 15 In

Note: The term “cold” means that the test is carried out at a reference calibration temperature without load before the test.

Why Choose CHAC

With 30+ years of manufacturing experience, 1100+ employees, 100M+ poles
annual capacity and 90% automated production, CHAC provides stable production capacity and strict
quality control for global OEM/ODM customers. Our in-house manufacturing system supports long-term
cooperation for electrical brands, importers and distributors.

Cqw2 Series Air Circuit Breaker product image
30+

YEARS EXPERIENCE

Specialized in low-voltage electrical manufacturing

Cqw2 Series Air Circuit Breaker product image
1100+

EMPLOYEES

Professional team ensures stable quality and delivery

Cqw2 Series Air Circuit Breaker product image
100M+

POLES ANNUAL CAPACITY

Large-scale production capacity to meet global demand

Cqw2 Series Air Circuit Breaker product image
90%

AUTOMATED PRODUCTION

Advanced automation for high efficiency and consistency

PXB6HDC-63 DC Miniature Circuit Breaker product image

Automated Assembly Line

PXB6HDC-63 DC Miniature Circuit Breaker product image

Testing Laboratory

PXB6HDC-63 DC Miniature Circuit Breaker product image

Injection & Stamping

PXB6HDC-63 DC Miniature Circuit Breaker product image

Quality Inspection

PXB6HDC-63 DC Miniature Circuit Breaker product image
PXB6HDC-63 DC Miniature Circuit Breaker product image
PXB6HDC-63 DC Miniature Circuit Breaker product image
PXB6HDC-63 DC Miniature Circuit Breaker product image
PXB6HDC-63 DC Miniature Circuit Breaker product image

Strict quality control system ensures every product meets global standards.

What Can We Customize?

For PXB6HDC-63 projects, CHAC can review private-label marking, packaging, approved appearance options and the published electrical configurations. Requests outside the published range require engineering evaluation, testing and feasibility review.

Pxb6Hdc 125M Dc Miniature Circuit Breaker product image

Logo & Branding

Custom logo printing, laser marking and nameplate solutions.

PXB6HDC-63 DC Miniature Circuit Breaker product image
Pxb6Hdc 125M Dc Miniature Circuit Breaker product image

Packaging
Customization

Customized color boxes, cartons, labels and manuals.

PXB6HDC-63 DC Miniature Circuit Breaker product image
Pxb6Hdc 125M Dc Miniature Circuit Breaker product image

Electrical
Customization

Current, voltage, breaking capacity, trip curve and other
special functions.

PXB6HDC-63 DC Miniature Circuit Breaker product image
Pxb6Hdc 125M Dc Miniature Circuit Breaker product image

Product
Appearance

Housing color, handle color and appearance customization.

PXB6HDC-63 DC Miniature Circuit Breaker product image
Pxb6Hdc 125M Dc Miniature Circuit Breaker product image

Certification
Support

Products comply with international standards and market
requirements.

PXB6HDC-63 DC Miniature Circuit Breaker product image
Pxb6Hdc 125M Dc Miniature Circuit Breaker product image

Engineering
Development

Drawing evaluation, prototype testing and mass production.

PXB6HDC-63 DC Miniature Circuit Breaker product image

Download

PDF

PXB6 Series Miniature Circuit Breaker

Complete product overview for low-voltage electrical components and product selection reference.

Download PDF

SUP

Need Technical Documents?

Contact us for datasheets, certificates, drawings, selection guidance or OEM/ODM project support.

Contact Us

PXB6HDC-63 Product FAQ

What is the PXB6HDC-63 used for?

The PXB6HDC-63 is specified for DC overload and short-circuit protection in 1P DC 220/250V; 2P DC 440/500V applications, within the ratings and configurations listed in its technical table. Final suitability depends on the complete circuit design.

How does the PXB6HDC-63 work?

Its operating principle follows the documented function: DC overload and short-circuit protection. Use the exact model documentation for thresholds, timing, trip behaviour, terminals and test procedures.

How do I choose the PXB6HDC-63 rating and poles?

Start with the design current and system arrangement, then choose only a published option. The page lists pole options as 1P / 2P; confirm neutral, polarity, conductors and isolation requirements.

What safety limitation applies to the PXB6HDC-63?

Do not treat the PXB6HDC-63 as a universal substitute for another device. Confirm 6kA Ics, the system voltage, fault or leakage conditions and any separate upstream protection before selection.

Can the PXB6HDC-63 be used in another circuit type?

Only when the exact ordered configuration is rated for that circuit. AC and DC duties, residual-current devices, isolators, smart controls and voltage protectors are not interchangeable by appearance or current rating.

How should the PXB6HDC-63 be installed and tested?

Use the exact product drawing, terminal identification and instructions. A qualified person should verify isolation, conductors, torque, settings, coordination and functional tests before energising the circuit.

Confirm the Right PXB6HDC-63 Configuration

Send the model, rating, poles, system voltage, application, quantity and document requirements. CHAC will review the request against the published data.