DC Circuit Breaker Sizing Calculator

Calculate DC design current and check an entered breaker against cable capacity, maximum source voltage, DC fault capability and pole-wiring confirmation.

Application example · Illustrative inputs

Reviewing a 48 V DC feeder against PXB6DC-63 data

A 3 kW DC load at 48 V draws 62.50 A, giving a 63 A reference with the factor set to 1.00. The CHAC PXB6DC-63 table includes 63 A, lists DC125V among its 1P voltage options, and declares 10 kA Icu and 7.5 kA Ics. For this example, a 60 V maximum system voltage and 5 kA fault level can be compared with those entered ratings. The result still leaves the exact voltage variant, pole diagram and source fault behavior to verify. A constant-power load operating below 48 V also needs a higher-current check.

Product data: PXB6DC-63 DC Miniature Circuit Breaker