STE1 Series High-voltage DC contactor (Square Ceramic Sealing)STE1 Series High-voltage DC contactor (Square Ceramic Sealing)
Product Features
■ Advanced Sealing Technology
•Square ceramicencapsulated design, offering superior hightemperature resistance andcorrosion protection for environments ≥1500VDC.
■ UltraHigh Voltage Support
•Operating voltage range: 750VDC to 1800VDC(e.g., STE1400).
■ HighCurrent Handling
•Rated current: 40A600A; peak breaking capacity up to 2500A (at 300VDC).
•Shortterm overload endurance (e.g., STE1600: 800A for 20 minutes).
Type designation

| Product model | Working voltage | Working current | Load polarity | Coil polarity | Auxiliary contact |
| STE1-40 | 1500 | 40 | Non-polarity | Non-polarity | / |
| STE1-60 | 1000 | 60 | Non-polarity | Non-polarity | / |
| STE1-100 | 1000 | 100 | Having polarity | Non-polarity | / |
| STE1-150 | 750 | 150 | Non-polarity | Non-polarity | / |
| STE1-200 | 750 | 200 | Having polarity | Non-polarity | / |
| STE1-L200 | 1000 | 200 | Non-polarity | Non-polarity | 1NO |
| STE1-L300 | 1000 | 300 | Non-polarity | Non-polarity | 1NO |
| STE1-X300 | 1000 | 300 | Non-polarity | Non-polarity | / |
| STE1-300 | 1000 | 300 | Having polarity | Having polarity | / |
| STE1-300D | 1500 | 300 | Non-polarity | Non-polarity | 1NO |
| STE1-350 | 1500 | 350 | Non-polarity | Having polarity | 1NO |
| STE1-400 | 1500 | 400 | Non-polarity | Non-polarity | 1NO |
| STE1-600 | 1000 | 600 | Having polarity | Having polarity | / |
Technical Specifications
| Product model | STE140 | STE160 | |
| Contact form | 1H | 1H | |
| Auxiliary contact | / | / | |
| Contact polarity | Non-polanity | Non-polanity | |
| Contact resistance | ≤5mΩ(at 40A) | ≤5mΩ(at 60A) | |
| Operating voltage | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 40A | 60A | |
| Electrical endurance | 10~1500V | 10~1000V | |
| Maximum breaking current | 400A(300VDC) | 600A(300VDC) | |
| Electrical endurance | ≥300 times(40AV1500VDC) | ≥1×10⁴times(60A/750VDC) ≥5×10³times(60A/1000VDC)“ |
|
| Current carrying | 40A:Continuous for 60A:60min 160A:10s | 60A:Continuous for 80A:20min 160A:40s | |
| Dielectric withstand voltage | Between open contacts | 3000VAC | 3000VAC |
| Between contact coils | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×105times | 2×105times | |
| Coil Voltage | 12V,24V | 12V,24V | |
| Coil power consumption | 3W | 3W | |
| Load extraction method | Internal thread | Internal thread | |
| Coil lead out method | Connector | Connector | |
| Weight | About 180g | About 180g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions/mm | 79.2×36.7×48 | 79.2×36.7×48 | |
Note:
1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:54s.
| Product model | STE1-100 | STE1-150 | STE1-200 | |
| Contact form | 1H | 1H | 1H | |
| Auxiliary contact | / | / | / | |
| Contact polarity | Having polarity | Non-polarity | Having polarity | |
| Contact resistance | ≤1mΩ(at 100A) | ≤5mΩ(at 150A) | ≤0.5mΩ(at 200A) | |
| Operating voltage | ≤75%Un | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 100A | 150A | 200A | |
| Electrical endurance | 10~1000V | 10~750V | 10~750V | |
| Maximum breaking current | 1000A(300VDC) | 1500A(300VDC) | 2000A(300VDC) | |
| Electrical endurance | ≥6×10³ times(100A/750VDC) ≥5×10³ times(100A/1000VDC) |
≥1.5×10³ times(150A/450VDC) ≥500 times(150A/750VDC) |
≥1×10³ times(200A/450VDC) ≥500 times(200A/750VDC) |
|
| Current carrying | 100A:Continuous for 120A:2h 200A:10min |
150A:Continuous for 180A:2h 225A:15min |
200A:Continuous for 250A:15min 320A:5min |
|
| Dielectric withstand voltage | Between open contacts | 3000VAC | 3000VAC | 3000VAC |
| Between contact coils | 4000VAC | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | 2×10⁵ times | |
| Coil Voltage | 12V,24V | 12V,24V | 12V,24V | |
| Coil power consumption | 4.5W | 4.5W | 6W | |
| Load extraction method | Copper bar connection | Copper bar connection | Internal thread | |
| Coil lead out method | Connector | Connector | Connector | |
| Weight | About 400g | About 400g | About 350g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 81.5×40×78.3 | 81.5×40×78.3 | 81×39×70 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Product model | STE1-L200 | STE1-L300 | |
| Contact form | 1H | 1H | |
| Auxiliary contact | 1NO | 1NO | |
| Contact polarity | Non-polarity | Non-polarity | |
| Contact resistance | ≤0.5mΩ(at 200A) | ≤0.3mΩ(at 300A) | |
| Operating voltage | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 200A | 300A | |
| Electrical endurance | 10~1000V | 10~1000V | |
| Maximum breaking current | 1000A(300VDC) | 2000A(300VDC) | |
| Electrical endurance | ≥5×10³ times(200A/450VDC) ≥1×10³ times(200A/750VDC) ≥300 times(200A/1000VDC) |
≥2×10³ times(300A/450VDC) ≥700 times(300A/750VDC) ≥300 times(300A/1000VDC) |
|
| Current carrying | 200A:Continuous for 300A:30min 400A:5min |
300A:Continuous for 450A:5min 600A:1min |
|
| Dielectric withstand voltage | Between open contacts | 4000VAC | 4000VAC |
| Between contact coils | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | |
| Coil Voltage | 12V,24V | 12V,24V | |
| Coil power consumption | 3W | 4.5W | |
| Load extraction method | Internal thread | Internal thread | |
| Coil lead out method | lead wire | lead wire | |
| Weight | About 185g | About 320g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 71.8×36×51 | 83.4×48×63.5 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Product model | STE1-X300 | STE1-300 | STE1-300D | |
| Contact form | 1H | 1H | 1H | |
| Auxiliary contact | / | / | 1NO | |
| Contact polarity | Non-polarity | Having polarity | Non-polarity | |
| Contact resistance | ≤0.5mΩ(at 300A) | ≤0.2mΩ(at 300A) | ≤0.3mΩ(at 300A) | |
| Operating voltage | ≤75%Un | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 300A | 300A | 300A | |
| Electrical endurance | 10~1000V | 10~1000V | 10~1500V | |
| Maximum breaking current | 2000A(300VDC) | 2500A(300VDC) | 2000A(300VDC) | |
| Electrical endurance | ≥1×10³ times(300A/450VDC) ≥500 times(300A/750VDC) ≥100 times(300A/1000VDC) |
≥6×10³ times(300A/750VDC) ≥3×10³ times(300A/1000VDC) |
≥1.4×10³ times(250A/800VDC) ≥1×10³ times(400A/1000VDC) ≥500 times(400A/1500VDC) |
|
| Current carrying | 300A:Continuous for 450A:5min 600A:2min |
300A:Continuous for 600A:1min 900A:10s |
400A:Continuous for 600A:1h 800A:10min |
|
| Dielectric withstand voltage | Between open contacts | 3000VAC | 3000VAC | 4000VAC |
| Between contact coils | 3000VAC | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | 2×10⁵ times | |
| Coil Voltage | 12V,24V | 12V,24V | 12V,24V | |
| Coil power consumption | 6W | Connect 46W and maintain 4.5W | 10W | |
| Load extraction method | Internal thread | Copper bar connection | Internal thread | |
| Coil lead out method | Connector | Connector | Connector | |
| Weight | About 370g | About 850g | About 700g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 88.3×42.5×74.5 | 112.6×64.7×83.9 | 98.4×45×91.5 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
| Product model | STE1-350 | STE1-400 | STE1-600 | |
| Contact form | 1H | 1H | 1H | |
| Auxiliary contact | 1NO | 1NO | / | |
| Contact polarity | The coil has polarity while the contacts have no polarity |
Non-polarity | Having polarity | |
| Contact resistance | ≤0.3mΩ(at 350A) | ≤0.2mΩ(at 400A) | ≤0.2mΩ(at 600A) | |
| Operating voltage | ≤75%Un | ≤75%Un | ≤75%Un | |
| Maximum breaking current | 400A | 400A | 600A | |
| Electrical endurance | 10~1500V | 10~1800V | 10~1500V | |
| Maximum breaking current | 2000A(300VDC) | 2500A(300VDC) | 2500A(300VDC) | |
| Electrical endurance | ≥100 times(150A/1800VDC) ≥1×10³ times(400A/1000VDC) ≥500 times(400A/1500VDC) |
≥100 times(150A/1800VDC) ≥1×10³ times(400A/1000VDC) ≥500 times(400A/1500VDC) |
≥1×10³ times(600A/750VDC) ≥500 times(600A/1000VDC) ≥100 times(600A/1500VDC) |
|
| Current carrying | 400A:Continuous for 450A:60min 600A:2min |
400A:Continuous for 450A:10min 600A:90s |
600A:Continuous for 800A:20min 1000A:5min |
|
| Dielectric withstand voltage | Between open contacts | 4000VAC | 4000VAC | 3000VAC |
| Between contact coils | 4000VAC | 4000VAC | 4000VAC | |
| Mechanical Endurance | 2×10⁵ times | 2×10⁵ times | 2×10⁵ times | |
| Coil Voltage | 12V,24V | 12V,24V | 12V,24V | |
| Coil power consumption | Connect 46W and maintain 4.5W | 10W | Connect 50W and maintain 10W | |
| Load extraction method | Internal thread | Internal thread | Internal thread | |
| Coil lead out method | Connector | Connector | lead wire | |
| Weight | About 730g | About 850g | About 1020g | |
| Vibrate | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | 10Hz~500Hz 49m/s² | |
| Humidity | 5%~85%RH | 5%~85%RH | 5%~85%RH | |
| Humidity range | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ | |
| External dimensions (mm) | 104×65×97.4 | 108×67×101.6 | 194.4×66.8×121.5 | |
Note: 1.The above parameters are all initial values,measured at room temperature of 23℃.
2.Unless otherwise specified,the electrical durability tests are conducted on resistive loads with a on/off ratio of 0.6s:5s.
Why Choose CHAC
With 30+ years of manufacturing experience, 1100+ employees, 100M+ poles
annual capacity and 90% automated production, CHAC provides stable production capacity and strict
quality control for global OEM/ODM customers. Our in-house manufacturing system supports long-term
cooperation for electrical brands, importers and distributors.
30+
YEARS EXPERIENCE
Specialized in low-voltage electrical manufacturing
1100+
EMPLOYEES
Professional team ensures stable quality and delivery
100M+
POLES ANNUAL CAPACITY
Large-scale production capacity to meet global demand
90%
AUTOMATED PRODUCTION
Advanced automation for high efficiency and consistency

Automated Assembly Line

Testing Laboratory

Injection & Stamping

Quality Inspection





Strict quality control system ensures every product meets global standards.
What Can We Customize?
CHAC supports customization of coil voltage, auxiliary contact configuration,
electrical parameters, product branding,packaging design and engineering development according to customers’ equipment and market requirements.
Coil Voltage
AC and DC coil voltage options tailored to application requirements.

Auxiliary Contacts
Flexible auxiliary contact combinations for different control functions.

Electrical Parameters
Current ratings, protection ranges and functional parameters can be customized.

Product Branding
Private label logos, nameplates and product identification support.

Packaging Design
Custom cartons, labels, manuals and packaging solutions.

Engineering Development
Support from drawing optimization to product development and application matching.

Download
STE Series High Voltage DC Contactor
Complete product overview for low-voltage electrical components and product selection reference.
Need Technical Documents?
Contact us for datasheets, certificates, drawings, selection guidance or OEM/ODM project support.
Frequently Asked Questions
Q1. Do you support product customization based on our design requirements?
A1:Absolutely. We specialize in OEM and ODM cooperation in the low-voltage electrical field and have provided customized services for many internationally renowned companies. We offer full-process support, including R&D design, parameter adjustments, and special material selection, ensuring the product fully meets your requirements.
Q2: What is your production capacity and Minimum Order Quantity (MOQ)?
A2: We operate a highly automated production base with an annual output of over 100 million poles for miniature circuit breakers. Our MOQ policy is flexible. We can provide competitive trial orders for small batches and dedicated production capacity guarantee plans.
Q3: What assurances are there for product quality and certifications?
A3: Our main products are certified with CCC, CE, CB, and more, and are sold in over 30 countries and regions worldwide. The company has established a dedicated Quality Operations Center that works with the business and production departments to implement full-process quality control, ensuring products meet international standards.
Q4: Do you have the capability for product R&D and turning concepts into reality?
A4: We have a complete R&D team and digital workshops, backed by extensive customization experience serving numerous international clients. From concept proposal and sample development to mass production, we provide end-to-end technical support to help bring your ideas to life.