Voltage Drop Calculator

Calculate resistive cable voltage drop in volts and percent for single-phase, three-phase or DC circuits. Includes the voltage drop formula and a worked example.

Application example · Illustrative inputs

Comparing cable areas on a 70 m equipment feeder

A remote ventilation load can leave a panel builder balancing cable cost against the voltage available at the equipment. For a 40 A, 400 V three-phase feeder with a 70 m one-way copper route, the calculator gives 1.33% resistive drop with 16 mm² conductors. Changing only the area to 25 mm² reduces it to 0.85%. That comparison helps review the cable schedule alongside a CHAC distribution box and its protective devices. Increasing the breaker rating will not reduce the drop; the cable’s temperature, ampacity and the upstream voltage budget must also be checked.

Product data: CQMG20C Series Distribution Box · PXB6-63 Miniature Circuit Breaker