Cable Short-Circuit Calculator

Estimate cable short-circuit withstand area with S = I√t/k using fault current, clearing time and a verified conductor k value. Compare with an installed conductor.

Application example · Illustrative inputs

Checking conductor thermal withstand against an assumed fault

For a feeder study, enter a prospective fault current of 6 kA, a clearing time of 0.15 s and k = 115, provided that k matches the conductor, insulation and temperature conditions being studied. The adiabatic calculation gives a minimum area of 20.21 mm², so a 25 mm² conductor clears this entered thermal comparison. It is not a final cable selection. When reviewing CHAC PXB6-63 or CQM6 protection, obtain the applicable clearing or let-through data: the breaker’s ampere rating and breaking capacity alone do not establish the thermal energy reaching the conductor.